![Daikin MicroTech I Скачать руководство пользователя страница 6](http://html.mh-extra.com/html/daikin/microtech-i/microtech-i_installation-and-maintenance-manual_501842006.webp)
IM 1285-4 • MICROTECH III 6 www.DaikinApplied.com
Installation
Installation
MicroTech I Display and Board Removal
Once each of the wires is labeled, unplug all wires from MCB,
Output Board, and Input Board. Leave all paired wires in their
respective plugs to keep them organized. Unscrew each of
the boards from the control panel. Remove the wires from the
back of the MT I Display. Unscrew the display and remove from
control panel.
Figure 5
below shows the control panel with all
wiring labeled and boards removed.
Figure 5: Control Panel without Components
Removing Temperature Sensors, Pressure Sensors and Pressure
Switches
The following temperature sensors will need to be removed
from the unit: DAT, RAT, MAT, EWT. Be aware and take note of
the mounting location for each of these sensors because new
sensors will be remounted and wired to the MT III MCB later on
in this manual.
If the PC5, PC7 and DHL tubing does not need replacing, then
save existing tubing. Be aware and take note of the high and
low side of pressure designations to avoid erroneous readings
after install.
Содержание MicroTech I
Страница 19: ...Appendix www DaikinApplied com 19 IM 1285 4 MICROTECH III Appendix B Figure 26 200s Wiring Diagram ...
Страница 20: ...IM 1285 4 MICROTECH III 20 www DaikinApplied com Appendix Figure 26 continued 200s Wiring Diagram ...
Страница 21: ...Appendix www DaikinApplied com 21 IM 1285 4 MICROTECH III Figure 27 800s Wiring Diagram ...
Страница 22: ...IM 1285 4 MICROTECH III 22 www DaikinApplied com Appendix Figure 27 continued 800s Wiring Diagram ...