6 Installation
Installer and user reference guide
16
SERHQ020~0 SEHVX20~64BAW
Split packaged air-cooled water chiller
4P508020-1B – 2018.04
WARNING
▪ All wiring MUST be performed by an authorised
electrician and MUST comply with the applicable
legislation.
▪ Make electrical connections to the fixed wiring.
▪ All components procured on-site and all electrical
construction MUST comply with the applicable
legislation.
WARNING
ALWAYS use multicore cable for power supply cables.
5.5.2
About electrical compliance
This equipment complies with:
▪
EN/IEC 61000‑3‑11
provided that the system impedance Z
sys
is
less than or equal to Z
max
at the interface point between the user's
supply and the public system.
▪ EN/IEC
61000‑3‑11
=
European/International
Technical
Standard setting the limits for voltage changes, voltage
fluctuations and flicker in public low-voltage supply systems for
equipment with rated current ≤75 A.
▪ It is the responsibility of the installer or user of the equipment to
ensure, by consultation with the distribution network operator if
necessary, that the equipment is connected only to a supply
with a system impedance Z
sys
less than or equal to Z
max
.
▪
EN/IEC 61000‑3‑12
provided that the short-circuit power S
sc
is
greater than or equal to the minimum S
sc
value at the interface
point between the user's supply and the public system.
▪ EN/IEC
61000‑3‑12
=
European/International
Technical
Standard setting the limits for harmonic currents produced by
equipment connected to public low-voltage systems with input
current >16 A and ≤75 A per phase.
▪ It is the responsibility of the installer or user of the equipment to
ensure, by consultation with the distribution network operator if
necessary, that the equipment is connected only to a supply
with a short-circuit power S
sc
greater than or equal to the
minimum S
sc
value.
Outdoor unit
Z
max
(Ω)
Minimum S
sc
value
(kVA)
SERHQ020BAW1
0.27
838
SERHQ032BAW1
0.24
873
Indoor unit
Z
max
(Ω)
Minimum S
sc
value
(kVA)
SEHVX20BAW
0.27
820
SEHVX32BAW
0.24
874
SEHVX40BAW
0.25
1639
SEHVX64BAW
0.22
1747
The local wiring power cord must comply with IEC60245.
The wiring type in protected pipes must be H05VV; H07RN-F must
be used in unprotected pipes.
5.5.3
Cable requirements
Item
Cable
bundle
Description
Required
number of
conductors
Maximum
running
current
1
PS
Indoor unit power supply
4+GND
(b)
2
LV
Communication cable between indoor
unit and outdoor unit
2
(d)
(d)
3
LV
Standard remote controller (F1/F2)
2
(c)
4
LV
Secondary remote controller (F1/F2)
(a)
2
(c)
5
LV
Thermostat ON/OFF signal
(a)
2
(c)
6
LV
Thermostat cooling/heating signal
(a)
2
(c)
Item
Cable
bundle
Description
Required
number of
conductors
Maximum
running
current
7
LV
Operation ON signal
(a)
2
(c)
8
LV
Operation OFF signal
(a)
2
(c)
9
HV
Cooling/heating output
2
0.3 A
10
HV
Operation ON/OFF output
2
0.3 A
11
HV
Error output
2
0.3 A
12
HV
Water piping heater output
2
1 A
13
HV
Pump ON/OFF output
2
0.3 A
(a)
Optional
(b)
Refer to the nameplate on the unit or to the technical data
book.
(c)
Minimum cable section 0.75 mm
2
.
(d)
Minimum cable section 1.5 mm
2
.
PS
Power supply
LV
Low voltage
HV
High voltage
5.5.4
Safety device requirements
The power supply must be protected with the required safety
devices, i.e. a main switch, a slow blow fuse on each phase and an
earth leakage protector in accordance with the applicable legislation.
Selection and sizing of the wiring should be done in accordance with
the applicable legislation based on the information mentioned in the
table below.
INFORMATION
Multi units are standard combinations.
Outdoor unit
Recommended fuses
SERHQ020BAW1
32 A
SERHQ032BAW1
40 A
Indoor unit
Recommended fuses
SEHVX20BAW
6 A
SEHVX32BAW
10 A
SEHVX40BAW
SEHVX64BAW
NOTICE
When using residual current operated circuit breakers, be
sure to use a high-speed type 300 mA rated residual
operating current.
6
Installation
6.1
Overview: Installation
This chapter describes what you have to do and know on-site to
install the system.
Typical workflow
Installation typically consists of the following stages:
1
Mounting the outdoor unit.
2
Mounting the indoor unit.
3
Connecting the refrigerant piping.
4
Checking the refrigerant piping.
5
Charging refrigerant.
6
Connecting the water piping.
7
Connecting the electrical wiring.