Components
Service manual
109
RXM20~71R(9) + ARXM25~71R(9) + FTXM20~71R + ATXM25~50R +
FVXM25~50A
Split New Perfera R32
ESIE20-11B – 2022.02
Does the HAP LED blink in regular
intervals (1 second ON/1 second OFF)?
Action
Yes
Return to
106] of the indoor unit
main PCB and continue with the next
procedure.
No
Replace the indoor unit main PCB, see
To check if the correct spare part is installed
Prerequisite:
First perform all earlier checks of the indoor unit main PCB, see
1
Visit your local spare parts webbank.
2
Enter the model name of your unit and check if the installed spare part
number corresponds with the spare part number indicated in the webbank.
Is the correct spare part for the indoor
unit main PCB installed?
Action
Yes
Return to
106] of the indoor unit
main PCB and continue with the next
procedure.
No
Replace the indoor unit main PCB, see
To check the wiring of the indoor unit main PCB
Prerequisite:
First perform all earlier checks of the indoor unit main PCB, see
Prerequisite:
Stop the unit operation via the user interface.
Prerequisite:
Turn OFF the respective circuit breaker.
1
Check that all wires are properly connected and that all connectors are fully
plugged‑in.
2
Check that no connectors or wires are damaged.
3
Check that the wiring corresponds with the wiring diagram, see
INFORMATION
Correct the wiring as needed.
Is the problem solved?
Action
Yes
No further actions required.
No
Return to
106] of the indoor unit
main PCB and continue with the next
procedure.
Problem solved?
After all checking procedures listed above have been performed: