Installation manual
23
R REMQ10~16P8 + REMHQ12P8Y1B
VRVIII System air conditioner
4PW48463-1A
Possible LED combinations in function of weight of additional
refrigerant charge (= x) to input;
5
Return to setting mode 1 (= initial state) by pressing the
button.
Perform a test operation as described in
"12.4. Test operation" on
page 26
.
11.7. Checks after adding refrigerant
■
Are the stop valves for both liquid and gas open?
■
Is the amount of refrigerant, that has been added, recorded?
12. B
EFORE
OPERATION
12.1.
Service precautions
Pay attention to the fan. It is dangerous to inspect the unit while the
fan is running. Be sure to turn off the main switch and to remove the
fuses from the control circuit located in the outdoor unit.
kg
H1P
H2P
H3P
H4P
H5P
H6P
H7P
0
x=0
w x
x
x
x
x
x
1
0<x<5
w x
x
x
x
x w
2
5
≤
x<10
w x
x
x
x w x
3
10
≤
x<15
w x
x
x
x w w
4
15
≤
x<20
w x
x
x w x
x
5
20
≤
x<25
w x
x
x w x w
6
25
≤
x<30
w x
x
x w w x
7
30
≤
x<35
w x
x
x w w w
8
35
≤
x<40
w x
x w x
x
x
9
40
≤
x<45
w x
x w x
x w
10
45
≤
x<50
w x
x w x w x
11
50
≤
x<55
w x
x w x w w
12
55
≤
x<60
w x
x w w x
x
13
60
≤
x<65
w x
x w w x w
14
65
≤
x<70
w x
x w w w x
15
70
≤
x<75
w x
x w w w w
16
75
≤
x<80
w x w x
x
x
x
17
80
≤
x<85
w x w x
x
x w
18
85
≤
x<90
w x w x
x w x
19
90
≤
x<95
w x w x
x w w
20
95
≤
x<100
w x w x w x
x
21
100
≤
x
w x w x w x w
NOTE
If you get confused in the middle of the input
process, press the
button to return to
setting mode 1 (= initial state).
The H1P LED is off
x
.
Resume the input procedure from step 2 onwards.
Make sure to open the stop valves after charging the
refrigerant.
Operating with the stop valves closed will damage the
compressor.
BS1 MODE
BS1 MODE
WARNING: ELECTRIC SHOCK
Caution when performing service to inverter
equipment
1
Do not open the electric box cover for 10 minutes after
the power supply is turned off.
2
Measure the voltage between terminals on the
terminal block for power supply with a tester and
confirm that the power supply is shut off.
In addition, measure the points, as shown in the figure
below, with a tester and confirm that the voltage of the
capacitor in the main circuit is less than 50 V DC.
3
To prevent damaging the PC-board, touch a
noncoated metal part to eliminate static electricity
before pulling out or plugging in connectors.
4
The performing of the service to the inverter
equipment must be started after the junction
connectors X1A, X2A, X3A, X4A (X3A and X4A are
for 16 + REYHQ12 unit type only) for the
fan motors in the outdoor unit are been pulled out. Be
careful not to touch the live parts.
(If a fan rotates due to strong wind, it may store
electricity in the capacitor or in the main circuit and
cause electric shock.)
5
After the service is finished, plug the junction
connecter back in. Otherwise the error code
E7
will be
displayed on the remote controller and normal
operation will not be performed.
For details refer to the wiring diagram labelled on the back
of the electric box cover.
NOTE
Play it safe!
For protection of the PCB, touch the switch box casing
by hand in order to eliminate static electricity from your
body before performing service.
A2P
A2P
A1P
A3P
TP1 TP2