SiBE041401E
Control Specification
Function and Control
46
3.11.1 Fully Closing with Power ON
The electronic expansion valve is initialized when turning on the power. The opening position is
set and the pressure is equalized.
3.11.2 Pressure Equalizing Control
When the compressor is stopped, the pressure equalizing control is activated. The electronic
expansion valve opens and the pressure is equalized.
3.11.3 Opening Limit Control
The maximum and minimum opening of the electronic expansion valve are limited.
The electronic expansion valve is fully closed when cooling operation stops, and is opened at a
fixed degree during defrosting.
3.11.4 Starting Operation Control
The electronic expansion valve opening is controlled when the operation starts, thus preventing
superheating or liquid compression.
3.11.5 Control when the Frequency Changes
When the target discharge pipe temperature control is active, if the target frequency changes to
a specified value in a certain time period, the target discharge pipe temperature control is
canceled and the target opening of the electronic expansion valve is changed according to the
frequency shift.
3.11.6 High Discharge Pipe Temperature Control
When the compressor is operating, if the discharge pipe temperature exceeds a certain value,
the electronic expansion valve opens and the refrigerant runs to the low pressure side. This
procedure lowers the discharge pipe temperature.
20/25/35 class
50 class
Maximum opening (pulse)
480
480
Minimum opening (pulse)
32
54
Содержание RXG20L2V1B
Страница 12: ...SiBE041401E 1 List of Functions Part 1 List of Functions 1 Functions 2 ...
Страница 14: ...SiBE041401E 3 Specifications Part 2 Specifications 1 Specifications 4 ...
Страница 60: ...SiBE041401E 49 Remote Controller Part 5 Remote Controller 1 Remote controller 50 ...
Страница 113: ...SiBE041401E Check Service Diagnosis 102 50 class Diode bridge R19944 ...
Страница 127: ...Revision History Month Year Version Revised contents 03 2014 SiBE041401E First edition ...