Troubleshooting
SiBE041401E
67
Service Diagnosis
4.8
Low-voltage Detection or Over-voltage Detection
Error Code
U2
Method of Error
Detection
★
Indoor Unit
The zero-cross detection of the power supply is evaluated by the indoor unit PCB.
★
Outdoor Unit
Low-voltage detection:
An abnormal voltage drop is detected by the DC voltage detection circuit.
Over-voltage detection:
An abnormal voltage rise is detected by the over-voltage detection circuit.
Error Decision
Conditions
★
Indoor Unit
There is no zero-cross detection in approximately 10 seconds.
★
Outdoor Unit
Low-voltage detection:
The voltage detected by the DC voltage detection circuit is below 150 ~ 180 V (depending on
the model).
The compressor stops if the error occurs, and restarts automatically after 3-minute standby.
Over-voltage detection:
An over-voltage signal is fed from the over-voltage detection circuit to the microcomputer.
The compressor stops if the error occurs, and restarts automatically after 3-minute standby.
Supposed
Causes
Power supply voltage is not as specified.
Defective DC voltage detection circuit
Defective over-voltage detection circuit
Defective PAM control part
Disconnection of compressor harness
Short circuit inside the fan motor winding
Noise
Momentary drop of voltage
Momentary power failure
Defective outdoor unit PCB
Defective indoor unit PCB
Содержание RXG20L2V1B
Страница 12: ...SiBE041401E 1 List of Functions Part 1 List of Functions 1 Functions 2 ...
Страница 14: ...SiBE041401E 3 Specifications Part 2 Specifications 1 Specifications 4 ...
Страница 60: ...SiBE041401E 49 Remote Controller Part 5 Remote Controller 1 Remote controller 50 ...
Страница 113: ...SiBE041401E Check Service Diagnosis 102 50 class Diode bridge R19944 ...
Страница 127: ...Revision History Month Year Version Revised contents 03 2014 SiBE041401E First edition ...