background image

English

2

Accessories

Accessories supplied with the outdoor unit:

Precautions for Selecting the Location

1) Choose a place solid enough to bear the weight and vibration of the unit, where the operation noise will not be amplified.

2) Choose a location where the hot air discharged from the unit or the operation noise will not cause a nuisance to the neighbors of

the user.

3) Avoid places near a bedroom and the like, so that the operation noise will cause no trouble.

4) There must be sufficient spaces for carrying the unit into and out of the site.

5) There must be sufficient space for air passage and no obstructions around the air inlet and the air outlet.

6) The site must be free from the possibility of flammable gas leakage in a nearby place.

7) Install units, power cords and inter-unit cables at least 3 meter away from television and radio sets. This is to prevent interference

to images and sounds. (Noises may be heard even if they are more than 3 meter away depending on radio wave conditions.)

8) In coastal areas or other places with salty atmosphere of sulfate gas, corrosion may shorten the life of the air conditioner.

9) Since drain flows out of the outdoor unit, do not place under the unit anything which must be kept away from moisture.

NOTE

Cannot be installed hanging from ceiling or stacked.

CAUTION

When operating the air conditioner in a low outdoor ambient tempera-

ture, be sure to follow the instructions described below.
1) To prevent exposure to wind, install the outdoor unit with its suction

side facing the wall.

2) Never install the outdoor unit at a site where the suction side may

be exposed directly to wind.

3) To prevent exposure to wind, it is recommended to install a baffle

plate on the air discharge side of the outdoor unit.

4) In heavy snowfall areas, select an installation site where the snow will not affect the unit.

(B) Drain plug (Heat pump-Models)

It is on the bottom of the packing case.

1

Construct a large canopy.
Construct a pedestal.

Install the unit high enough off the
ground to prevent burying in snow.

Содержание RXB25B5V1

Страница 1: ...INSTALLATION MANUAL R410A Split Series Models RXB25B5V1 RXB35B5V1 English Installation manual R410A Split series Montaj K lavuzu T rk e R410A Split serisi...

Страница 2: ...shape the cables so that they do not put undue force on the electrical covers or panels Install covers over the wires Incomplete cover installation may cause terminal overheating electrical shock or...

Страница 3: ...heard even if they are more than 3 meter away depending on radio wave conditions 8 In coastal areas or other places with salty atmosphere of sulfate gas corrosion may shorten the life of the air cond...

Страница 4: ...onal refrigerant required for refrigerant pipe exceeding 10m in length Be sure to add the proper amount of additional refrigerant Failure to do so may result in reduced perfomance The suggested shorte...

Страница 5: ...oundation surface Outdoor Unit Installation 1 Installing outdoor unit 1 When installing the outdoor unit refer to Precautions for Selecting the Location and the Outdoor Unit Installation Draw ings 2 I...

Страница 6: ...torque wrenches when tightening the flare nuts to prevent damage to the flare nuts and gas leakage Align the centres of both flares and tighten the flare nuts 3 or 4 turns by hand Then tighten them f...

Страница 7: ...hose which comes from gauge manifold to gas stop valve s service port 2 Fully open gauge manifold s low pressure valve Lo and completely close its high pressure valve Hi High pressure valve subsequen...

Страница 8: ...owing 1 Insulation material Polyethylene foam Heat transfer rate 0 041 to 0 052W mK 0 035 to 0 045kcal mh C Refrigerant gas pipe s surface temperature reaches 110 C max Choose heat insulation material...

Страница 9: ...force a test run to stop press the indoor unit operation stop button Using the main unit s remote controller 1 Press the operation stop button Operation will start 2 Press the temperature button and t...

Страница 10: ...that the termi nal numbers match Tighten the terminal screws securely We recommend a flathead screwdriver be used to tighten the screws The screws are packed with the terminal board Observe the notes...

Страница 11: ...G N R G Notes Refer to the nameplate of the unit for power requirements t i n u r o o d n i o T T I N U R O O D N I O T y l p p u s r e w o P Y L P P U S R E W O P e p y t y l n o g n i l o o c f o e...

