
SiENBE04-808_A
Troubleshooting
Service Diagnosis
140
4.24 Refrigerant Shortage
Remote Control
Display
U0
Method of
Malfunction
Detection
Refrigerant shortage detection I:
Refrigerant shortage is detected by checking the input current value and the compressor
running frequency. If the refrigerant is short, the input current is smaller than the normal value.
Refrigerant shortage detection II:
Refrigerant shortage is detected by checking the discharge pipe temperature and the opening of
the electronic expansion valve. If the refrigerant is short, the discharge pipe temperature tends
to rise.
Refrigerant shortage detection III:
Refrigerant shortage is detected by checking the difference between suction and discharge
temperature.
Malfunction
Decision
Conditions
Refrigerant shortage detection I:
The following conditions continue for 7 minutes.
<20/25/35/42 class>
Input current × input voltage
≤
× output fre
Output frequency >
<50 class>
Input current
≤
× output fre
Output frequency >
Refrigerant shortage detection II :
The following conditions continue for 80 seconds.
Opening of the electronic expansion valve
≥
Discharge pipe temperature >
× target discharge pipe tempe
(–)
(W)
(Hz)
20/25/35 class
640/256
0
55
42 class
3446/256
–346
48
(–)
(A)
(Hz)
50 class
18/1000
0.7
55
(pulse)
(–)
(°C)
20/25/35 class
480
128/128
30
42 class
450
128/128
40
50 class
480
128/128
cooling: 20, heating: 45
SiENBE04-808_A.pdf 152
21/02/2011 13:20:03
Содержание Super Multi NX FTXS20G2V1B
Страница 13: ...SiENBE04 808_A 1 List of Functions Part 1 List of Functions 1 Functions 2 1 1 Cooling Only 2 1 2 Heat Pump 3...
Страница 17: ...SiENBE04 808_A 5 Specifications Part 2 Specifications 1 Specifications 6 1 1 Cooling Only 6 1 2 Heat Pump 9...
Страница 297: ...Outdoor Unit RK X S50G2V1B ARXS50G2V1B SiENBE04 808_A 285 Removal Procedure...