R REMQ10~16P8 + REMHQ12P8Y1B
VRVIII System air conditioner
4PW48463-1A
Installation manual
24
12.2. Checks before initial start-up
After the installation, check the following before switching on the
circuit breaker:
1
The position of the switches that require an initial setting
Make sure that switches are set according to your application
needs before turning the power supply on.
2
Power supply wiring and transmission wiring
Use a designated power supply and transmission wiring and
make sure that it has been carried out according to the
instructions described in this manual, according to the wiring
diagrams and according to local and national regulations.
3
Pipe sizes and pipe insulation
Make sure that correct pipe sizes are installed and that the
insulation work is properly executed.
4
Air tight test and vacuum drying
Make sure the air tight test and vacuum drying were completed.
5
Additional refrigerant charge
The amount of refrigerant to be added to the unit should be
written on the included "Added Refrigerant" plate and attached
to the rear side of the front cover.
6
Insulation test of the main power circuit
Measure the insulation resistance and check if the value is in
accordance with relevant local and national regulations..
7
Installation date and field setting
Be sure to keep record of the installation date on the sticker on
the rear of the upper front panel according to EN60335-2-40.
and keep record of the contents of the field setting.
12.3. Field setting
If required, carry out field settings according to the following
instructions. Refer to the service manual for more details.
Opening the switch box and handling the switches
When carrying out field settings, remove
the inspection cover (1).
Operate the switches with an insulated
stick (such as a ball-point pen) to avoid
touching live parts.
Make sure to re-attach the inspection cover (1) into the switch box
cover (2) after the job is finished.
Location of the dip switches, LEDs and buttons
LED state
Throughout the manual the state of the LEDs is indicated as follows:
Setting the push button switch (BS1~5)
Function of the push button switch which is located on the outdoor
unit PCB (A1P):
The figure shows state of the LED indications when the unit is
shipped from the factory.
Check operation procedure
1
Turn the power on for the outdoor unit and the indoor unit.
Be sure to turn the power on at least 6 hours before operation in
order to have power running to the crankcase heater.
2
Make sure that transmission is normal by checking the LED
display on the outdoor unit circuit board (A1P). (If transmission
is normal, each LED will be displayed as shown below.)
NOTE
Remark that during the first running period of the unit,
required power input may be higher than stated on the
nameplate of the unit. This phenomenon originates
from the compressor that needs elapse of a 50 hours
run in period before reaching smooth operation and
stable power consumption.
■
Make sure that the circuit breaker on the power supply
panel of the installation is switched off.
■
Attach the power wire securely.
■
Introducing power with a missing N-phase or with a
mistaken N-phase will break the equipment.
NOTE
Make sure that all outside panels, except for the panel
on the electric box, are closed while working.
Close the lid of the electric box firmly before turning on
the power.
2
1
1
LED H1~8P
2
Push button switches
BS1~BS5
3
DIP switch 1 (DS1: 1~4)
4
DIP switch 2 (DS2: 1~4)
5
DIP switch 3 (DS3: 1~2)
x
OFF
w
ON
c
Blinking
For changing the set mode
For field setting
For field setting
For test operation
For resetting the address when the wiring is changed or
when an additional indoor unit is installed
LED
display
(Default
status
before
delivery)
Micro-
computer
operation
monitor
Mode
Ready
/Error
Cooling/Heating
changeover
Low
noise
Demand
Multi
Indivi-
dual
Bulk
(master)
Bulk
(slave)
HAP
H1P
H2P
H3P
H4P
H5P
H6P
H7P
H8P
Single outdoor
unit system
c
x
x
w
x
x
x
x
x
Multiple
outdoor
unit
system
Master
unit
(a)
(a) The state of the H8P (multi) LED in a multi-system shows wich unit is the master
unit (
w
), slave 1 unit (
c
) or slave 2 unit (
x
).
Only the master unit is connected to the indoor units with interunit wiring.
c
x
x
w
x
x
x
x
w
Slave
unit
1
(a)
c
x
x
x
x
x
x
x
c
Slave
unit
2
(a)
c
x
x
x
x
x
x
x
x
1
2
4
3
5
BS2
SET
BS1
MODE
BS3
RETURN
BS4
TEST
BS5
RESET
H1P
H2P
H3P
H4P
H5P
H6P
H7P
MODE
TEST:
HWL:
IND
MASTER
SLAVE
L.N.O.P DEMAND
C/H SELECT
H8P
MULTI
BS1 MODE
BS2 SET
BS3 RETURN
BS4 TEST
BS5 RESET