Страница 12: ...operation in accordance with the operation manual to ensure that all functions and parts such as louver movement are working properly The air conditioner requires a small amount of power in its stand...

Страница 13: ...English 12...

Страница 14: ...olu turmayacak ekilde bi imlendiriniz Kablolar n zerine kapaklar monte ediniz Eksik kapak montaj kutuplar n a r s nmas elektrik arpmas veya yang na neden olabilir So utucu montaj i i s ras nda s z nt...

Страница 15: ...larda g r nt ve ses bozulmalar n nlemek i indir Radyo dalgalar n n durumuna ba l olarak 3 metreden uzakta olduklar nda da g r lt duyulabilir 8 K y b lgelerinde veya s lfat gaz i eren tuzlu atmosfer ol...

Страница 16: ...PI 4I6 7 G 87 85 F2 O B 1B O 1 2 F2 O B 1B VK2 B21 2 O 1 8 RV FHF E B B21 B2 D I B 1 21B VB B 1 2 F CF 1F B D FO B21BV I S VF F F2 B CKH B B BCB 1FE 1 I PJH K BCB B1B K K1 KVK B BH 1B B2 B 1B B 2J F E...

Страница 17: ...lay haz rlay n Temel c vatalar n uzunluklar temel y zeyinden 20mm olana kadar vidalaman z en iyisidir D nite Montaj 1 D nitenin Monte Edilmesi 1 D niteyi monte ederken Yer Se iminde nlemler ve D nite...

Страница 18: ...i y zeylerine uygulay n R410A i in so utma ya kullan n 3 Geni letme somunlar n n zarar g rmesini ve gaz ka a olu umunu engellemek i in geni letme somunlar n s k t r rken tork anahtarlar n kullan n Her...

Страница 19: ...r ld koruma taraf n gaz kapatma vana servis portuna ba lay n 2 Manometre manifoldunun d k bas n vanas n Lo t m yle a n ve y ksek bas n vanas n Hi tamamen kapat n Y ksek bas n l vanada daha sonra i le...

Страница 20: ...se imi Ticari bak r boru ve fitingler kullan rken a a dakilere dikkat edin 1 zolasyon malzemesi Polietilen k p k Is iletkenlik oran 0 041 ila 0 052W mK 0 035 ila 0 045kcal mh C So utma gaz borusunun...

Страница 21: ...k olarak durur Test al t rmas n durdurmak i in i nite al t rma durdurma d mesine bas n Cihaz n uzaktan kumandas n kullanarak 1 al t rma durdurma d mesine bas n al t rma ba lar 2 S cakl k d mesine bas...

Страница 22: ...n 20mm 2 nite ve d niteler aras nda ba lant kablolar n terminal numaralar birbirine uyacak ekilde ba lay n Terminal vidalar n iyice s k n Vidalar s kmak i in d z ba l bir tor navida kullan lmas tavsi...

Страница 23: ...Beyaz GRN Ye il YLW Sar Notlar G gereksinimleri i in nite etiketine bak n TO INDOOR UNIT niteye POWER SUPPLY G beslemesi IN CASE OF COOLING ONLY TYPE yaln zca so utma tipi kullan l yorsa OUTDOOR D CON...

Страница 24: ...areketi gibi t m i lev ve par alar n d zg n al t ndan emin olmak i in test i letimini Kullan c K lavuzuna uygun olarak ger ekle tirin Klima cihaz bekleme modunda iken az miktarda enerjiye ihtiya duyar...

Страница 25: ...12 T rk e...

Страница 26: ...1 R410A O p p p p p p p p p p p p p p p...

Страница 27: ...2 1 2 3 4 5 6 7 3 3 8 9 1 2 3 4 B 1 99 2 1 51 4 99 2 1 692 5 4 5 5 1 7 9 97 9 8 97 139 1 696 2 134...

