Other Control
SiUS39-601
56
Function
5.2.3 In The Case of Multi-Outdoor-Unit System (RXYQ144, 168, 192MTJU)
Automatic backup operation
With multi-outdoor-unit system, if a certain outdoor unit system malfunctions (i.e., the system
stops and indoor unit remote controller displays the malfunction), by resetting the system with the
indoor unit remote controller, the applicable outdoor unit is inhibited from operating for 8 hours,
thus making it possible to perform emergency operation automatically.
However, in the event any of the following malfunctions occurs, automatic backup operation can
be performed.
Malfunctions under which automatic backup operation can be performed:
• E3, E4, E5, E7
• F3
• H7, H9
• J2, J3, J5, J6, J7, J9, JA, JC
• L3, L4, L5, L8, L9, LC
• U2, UJ
Emergency operation with settings in service mode
∗
“Inhibition of operation” is set with each outdoor unit.
Make the following settings with the master unit. (Setting with the slave unit becomes disabled.)
∗
Discriminate the operating status of the master unit/slave units through the following LED
display.
• To inhibit the master unit from operating
→
Set setting
mode 2 from No. 38 to No. 2.
(Procedure)
(1) Press and hold the MODE button (BS1) for 5 sec. or
more.
(2) Press the SET button (BS2) 38 times.
(3) Press the RETURN button (BS3) once.
(4) Press the SET button (BS2) once.
(5) Press the RETURN button (BS3) twice.
(6) Press the MODE button (BS1) once.
• To inhibit the slave unit from operating
→
Set setting
mode 2 from No. 39 to No. 2.
(Procedure)
(1) Press and hold the MODE button (BS1) for 5 sec. or
more.
(2) Press the SET button (BS2) 39 times.
(3) Press the RETURN button (BS3) once.
(4) Press the SET button (BS2) once.
(5) Press the RETURN button (BS3) twice.
(6) Press the MODE button (BS1) once.
LED display (
7
:ON
7
7
:OFF
9
9
:Blink)
H1P---H7P H8P
(Factory set)
Master:
Slave :
77
7777777
7777 7
7777777
7777777 9
9
LED display (
7
:ON
7
7
:OFF
9
9
:Blink)
H1P---H7P
(Factory set)
7
777777
777777
7777
77777
7
777777
777779
9
77777
77779
97
7
7777777
777777
77
7777777
7777
LED display (
7
:ON
7
7
:OFF
9
9
:Blink)
H1P---H7P
(Factory set)
7
777777
777777
7777
77777
777777
777779
9
77777
77779
97
7
7777777
777777
77
7777777
7777
Содержание RXYQ72
Страница 16: ...SiUS39 601 Specifications 5 Part 2 Specifications 1 Specifications 6 1 1 Outdoor Units 6 1 2 Indoor Units 11...
Страница 115: ...Field Setting SiUS39 601 104 Test Operation...
Страница 227: ...Troubleshooting OP Unified ON OFF Controller SiUS39 601 216 Troubleshooting...
Страница 231: ...Piping Diagrams SiUS39 601 220 Appendix 1 Piping Diagrams 1 1 Outdoor Unit RXYQ72M 96M...
Страница 235: ...Wiring Diagrams for Reference SiUS39 601 224 Appendix 2 2 Field Wiring RXYQ72 96MTJU C 3D042647B...
Страница 236: ...SiUS39 601 Wiring Diagrams for Reference Appendix 225 RXYQ144 168 192MTJU C 3D050353A...
Страница 239: ...Wiring Diagrams for Reference SiUS39 601 228 Appendix FXAQ07M 09M 12M 18M 24MVJU FXHQ12M 24M 36M 3D046039C 3D048116...
Страница 240: ...SiUS39 601 Wiring Diagrams for Reference Appendix 229 FXLQ12M 18M 24MVJU FXNQ12M 18M 24MVJU 3D045644A...
Страница 249: ...Example of Connection SiUS39 601 238 Appendix...
Страница 255: ...Method of Replacing The Inverter s Power Transistors and Diode Modules SiUS39 601 244 Appendix...
Страница 265: ...Precautions for New Refrigerant R 410A SiUS39 601 254 Precautions for New Refrigerant R 410A...
Страница 269: ...SiUS39 601 iv Index...