15
|
Disposal
Installer reference guide
63
RXF50~71D5V1B
R32 split series
4P519439-18T – 2022.06
c
b
e
d
d
a
a
Gas stop valve
b
Closing direction
c
Hexagonal wrench
d
Valve cap
e
Liquid stop valve
15.3 To start and stop forced cooling
There are 2 methods to perform forced cooling.
▪
Method 1.
Using the indoor unit ON/OFF switch (if present on the indoor unit).
▪
Method 2.
Using the indoor unit user interface.
15.3.1 To start and stop forced cooling using the indoor unit ON/OFF switch
1
Press the ON/OFF switch for at least 5 seconds.
Result:
Operation will start.
INFORMATION
Forced cooling stops automatically after 15 minutes.
2
To stop operation sooner, press the ON/OFF switch.
15.3.2 To start and stop forced cooling using the indoor unit user interface
1
Set the operation mode to
cooling
. Refer to "To perform a test run" in the
installation manual of the indoor unit.
Note:
Forced cooling will stop automatically after around 30 minutes.
2
To stop operation sooner, press the ON/OFF switch.
INFORMATION
If forced cooling is used and the outside temperature is <−10°C, the safety device
may prevent operation. Warm the outside temperature thermistor on the outdoor
unit to ≥−10°C.
Result:
Operation will start.