Test Operation
SiUS39-601
66
Test Operation
Malfunction code
In case of an alarm code displayed on remote controller:
1.1.4 Confirmation on Normal Operation
•
Conduct normal unit operation after the check operation has been completed.
(When outdoor air temperature is 75°F or higher, the unit can not be operated with heating
mode. See the instruction manual attached.)
Confirm that the indoor/outdoor units can be operated normally.
(When an abnormal noise due to liquid compression by the compressor can be heard, stop the
unit immediately, and turn on the crankcase heater to heat up it sufficiently, then start operation
again.)
•
Operate indoor unit one by one to check that the corresponding outdoor unit operates.
•
Confirm that the indoor unit discharges cold air (or warm air).
•
Operate the air direction control button and flow rate control button to check the function of the
devices.
Cause of trouble due to faulty
installation work
Alarm
code
Countermeasure
Closed stop valve of outdoor unit
E3
E4
F3
UF
In case of RXYQ72M, 96M Single outdoor installation
Liquid side stop valve : Open
Gas side stop valve : Open
Oil equalizing pipe stop valve : Close
In case of RXYQ144M, 168M, 192M Multi outdoor installation
Liquid side stop valve : Open
Gas side stop valve : Open
Oil equalizing pipe stop valve : Open
Reversed phase in power cable
connection for outdoor unit
U1
Change connection of two wires among three for correct phasing.
Electric power for outdoor or indoor unit
is not supplied. (Including open phase)
U4
Check that the power cable for outdoor unit is connected properly.
Incorrect wiring between units
UF
Check that the wiring between units corresponds correctly to
refrigerant piping system.
Refrigerant overcharge
E3
F6
UF
Compute again optimum amount of refrigerant to be added based on
the piping length, then, collect the excessive amount by using
refrigerant collector to make the refrigerant amount proper.
Insufficient refrigerant
E4
F3
- Check that additional charging has been carried out.
- Compute again the refrigerant amount to be added based on the
piping length, and charge proper amount of refrigerant additionally.
Содержание RXYQ72
Страница 16: ...SiUS39 601 Specifications 5 Part 2 Specifications 1 Specifications 6 1 1 Outdoor Units 6 1 2 Indoor Units 11...
Страница 115: ...Field Setting SiUS39 601 104 Test Operation...
Страница 227: ...Troubleshooting OP Unified ON OFF Controller SiUS39 601 216 Troubleshooting...
Страница 231: ...Piping Diagrams SiUS39 601 220 Appendix 1 Piping Diagrams 1 1 Outdoor Unit RXYQ72M 96M...
Страница 235: ...Wiring Diagrams for Reference SiUS39 601 224 Appendix 2 2 Field Wiring RXYQ72 96MTJU C 3D042647B...
Страница 236: ...SiUS39 601 Wiring Diagrams for Reference Appendix 225 RXYQ144 168 192MTJU C 3D050353A...
Страница 239: ...Wiring Diagrams for Reference SiUS39 601 228 Appendix FXAQ07M 09M 12M 18M 24MVJU FXHQ12M 24M 36M 3D046039C 3D048116...
Страница 240: ...SiUS39 601 Wiring Diagrams for Reference Appendix 229 FXLQ12M 18M 24MVJU FXNQ12M 18M 24MVJU 3D045644A...
Страница 249: ...Example of Connection SiUS39 601 238 Appendix...
Страница 255: ...Method of Replacing The Inverter s Power Transistors and Diode Modules SiUS39 601 244 Appendix...
Страница 265: ...Precautions for New Refrigerant R 410A SiUS39 601 254 Precautions for New Refrigerant R 410A...
Страница 269: ...SiUS39 601 iv Index...