![Daikin Perfera RXM20R Скачать руководство пользователя страница 179](http://html1.mh-extra.com/html/daikin/perfera-rxm20r/perfera-rxm20r_service-manual_4700072179.webp)
4
|
Components
Service manual
179
RXM20~71R(9) + ARXM25~71R(9) + FTXM20~71R + ATXM25~50R +
FVXM25~50A
Split New Perfera R32
ESIE20-11B – 2022.02
To install the swing flap motor
1
Connect the wiring harness to the swing flap motor.
2
Install the swing flap motor on the correct location on the indoor unit. Make
sure the swing flap motor shaft is correctly inserted in the link.
b
a
c
d
a
Main swing flap
b
Secondary swing flap
c
Screw (swing flap motor fixation)
d
Swing flap motor
3
Install and tighten the screw to fix the swing flap motor.
4
Install the secondary swing flap in the indoor unit (by clicking it on).
5
Install the main swing flap in the indoor unit (by clicking it on).
6
Install the switch box, see
Is the problem solved?
Action
Yes
No further actions required.
No
Return to the troubleshooting of the
specific error and continue with the
next procedure.
To remove the swing flap motor wiring harness
Prerequisite:
Stop the unit operation via the user interface.
Prerequisite:
Turn OFF the respective circuit breaker.
Prerequisite:
Remove the required plate work, see
1
Remove the swing flap motor, see
178].
INFORMATION
The swing flap motor wiring harness is also connected to the swing raster motor.
2
Put a small drain pan (or container) under the drain hose.
3
Remove the screw from the fixation bracket and pull the drain hose
downwards to remove it from the indoor unit.