![Daikin RXP50N5V1B Скачать руководство пользователя страница 33](http://html1.mh-extra.com/html/daikin/rxp50n5v1b/rxp50n5v1b_installers-reference-manual_2459930033.webp)
7
|
Piping installation
Installer reference guide
33
RXF50~71D5V1B
R32 split series
4P519439-18T – 2022.06
7 Piping installation
In this chapter
7.1 Preparing refrigerant piping
7.1.1 Refrigerant piping requirements
CAUTION
Piping and joints of a split system shall be made with permanent joints when inside
an occupied space except joints directly connecting the piping to the indoor units.
NOTICE
The piping and other pressure-containing parts shall be suitable for refrigerant. Use
phosphoric acid deoxidised seamless copper for refrigerant piping.
INFORMATION
Also read the precautions and requirements in the
7].
▪
Foreign materials inside pipes (including oils for fabrication) must be
≤30 mg/10 m.
Refrigerant piping diameter
Use the same diameters as the connections on the outdoor units:
Pipe outer diameter (mm)
Liquid piping
Gas piping
Ø6.4
Ø12.7
Refrigerant piping material
▪
Piping material:
phosphoric acid deoxidised seamless copper
▪
Flare connections:
Only use annealed material.
▪
Piping temper grade and thickness: