3.11.7 Discharge Pipe Thermistor Disconnection Control
Outline
The disconnection of the discharge pipe thermistor is detected by comparing the discharge pipe
temperature with the condensation temperature. If the discharge pipe thermistor is
disconnected, the electronic expansion valve opens according to the outdoor temperature and
the operation frequency, operates for a specified time, and then stops.
After 3 minutes, the operation restarts and checks if the discharge pipe thermistor is
disconnected. If the discharge pipe thermistor is disconnected, the system stops after operating
for a specified time.
If the disconnection is detected repeatedly, the system is shut down. When the compressor runs
for 60 minutes without any error, the error counter is reset.
Detail
When the starting control (cooling:
A
seconds, heating:
B
seconds) finishes, the detection timer
for disconnection of the discharge pipe thermistor (
C
seconds) starts. When the timer is over,
the following adjustment is made.
1. When the operation mode is cooling
When the following condition is fulfilled, the discharge pipe thermistor disconnection is
ascertained.
Discharge pipe tempe 6°C < outdoor heat exchanger temperature
2. When the operation mode is heating
When the following condition is fulfilled, the discharge pipe thermistor disconnection is
ascertained.
Discharge pipe tempe 6°C < indoor heat exchanger temperature
When the thermistor is disconnected
When the disconnection is ascertained, the compressor continues operation for 9 minutes and
then stops.
If the compressor stops repeatedly, the system is shut down.
3.11.8 Target Discharge Pipe Temperature Control
The target discharge pipe temperature is obtained from the indoor and outdoor heat exchanger
temperature, and the electronic expansion valve opening is adjusted so that the actual
discharge pipe temperature becomes close to the target discharge pipe temperature. (Indirect
SH (superheating) control using the discharge pipe temperature)
The electronic expansion valve opening and the target discharge pipe temperature are checked
every 20 seconds. The opening degree of the electronic expansion valve is adjusted by the
followings.
Target discharge pipe temperature
Actual discharge pipe temperature
Previous discharge pipe temperature
20/25/35 class
50 class
A
(seconds)
10
10
B
(seconds)
120
30
C
(seconds)
810
540
SC
(Subcool)
SH
(Superheat)
The target discharge pipe
temperature is set as to become
the aim SH.
The inclination does not change
depending on the operating condition.
(R18921)
Содержание RXG20L2V1B
Страница 12: ...SiBE041401E 1 List of Functions Part 1 List of Functions 1 Functions 2 ...
Страница 14: ...SiBE041401E 3 Specifications Part 2 Specifications 1 Specifications 4 ...
Страница 60: ...SiBE041401E 49 Remote Controller Part 5 Remote Controller 1 Remote controller 50 ...
Страница 113: ...SiBE041401E Check Service Diagnosis 102 50 class Diode bridge R19944 ...
Страница 127: ...Revision History Month Year Version Revised contents 03 2014 SiBE041401E First edition ...