IM 1285-4 • MICROTECH III 34 www.DaikinApplied.com
Appendix
Appendix E
Figure 29: Parameters
On the PC exactly…
Appears as…
Paramete
r
MCT 10 Noun
MCT 10 value
Keypad Menu-then drop
Keypad Noun
Keypad Value
Comments
0-03
Regional Settings
North America
start at 0-0* Basic Settings
0-03 Regional Settings
[1] North America
Required change to allow many 60 Hz settings
1-21
Motor Power [HP]
enter dataplate value
start at 1-** Load and Motor
1-21 Motor Power [HP]
enter dataplate value
FACTORY ENTER
1-22
Motor Voltage
enter dataplate value
start at 1-** Load and Motor
1-22 Motor Voltage
enter dataplate value
FACTORY ENTER
1-23
Motor Frequency
60Hz
start at 1-** Load and Motor
1-23 Motor Frequency
60Hz
Almost always 60 Hz
1-25
Motor Nominal Speed
1760
start at 1-** Load and Motor
1-25 Motor Nominal Speed
1760
1760 is close, motor nameplate may be different.
1-73
Flying Start
Enabled
start at 1-** Load and Motor
1-73 Flying Start
[1] Enabled
3-02
Minimum Reference
00.00
start at 3-0* Reference Limits
3-02 Minimum Reference
00.000
Modbus comms controls the lowest motor speed.
3-04
Reference Function
Sum
start at 3-0* Reference Limits
3-04 Reference Function
[0] Sum
Sum of all presets-Writes via modbus to parameter 3-
10. Others will be zero.
3-15
Reference 1 Source
No Function
start at 3-1* References
3-15 Reference 1 Source
[0] No function
Duct Static P1: Signal between 53 & 55. Set switch
A53 to ON for ma.
3-16
Reference 2 Source
No Function
start at 3-1* References
3-16 Reference 2 Source
[0] No Function
Duct Static P2: Signal between 54 & 55. Set switch
A54 to ON for ma.
3-17
Reference 3 Source
No Function
start at 3-1* References
3-17 Reference 3 Source
[0] No Function
3-41
Ramp 1 Ramp Up Time
60.00
start at 3-4* Ramp 1
3-41 Ramp 1 Ramp Up Time
60.00s
3-42
Ramp 1 Ramp Down Time 60.00
start at 3-4* Ramp 1
3-42 Ramp 1 Ramp Down Time 60.00s
5-01
Terminal 27 Mode
Input
start at 5-00 Digital I/O mode
5-01 Terminal 27 mode
[0] Input
Contacts between 27 and 12.
5-02
Terminal 29 Mode
Output
start at 5-00 Digital I/O mode
5-02 Terminal 27 mode
[1] Output
If not [1] then 5-31 is locked-out.
5-12
Terminal 27 Digital Input
External Interlock
start at 5-1* Digital Inputs
5-12 Terminal 27 Digital Input
[7] External Interlock
5-14
Terminal 32 Digital Input
Fire Mode
start at 5-1* Digital Inputs
5-14- Terminal 32 Digital Input
[37] Fire Mode
5-15
Terminal 33 Digital input
No Operation
start 5-1* Digital Inputs
5-15 Terminal 33 Digital Input
[0] No Operation
5-31
Terminal 29 Digital Output No Operation
start 5-3* Digital Outputs
5-31 Terminal 29 Digital Output
[60] Comparator 0
Must set 5-02 first, then 13-10, 13-11, and 13-12, then
5-31 last.
8-30
Protocol
FC (required for write to drive) start at 8-3* FC Port Settings
8-30 Protocol
[2] RTU Modbus
Change via keypad, power cycle required. Wired
+@#68, -@ #69, Shield at #61
8-31
Address
1 (found at default)
start at 8-3* FC Port Settings
8-31 Address
[1]SAF,[2]RAF,[3]EXH
Change via keypad, power cycle required. Choose
MT3 address of VFD to be controlled
8-32
Baud rate
9600 Baud (found at default)
start at 8-3* FC Port Settings
8-32 Baud rate
[3] 19200 Baud
Change via keypad, power cycle required. 19,200
required for MT3 coms
8-33
Parity / Stop Bits
Even Parity,1 Stop Bit (at default)
start at 8-3* FC Port Settings
8-33 Parity, Stop Bits
[3] No Parity, 2 Stop Bits
Change via keypad, power cycle required. Required
for MT3 comms
8-35
Minimum Response Delay need to enter new value = 100 start at 8-3* FC Port Settings
8-35 Minimum Response Delay
100ms
MT3 best operation this setting
8-50
Protocol
Logic OR (default)
8-50* Digital Bus
8-50 Coasting Select
[3] Logic OR
MT3 best operation this setting
8-53
Start Select
Logic OR (default)
8-50* Digital Bus
8-53 Start Select Logic OR
[3] Logic OR
Modbus OR Input 53
13-10 .00
Comparator Operand
Alarm Number
Comparators-1 13-1*
13-10 Comparator Operand
[20] Alarm Number
Set 5-02 first, then 13-10, then 13-11 next
13-11 .0
Comparator Operator
(equal)
Comparators-1 13-1*
13-11 Comparator Operator
[1] = (equal)
Set 13-10 first, then 13-11, then 13-12 next
13-12 .0
Comparator Value
60.000
Comparators-1 13-1*
13-12 Comparator Value
60.000
Set 13-11 first, then 13-12, then 5-31 last
Switch- TERM .
Set to IN at highest address of 8-31
Set to IN at highest address of 8-31
Switch A53
set to = I
set to = I
Switch is behind keypad.
Switch A54
set to = I
set to = I
Switch is behind keypad.
IMPORTANT NOTES:
Technical assistance from Danfoss 414-365-8639, cell 414-704-8997; Ken Fonstad or others .
"Numeric" keypads only display the parameter value as a number, it is not followed by words as the "Graphical" keypad displays .
Yellow shaded parameters are unique to MT3 controls and MODBUS communications
Light Green shaded parameters are general in nature, some are FACTORY set from motor dataplate values .
Danfoss FC102 drives are configured for FC port communications "out of the box" . Use a PC and the MCT 10 software which performs a WRITE to DRIVE that downloads all except
the Modbus communications parameters into the drive . Additional instructions are
Change the Communication parameters 8-30, 8-31, 8-32, & 8-33 with the keypad . Cycle the power .
If unit will not communicate, FC102 terminals 68 & 69 might be accidently exchanged .
Keypad Password access parameters are 0-60, 0-61, 0-65 & 0-66 . Full Access is normal . Graphic keypads can "transport" parameters to other drives . Use parameter 0-50 = [2]
Copt All From LCP . Use 0-50 = [1] to Copt All TO LCP . Numeric keypads cannot do this copy operation . .
P:\Engineering\ENG_data\AFD PARAMETER SOURCE FILES\170632800.xls
MT3 FC102 All Modbus
Содержание MicroTech I
Страница 19: ...Appendix www DaikinApplied com 19 IM 1285 4 MICROTECH III Appendix B Figure 26 200s Wiring Diagram ...
Страница 20: ...IM 1285 4 MICROTECH III 20 www DaikinApplied com Appendix Figure 26 continued 200s Wiring Diagram ...
Страница 21: ...Appendix www DaikinApplied com 21 IM 1285 4 MICROTECH III Figure 27 800s Wiring Diagram ...
Страница 22: ...IM 1285 4 MICROTECH III 22 www DaikinApplied com Appendix Figure 27 continued 800s Wiring Diagram ...