IM 1285-4 • MICROTECH III 37 www.DaikinApplied.com
Appendix
Figure 30 continued: ATV 212 (MD2) Drive Parameters
PART NUMBER
REV
PART DESCRIPTION
170632000
B
Rooftop - MT3 SAF (set 321) PARAMETERS
Drive
Voltage
HP
Application
ATV21
ALL
ALL
SAF/RAF, RT/SC
Code
Function Description
Unit
Min. Value
Max. Value
Default
Value
New Value
Logical
Address
F471
VIA gain
1
0
255
148
471
F472
VIB bias
1
0
255
128
472
F473
VIB gain
1
0
255
148
473
F480
Exciting strengthening coefficient
1%
100
130
100
480
F481
Factory adjustment 1
1
0
9999
0
481
F482
Factory adjustment2
1
0
9999
442
482
F483
Factory adjustment3
0.1
0,0
300,0
100
483
F485
Stall cooperation gain at field weakening zone 1
1
10
250
100
485
F492
Stall cooperation gain at field weakening zone 2
1
50
150
100
492
F494
Motor adjustment factor
1
0
200
70
494
F495
Maximum voltage adjustment factor
1%
90
120
104
495
F496
Carrier change adjustment factor
0.1kHz
0,1
14,0
14
496
F500
Acceleration time 2
0.1sec
0,0
3200,0
20
500
F501
Deceleration time 2
0.1sec
0,0
3200,0
20
501
F502
Acceleration/deceleration 1 pattern
1
0
2
0
502
F503
Acceleration/deceleration 2 pattern
1
0
2
0
503
F504
Acceleration/deceleration selection (1/2/3)
1
1
2
1
504
F505
Acceleration/deceleration 1 and 2 switching frequency
0.01Hz
0,00
60,00
0
505
F506
S-pattern lower-limit adjustment amount
1%
0
50
10
506
F507
S-pattern upper-limit adjustment amount
1%
0
50
10
507
F601
Stall prevention level 1
1%
10
111
110
601
F602
Inverter trip retention selection
1
0
1
0
602
F603
Emergency stop selection
1
0
2
0
603
F604
Emergency DC braking time
0.1sec
0,0
20,0
1
604
F605
Output phase failure detection mode selection
1
0
5
3
5
605
F607
Motor 150%-overload time limit
1sec
10
2400
300
607
F608
Input phase failure detection mode selection
1
0
1
1
608
F609
Hysteresis for small current detection
1%
1
20
10
609
F610
Low current trip/alarm
1
0
1
0
610
F611
Small current detection current
1%
0
100
0
611
F612
Small current detection time
1sec
0
255
0
612
F613
Detection of output short-circuit during start-up
1
0
3
0
613
F615
Over-torque trip/alarm selection
1
0
1
0
615
F616
Over-torque detection level
1%
0
250
130
616
F618
Over-torque detection time
0.1sec
0,0
10,0
0.5
618
F619
Over-torque detection level hysteresis
1%
0
100
10
619
F621
Cumulative operation time alarm setting
0.1
0,0
999,9
610
621
F626
Over-voltage stall protection level
1%
100
150
140
626
F627
Under-voltage trip/alarm selection
1
0
2
0
627
F632
Thermal memory selection
1
0
1
0
632
F633
Trip at VIA low level input mode
1%
0
100
0
633
F634
Annual avg ambient temp (calculation for life alarms)
1
1
6
3
634
F645
Selection of PTC thermal
1
0
2
0
645
F646
Detection level of PTC
1ohm
100
9999
3000
646
F650
Rorced/Fire-speed control selection
1
0
1
0
650
F691
Inclination characteristic of analog output
1
0
1
1
691
F692
Meter bias
1%
0
100
0
692
F700
Prohibition of change of parameter settings
1
0
1
0
700
F701
Unit selection
1
0
1
1
701
F702
Free unit selection
0.01
0,00
200,00
0
702
F705
Inclination characteristic of free unit display
1
0
1
1
705
ATV21 MT3 SAF PAGE 3
Содержание MicroTech I
Страница 19: ...Appendix www DaikinApplied com 19 IM 1285 4 MICROTECH III Appendix B Figure 26 200s Wiring Diagram ...
Страница 20: ...IM 1285 4 MICROTECH III 20 www DaikinApplied com Appendix Figure 26 continued 200s Wiring Diagram ...
Страница 21: ...Appendix www DaikinApplied com 21 IM 1285 4 MICROTECH III Figure 27 800s Wiring Diagram ...
Страница 22: ...IM 1285 4 MICROTECH III 22 www DaikinApplied com Appendix Figure 27 continued 800s Wiring Diagram ...