11.6. Procedure for inputting the additional
refrigerant charge weight into the PCB
Availability of the leak detection function feature requires input of the
additional refrigerant charge amount immediately after finishing the
automatic charging. The input must be executed before performing
the test operation.
Procedure
1
Close the electric box lid and all front panels except the one on
the side of the electric box.
2
Press and hold the
button for 5 seconds to enter into
setting mode 2.
The H1P LED is on
w
.
3
Press the
button 14 times.
The LED display must be as follows:
Press the
button once as confirmation of the
LEDs combination.
LEDs will be blinking in function of the last entered setting
(factory setting = 0 kg).
4
The weighed and already recorded amount of additional
refrigerant charge (not the total amount of refrigerant present in
the system) must be entered by selecting the corresponding
LED display.
Scroll through the possible LED combinations by pressing the
button until the LED combination corresponds to the
weight of additional refrigerant charge you must input.
Select the required input by pressing the
button
and confirm the input into the PCB by pressing the
button again.
LED
display
(Default
status
before
delivery)
Micro-
computer
operation
monitor
Mode
Ready
/Error
Cooling/Heating
changeover
Low
noise
Demand
Multi
Indivi-
dual
Bulk
(master)
Bulk
(slave)
HAP
H1P
H2P
H3P
H4P
H5P
H6P
H7P
H8P
Single outdoor
unit system
c
x
x
w
x
x
x
x
x
Multiple
outdoor
unit
system
Master
unit
(a)
(a) The state of the H8P (multi) LED in a multi-system shows which unit is the master
unit (
w
), slave 1 unit (
c
) or slave 2 unit (
x
).
Only the master unit is connected to the indoor units with interunit wiring.
c
x
x
w
x
x
x
x
w
Slave
unit
1
(a)
c
x
x
x
x
x
x
x
c
Slave
unit
2
(a)
c
x
x
x
x
x
x
x
x
Error code
P8
recharge
operation
Close valve A immediately and press the TEST OPERATION
button once.
The operation will restart from the charging mode judgement
onwards.
P2
charge
hold
Close valve A immediately. Check
following items:
- Check if the gas side stop valve is
opened correctly
- Check if the valve of the refrigerant
cylinder is opened
- Check if the air inlet and outlet of the
indoor unit are not obstructed
After correcting the
abnormality, restart
the automatic
charging procedure
again.
Error code
PA
,
PH
,
PC
replace
cylinder
Close valve A and replace the empty cylinder. When renewed,
open valve A (the outdoor unit will not stop operating).
The code on the display shows the unit where a cylinder is to be
renewed:
PA
= master unit,
PH
= slave unit 1,
PC
= slave unit 2, flashing
PA
,
PH
and
PC
= all units
After recplacing the cylinder, open valve A again and continue the
work.
In case of an outdoor multi system, replacing the
refrigerant tank of the outdoor unit during the refrigerant
charging operation when the display on the remote
controller is not showing
PA
,
PH
or
PC
, may cause an
abnormal stop of the refrigerant charging operation.
P8
recharge
operation
Close valve A immediately.
Restart the automatic charging procedure again.
P2
charge
hold
Close valve A immediately. Check
following items:
- Check if the high pressure/low
pressure gas pipe, suction gas pipe,
liquid pipes and equalizer pipe stop
valves are opened correctly
- Check if the valve of the refrigerant
cylinder is opened
- Check if the air inlet and outlet of the
indoor unit are not obstructed
After correcting the
abnormality, restart
the automatic
charging procedure
again.
*
abnormal
stop
Close valve A immediately. Confirm the
malfunction code by the remote controller
and correct the abnormality by following
the
"Correcting after abnormal completion
of the test operation" on page 26
.
If a wrong value is inputted for the additional charged
refrigerant weight, the accuracy of the leak detection
function will decrease.
H1P
H2P
H3P
H4P
H5P
H6P
H7P
w x
x w w w x
BS1 MODE
BS2 SET
BS3 RETURN
BS2 SET
BS3 RETURN
BS3 RETURN