IM 1285-4 • MICROTECH III 36 www.DaikinApplied.com
Appendix
Figure 30 continued: ATV 212 (MD2) Drive Parameters
PART NUMBER
REV
PART DESCRIPTION
170632000
B
Rooftop - MT3 SAF (set 321) PARAMETERS
Drive
Voltage
HP
Application
ATV21
ALL
ALL
SAF/RAF, RT/SC
Code
Function Description
Unit
Min. Value
Max. Value
Default
Value
New Value
Logical
Address
F207
Frequency setting mode selection 2
1
1
5
2
207
F210
VIB input point 1 setting
1%
0
100
0
210
F211
VIB input point 1 frequency
0.01Hz
0,00
200,00
0
211
F212
VIB input point 2 setting
1%
0
100
100
212
F213
VIB input point 2 frequency
0.01Hz
0,00
200,00
50
213
F240
Starting frequency setting
0.01Hz
0,50
10,00
0.5
240
F241
Operation starting frequency
0.01Hz
0,00
80,00
0
241
F242
Operation starting frequency hysteresis
0.01Hz
0,00
80,00
0
242
F250
DC braking starting frequency
0.01Hz
0,00
80,00
0
250
F251
DC braking current
1%
0
100
50
251
F252
DC braking time
0.1sec
0,0
20,0
1
252
F256
Time limit for lower-limit frequency operation
0.1sec
0,0
600,0
0
256
F264
Input from external contacts-UP response time
0.1sec
0,0
10,0
0.1
264
F265
Input from external contacts-UP frequency step width
0.01Hz
0,00
80,00
0.1
265
F266
Input from external contacts-DOWN response time
0.1sec
0,0
10,0
0.1
266
F267
Input from external contacts-DOWN freq step width
0.01Hz
0,00
80,00
0.1
267
F268
Initial value of UP/DOWN frequency
0.01Hz
0,00
60,00
0
20
268
F269
Saving of changed value of UP/DOWN frequency
1
0
1
1
269
F270
Jump frequency 1
0.01Hz
0,00
80,00
0
270
F271
Jump width 1
0.01Hz
0,00
30,00
0
271
F272
Jump frequency 2
0.01Hz
0,00
80,00
0
272
F273
Jump width 2
0.01Hz
0,00
30,00
0
273
F274
Jump frequency 3
0.01Hz
0,00
80,00
0
274
F275
Jump width 3
0.01Hz
0,00
30,00
0
275
F294
Preset-speed operation frequency 15
0.01Hz
0,00
60,00
50
294
F295
Selection of bumpless
1
0
1
1
295
F300
PWM carrier frequency
0.1kHz
6,0
16,0
300
F301
Auto-restart control selection
1
0
4
3
301
F302
Regeneration power ride-through control (Deceleration stop)
1
0
2
0
302
F303
Retry selection (number of times)
1
0
10
3
5
303
F305
Over-voltage limit operation (Slowdown stop mode selection)
1
0
3
2
305
F307
Supply voltage correction (limitation of output voltage)
1
0
3
3
307
F311
Reverse-run prohibition
1
0
2
1
311
F312
Random mode
1
0
1
0
312
F316
Carrier frequency control mode selection
1
0
3
1
316
F320
Drooping gain
1%
0
100
0
320
F323
Drooping insensitive torque band
1%
0
100
10
323
F359
PID control waiting time
1sec
0
2400
0
359
F360
PID control
1
0
2
0
360
F362
Proportional gain
0.01
0,01
100,00
0.3
362
F363
Integral gain
0.01
0,01
100,00
0.2
363
F366
Differential gain
0.01
0,00
2,55
0
366
F400
Auto-tuning
1
0
2
0
400
F401
Slip frequency gain
1%
0
150
50
401
F402
Motor constant #1 (primary resistance)
0.10%
0,0
30,0
402
F415
Motor rated current
0.1A
0,1
200,0
415
F416
Motor no-load current
1%
10
100
416
F417
Motor rated speed
1min-1
100
15000
417
F418
Speed control response coefficient
1
1
150
40
418
F419
Speed control stability coefficient
1
1
100
20
419
F470
VIA bias
1
0
255
128
470
ATV21 MT3 SAF PAGE 2
Содержание MicroTech I
Страница 19: ...Appendix www DaikinApplied com 19 IM 1285 4 MICROTECH III Appendix B Figure 26 200s Wiring Diagram ...
Страница 20: ...IM 1285 4 MICROTECH III 20 www DaikinApplied com Appendix Figure 26 continued 200s Wiring Diagram ...
Страница 21: ...Appendix www DaikinApplied com 21 IM 1285 4 MICROTECH III Figure 27 800s Wiring Diagram ...
Страница 22: ...IM 1285 4 MICROTECH III 22 www DaikinApplied com Appendix Figure 27 continued 800s Wiring Diagram ...