Страница 28: ...GI KUK 4N611 20g 1 121 151 I3 K D 1IH D2 I I3 K D 1IH FO I T 2 C2M O 2IDIEC N CG C1O D2H GO 2IDIEC I D2 G 2CC 8 1K R 9 3 2 C D GIF2C C CG C1 E 3 2 C FI D 2 C2M E 2IDIEC IK CFO 2 C C DI E CG FI H CFI...

Страница 29: ...0 20 1 1 2 2 1 2 30 3 7 1 4 2 11 01 2 11 01 4 8 1 1 14 3 7 1 49 6 7 1 16 2 11 01 2 11 01 2 11 01 4 91 6 2 11 01 4 91 6 2 11 01 2 11 01 5 2 11 01 20 7 27 8 8 7 A5 9 8 25 21 A A 2 A A 0 A 23 6 A 2 7 A 7...

Страница 30: ...L 7 2 1 F C2 BF 2 F DF DP 8 E DA BE D AE80 E CE E AE E E 0 4F G8 E 6F3 G8 E 45K H4 K 9 63K5H6 K5 9 T444H37 0A R T633H6 2 0A R DP 8 E DA BE D 0 EU0E 0 E E E E AE E E 0 4F G8 E 6F3 G8 E 56K1H5 K3 9 56K1...

Страница 31: ...6 5 1 R410A 2 3 R410A 4 R410A 4 1 2 2 4 1 2 Lo Hi 3 0 1 76 1 4 Lo 2 5 6 90 5 7 8 15 10 8 278 21 8 3 8 2 8 9 8 2 9 8 2 23 9 8 2 6 1 8 2 1 0 1 529 1 8 4 2 0 1 3 1 0 3 7 8 4 2 8 8...

Страница 32: ...10 30 0 8 C1220T O 0B 2A9 959 B 4 2 9 2 9 2 B 2 5B 9 22 9 98 A9 9 A2 B 9 69 29 959 B B 7 A 2 2 99A 2 B A B A 9 9 B82 B 29 959 B B 9 91 A 1 25 5B 9 2 62 A 9 A 9 9A 0B 9 29 2 959 B 3 5B 9 2 9 9 9 2A9 9...

Страница 33: ...8 1 2 3 4 15 1 2 3 4 30 1 2 KF 1J7 BF CJ7 54F F1 JP5F 54F F1F C 7 54GR KF5 J 9 KF 1J7 9 5 1J7 54F F1...

Страница 34: ...L K D J LC 71 5K E CL 1 E7 K E2 1 L L G 25 H 1 LK 25 H 1 LC 71 5K E CL 1 E7 K E2 1 L 3 09G5K E C C7L K D J 1 2 3 1 2 3 I IDL D AI I7N R FO 1 1 H D DI5 5 1 3 I7 O J 7 OQ7 I 1 B 75I I1IK 5 331IH 7 5 A7I...

Страница 35: ...U RED BRN WHT GRN YLW TO INDOOR UNIT POWER SUPPLY IN CASE OF COOLING ONLY TYPE OUTDOOR CONDENSER DISCHARGE C5 C6 C119 DB1 DB2 DB3 FU1 FU2 FU3 IPM1 IPM2 L L1 L1R M1C M1F MR4 MR30 MRM10 MRM20 N Q1L PCB1...

Страница 36: ...11 1 1 1 1 2 1 2 26 C 28 C 20 C 24 C 3 1 2 26 C 28 C 3 1 3 2 RC...

Страница 37: ...emmelserne i 11 enligt villkoren i 12 gitt i henhold til bestemmelsene i 13 noudattaen m r yksi 14 za dodr en ustanoven p edpisu 15 prema odredbama 16 k veti a z 17 zgodnie z postanowieniami Dyrektyw...

Страница 38: ...ikineurope com 3P341265 4E 2014 01 Copyright 2014 Daikin DAIKIN ISITMA VE SO UTMA S STEMLER SAN T C A H rriyet Mah D 100 Kuzey Yanyol No 49 1 2 Kartal ISTANBUL T RK YE Tel 0216 453 27 00 Faks 0216 671...

Отзывы: