Replacement Procedure for INV Compressor, VRV (RXYQ72M, 96M)
SiUS39-601
218
Replacement Procedure for INV Compressor, VRV
1.
Replacement Procedure for INV Compressor,
VRV (RXYQ72M, 96M)
1.1
Replacement Procedure
(1) Collect the refrigerant by using refrigerant recovery
unit.
(Since the setting on outdoor unit PCB is
required for refrigerant recovery, refer to the
warning plate "Precautions in service work"
attached on the switch box cover.)
(2) Remove the sound insulator mat covering the faulty
compressor, and disconnect the power cable from
terminal board of the compressor.
(3) Disconnect the brazing sections of suction pipe and
discharge pipe by using brazing torch after the
refrigerant has been collected completely.
(4) Pinch the oil pressure equalizing pipe of the faulty
compressor at the lower part of the brazed joint as
shown in figure 1, and cut it between the pinched
section and brazed joint in order to prevent residual
oil from discharging.
(5) Remove three bolts at cushion rubber section to
take out the faulty compressor outside the unit.
(6) Check that no oil remains in the oil pressure
equalizing pipe as shown in figure 2, then remove
the cut pipe from the brazed joint with brazing torch.
(7) Install the new compressor in the unit.
(Be sure to insert the cushion rubbers before
tightening the fixing bolts of compressor.)
(8) Remove the rubber caps put on the suction and
discharge pipe of the new compressor to release the
sealing nitrogen gas.
(Take note that oil may spout due to the pipe inside
pressure if the plug put on the equalizing seat is
removed before removing of rubber cap.)
(9) Remove the plug put on the equalizing seat of the
new compressor.
(10) Install the outlet pipe on the equalizing seat of the
new compressor.
(11) Braze the equalizing seat outlet pipe to the oil
pressure equalizing pipe with brazing torch.
* Since an O-ring is put in the equalizing seat, be
sure to maintain the parts around O-ring in cool.
(12) Braze the suction and discharge pipe with brazing
torch to the compressor.
(13) Conduct air tight test to check the piping system is
free from leakage.
(14) Connect power cable to the terminal board of
compressor and cover the compressor with sound
insulator mat.
(15) Conduct vacuum drying.
(Since the setting on outdoor unit PCB is required for vacuum drying, refer to the warning plate
“Precautions in service work” attached on the switch box cover.)
(16) Charge refrigerant after the completion of vacuum drying, and check the function of
compressor with cooling or heating operation.
Suction pipe
Discharge pipe
INV
compressor
Oil equalizing
pipe
Equalizing seat
Bolts
Cushion
rubber
Brazed section
2. Cut
1. Pinch
Equalizing seat outlet pipe
Equalizing seat
Fig. 1
Oil pressure equalizing pipe
Brazed section
Cut section
Remove
* Check that no oil remains in the oil pressure
equalizing pipe before removing of the cut
pipe.
Fig. 2
Содержание RXYQ72
Страница 16: ...SiUS39 601 Specifications 5 Part 2 Specifications 1 Specifications 6 1 1 Outdoor Units 6 1 2 Indoor Units 11...
Страница 115: ...Field Setting SiUS39 601 104 Test Operation...
Страница 227: ...Troubleshooting OP Unified ON OFF Controller SiUS39 601 216 Troubleshooting...
Страница 231: ...Piping Diagrams SiUS39 601 220 Appendix 1 Piping Diagrams 1 1 Outdoor Unit RXYQ72M 96M...
Страница 235: ...Wiring Diagrams for Reference SiUS39 601 224 Appendix 2 2 Field Wiring RXYQ72 96MTJU C 3D042647B...
Страница 236: ...SiUS39 601 Wiring Diagrams for Reference Appendix 225 RXYQ144 168 192MTJU C 3D050353A...
Страница 239: ...Wiring Diagrams for Reference SiUS39 601 228 Appendix FXAQ07M 09M 12M 18M 24MVJU FXHQ12M 24M 36M 3D046039C 3D048116...
Страница 240: ...SiUS39 601 Wiring Diagrams for Reference Appendix 229 FXLQ12M 18M 24MVJU FXNQ12M 18M 24MVJU 3D045644A...
Страница 249: ...Example of Connection SiUS39 601 238 Appendix...
Страница 255: ...Method of Replacing The Inverter s Power Transistors and Diode Modules SiUS39 601 244 Appendix...
Страница 265: ...Precautions for New Refrigerant R 410A SiUS39 601 254 Precautions for New Refrigerant R 410A...