General safety precautions
Installer reference guide
14
RXF50~71D5V1B
R32 split series
4P519439-18T – 2022.06
Install power cables at least 1 meter away from televisions or radios to prevent
interference. Depending on the radio waves, a distance of 1 meter may NOT be
sufficient.
NOTICE
ONLY applicable if the power supply is three‑phase, and the compressor has an ON/
OFF starting method.
If there exists the possibility of reversed phase after a momentary black out and the
power goes ON and OFF while the product is operating, attach a reversed phase
protection circuit locally. Running the product in reversed phase can break the
compressor and other parts.