Specifications
SiUS39-601
14
Specifications
Slim Ceiling Mounted Duct Type
Notes:
★
1 Nominal cooling capacities are based on the following conditions:
Return air temperature: 80°FDB, 67°FWB
Outdoor temperature: 95°FDB
Equivalent ref. piping length: 25ft (Horizontal)
★
2 Nominal heating capacities are based on the following conditions:
Return air temperature: 70°FDB.
Outdoor temperature: 47°FDB, 43°FWB
Equivalent ref. piping length: 25ft (Horizontal)
3 Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
★
4 External static pressure is changeable to change over the connectors inside electrical box, this pressure means
"High static pressure – Standard – Low static pressure".
★
5 Anechoic chamber conversion value, measured under JISB8616 conditions. During actual operation,
these values are normally somewhat higher as a result of installation conditions.
Model
FXDQ18MVJU
FXDQ24MVJU
★
1 Cooling Capacity
Btu/h
18,000
24,000
★
2 Heating Capacity
Btu/h
20,000
27,000
Casing / Color
Galvanized Steel Plate
Galvanized Steel Plate
Dimensions: (H×W×D)
in
7-7/8
×
35-7/16
×
24-7/16
7-7/8
×
43-5/16
×
24-7/16
Coil (Cross
Fin Coil)
Rows × Stages × FPI
3
×
12
×
17
3
×
12
×
17
Face Area
ft²
1.89
2.44
Fan
Model
—
—
Type
Sirocco Fan
Sirocco Fan
Motor Output
HP
0.17
0.17
Air Flow Rate (H/L)
cfm
440/350 (H/L)
580/460 (H/L)
External Static Pressure
★
4
Pa
44-15
44-15
Drive
Direct Drive
Direct Drive
Temperature Control
Microprocessor Thermostat
for Cooling and Heating
Microprocessor Thermostat
for Cooling and Heating
Sound Absorbing Thermal Insulation Material
Foamed Polyethylene
Foamed Polyethylene
Air Filter
Removal, Washable, Mildew Proof
Removal, Washable, Mildew Proof
Piping
Connections
Liquid Pipes
in
φ
1/4 (Flare Connection)
φ
3/8 (Flare Connection)
Gas Pipes
in
φ
1/2 (Flare Connection)
φ
5/8 (Flare Connection)
Drain Pipe
in
VP20
(External Dia. 1-1/32 Internal Dia. 25/32)
VP20
(External Dia. 1-1/32 Internal Dia. 25/32)
Machine Weight (Mass)
Lbs
63
71
★
5 Sound Level (H/L)
dBA
35/31
36/32
Safety Devices
Fuse,
Thermal Protector for Fan Motor
Fuse,
Thermal Protector for Fan Motor
Refrigerant Control
Electronic Expansion Valve
Electronic Expansion Valve
Connectable outdoor unit
R-410A Series
R-410A Series
Standard Accessories
Operation Manual, Installation Manual, Paper Pattern for
Installation, Drain Hose, Clamp Metal, Insulation for Fitting,
Sealing Pads, Clamps, Screws, Washers, Conduit Mounting
Plate, Insulation Tube.
Operation Manual, Installation Manual, Paper Pattern for
Installation, Drain Hose, Clamp Metal, Insulation for Fitting,
Sealing Pads, Clamps, Screws, Washers, Conduit Mounting
Plate, Insulation Tube.
Drawing No.
C:3D051780A
Содержание RXYQ72
Страница 16: ...SiUS39 601 Specifications 5 Part 2 Specifications 1 Specifications 6 1 1 Outdoor Units 6 1 2 Indoor Units 11...
Страница 115: ...Field Setting SiUS39 601 104 Test Operation...
Страница 227: ...Troubleshooting OP Unified ON OFF Controller SiUS39 601 216 Troubleshooting...
Страница 231: ...Piping Diagrams SiUS39 601 220 Appendix 1 Piping Diagrams 1 1 Outdoor Unit RXYQ72M 96M...
Страница 235: ...Wiring Diagrams for Reference SiUS39 601 224 Appendix 2 2 Field Wiring RXYQ72 96MTJU C 3D042647B...
Страница 236: ...SiUS39 601 Wiring Diagrams for Reference Appendix 225 RXYQ144 168 192MTJU C 3D050353A...
Страница 239: ...Wiring Diagrams for Reference SiUS39 601 228 Appendix FXAQ07M 09M 12M 18M 24MVJU FXHQ12M 24M 36M 3D046039C 3D048116...
Страница 240: ...SiUS39 601 Wiring Diagrams for Reference Appendix 229 FXLQ12M 18M 24MVJU FXNQ12M 18M 24MVJU 3D045644A...
Страница 249: ...Example of Connection SiUS39 601 238 Appendix...
Страница 255: ...Method of Replacing The Inverter s Power Transistors and Diode Modules SiUS39 601 244 Appendix...