3.18.7 Activation according to time bands
The unit may be managed automatically according to time bands. The time band management logic is designed to stop the
unit, to edit the setpoint and to switch among operating modes.
The parameters concerned are shown in the table.
Parameter Min
Max
UM
Description
ES1
0
144
h
Time band 1 - Start
ES2
0
144
h
Time band 1 - End
ES3
0
144
h
Time band 2 - Start
ES4
0
144
h
Time band 2 - End
ES5
0
144
h
Time band 3 - Start
ES6
0
144
h
Time band 3 - End
ES7
0
15
-
Setpoint variation - Monday
ES8
0
15
-
Setpoint variation - Tuesday
ES9
0
15
-
Setpoint variation - Wednesday
ES10
0
15
-
Setpoint variation - Thursday
ES11
0
15
-
Setpoint variation - Friday
ES12
0
15
-
Setpoint variation - Saturday
ES13
0
15
-
Setpoint variation - Sunday
ES14
-25.0
25.0
°C
Setpoint variation - Mechanical cooling - Offset
ES16
-25.0
25.0
°C
Setpoint variation - Mechanical heating - Offset
ES18
0
15
-
Unit switch-off - Monday
ES19
0
15
-
Unit switch-off - Tuesday
ES20
0
15
-
Unit switch-off - Wednesday
ES21
0
15
-
Unit switch-off - Thursday
ES22
0
15
-
Unit switch-off - Friday
ES23
0
15
-
Unit switch-off - Saturday
ES24
0
15
-
Unit switch-off - Sunday
ES26
0
144
h
Time band 4 - Start
ES27
0
144
h
Time band 4 - End
ES31
0
15
-
Heating mode activation - Monday
ES32
0
15
-
Heating mode activation - Tuesday
ES33
0
15
-
Heating mode activation - Wednesday
ES34
0
15
-
Heating mode activation - Thursday
ES35
0
15
-
Heating mode activation - Friday
ES36
0
15
-
Heating mode activation - Saturday
ES37
0
15
-
Heating mode activation - Sunday
The pairs of start and end parameters are used to set as many as 4 time bands.
Each day of the week can be matched with a combination of the set time bands in order to edit the setpoint, switch the unit
off and switch between operating modes.
The setpoint is edited within the selected time band by way of applying an offset to the active operating value.
The active operating value is given by the value set in the relevant parameter and external offsets, if any.
The offset value can be either positive or negative. When it is positive, it is added; when it is negative, it is subtracted.
Two offset values can be set: one for operation in cooling mode and one in heating mode.
If the controller manages auxiliary heating, the setpoint in parameter “STH58” is maintained when the time
bands are activated in cooling mode; when they are activated in heating mode, the setpoint varies according
to the offset value.
In order for cooling/heating switching to work with time bands, the value in parameter “SP40” must be set to
“3”.
3 Software functions
Содержание UATYA-B
Страница 1: ...Operation manual Daikin R32 Rooftops UATYA B ESIE21 02...
Страница 4: ...4 Service manual Daikin R32 Rooftops UATYA B ESIE21 02 2021 03 Page intentionally blank...
Страница 122: ...122 Service manual Daikin R32 Rooftops UATYA B ESIE21 02 2021 03 Page intentionally blank...
Страница 123: ...123 Service manual Daikin R32 Rooftops UATYA B ESIE21 02 2021 03 Page intentionally blank...
Страница 124: ...124 Service manual Daikin R32 Rooftops UATYA B ESIE21 02 2021 03 Page intentionally blank...
Страница 125: ...125 Service manual Daikin R32 Rooftops UATYA B ESIE21 02 2021 03 Page intentionally blank...
Страница 126: ...ESIE21 02 2021 03 Copyright 2021 Daikin...