Installation manual
13
R REMQ10~16P8 + REMHQ12P8Y1B
VRVIII System air conditioner
4PW48463-1A
Y1S~Y7S............. Solenoid valve (RMTG, 4 way valve–PPE, 4 way
valve–H/E gas, RMTL, hot gas, EV bypass,
RMTO)
Z1C~Z10C........... Noise filter (ferrite core)
Z1F...................... Noise filter (with surge absorber)
L1,L2,L3 .............. Live
N.......................... Neutral
............ Field wiring
............... Terminal strip
....................... Connector
...................... Terminal
....................... Protective earth (screw)
BLK ..................... Black
BLU ..................... Blue
BRN..................... Brown
GRN .................... Green
GRY..................... Grey
ORG .................... Orange
PNK..................... Pink
RED..................... Red
WHT .................... White
YLW..................... Yellow
8.2.
Optional parts connector
X7A ..................... Operation output (A5P)
X9A ..................... Power supply (adapter) (A5P)
8.3.
Power circuit and cable requirements
A power circuit (see table below) must be provided for connection of
the unit. This circuit must be protected with the required safety
devices, i.e. a main switch, a slow blow fuse on each phase and an
earth leakage breaker.
When using residual current operated circuit breakers, be sure to use
a high-speed type 300 mA rated residual operating current.
Point for attention regarding quality of the public electric power
supply
This equipment complies with respectively:
■
EN/IEC 61000-3-11
(1)
provided that the system impedance Z
sys
is less than or equal to Z
max
and
■
EN/IEC 61000-3-12
(2)
provided that the short-circuit power S
sc
is greater than or equal to the minimum S
sc
value
at the interface point between the user's supply and the public
system. It is the responsibility of the installer or user of the equipment
to ensure, by consultation with the distribution network operator if
necessary, that the equipment is connected only to a supply with
respectively:
■
Z
sys
less than or equal to Z
max
and
■
S
sc
greater than or equal to the minimum S
sc
value.
NOTE
■
This wiring diagram only applies to the outdoor
unit.
■
When using the option adaptor, refer to the
installation manual.
■
Refer to the installation manual, for connection
wiring to indoor-outdoor transmission F1-F2,
outdoor-outdoor transmission F1-F2,
outdoor-multi transmission Q1-Q2 and on how to
use BS1~BS5 and DS1, DS2 switch.
■
Do not operate the unit by short-circuiting
protection device S1PH~S3PH.
NOTE
■
Use copper conductors only.
■
For connection wiring to the central remote
controller, refer to the installation manual of the
central remote controller.
■
Use insulated wire for the power cord.
Phase and
frequency
Voltage
Minimum
circuit
ampere
Recommended
fuses
Transmission line
section
REYQ18
3N~ 50 Hz
400 V
40.1 A
50 A
0.75~1.25 mm
2
REYQ20
3N~ 50 Hz
400 V
41.2 A
50 A
0.75~1.25 mm
2
REYQ22
3N~ 50 Hz
400 V
44.3 A
50 A
0.75~1.25 mm
2
REYQ24
3N~ 50 Hz
400 V
45.4 A
50 A
0.75~1.25 mm
2
REYQ26
3N~ 50 Hz
400 V
53.1 A
63 A
0.75~1.25 mm
2
REYQ28
3N~ 50 Hz
400 V
54.2 A
63 A
0.75~1.25 mm
2
REYQ30
3N~ 50 Hz
400 V
63.0 A
80 A
0.75~1.25 mm
2
REYQ32
3N~ 50 Hz
400 V
63.0 A
80 A
0.75~1.25 mm
2
REYQ34
3N~ 50 Hz
400 V
71.6 A
80 A
0.75~1.25 mm
2
REYQ36
3N~ 50 Hz
400 V
72.7 A
80 A
0.75~1.25 mm
2
REYQ38
3N~ 50 Hz
400 V
75.8 A
80 A
0.75~1.25 mm
2
REYQ40
3N~ 50 Hz
400 V
76.9 A
80 A
0.75~1.25 mm
2
REYQ42
3N~ 50 Hz
400 V
84.6 A
100 A
0.75~1.25 mm
2
REYQ44
3N~ 50 Hz
400 V
85.7 A
100 A
0.75~1.25 mm
2
REYQ46
3N~ 50 Hz
400 V
94.5 A
100 A
0.75~1.25 mm
2
REYQ48
3N~ 50 Hz
400 V
94.5 A
100 A
0.75~1.25 mm
2
Phase and
frequency
Voltage
Minimum
circuit
ampere
Recommended
fuses
Transmission line
section
REYHQ16
3N~ 50 Hz
400 V
37 A
50 A
0.75~1.25 mm
2
REYHQ20
3N~ 50 Hz
400 V
50 A
63 A
0.75~1.25 mm
2
REYHQ22
3N~ 50 Hz
400 V
53.1 A
63 A
0.75~1.25 mm
2
REYHQ24
3N~ 50 Hz
400 V
63 A
80 A
0.75~1.25 mm
2
(1) European/International Technical Standard setting the limits for voltage changes,
voltage fluctuations and flicker in public low-voltage supply systems for equipment
with rated current
≤
75 A.
(2) European/International Technical Standard setting the limits for harmonic currents
produced by equipment connected to public low-voltage systems with input
current >16 A and
≤
75 A per phase.