NOTE: If supply voltage is 208V, lead on primary 

of transformer(s) must be moved from the 240V 

to the 208V tap. Refer to wiring diagram on unit 

for details.

Main power wiring should be sized for the minimum circuit 

ampacity shown on the unit’s database.  Size wires in 

accordance with the ampacity tables in 

Article 310 of the 

National Electrical Code.  If long wires are required, it 

may be necessary to increase the wire size to prevent 

excessive voltage drop.  Wires should be sized for a 

maximum of 3% voltage drop.

Branch Circuit 

Ampacity

15

20

25

30

35 40 45 50

SUPPLY WIRE 

LENGTH - FEET

200

6

4

4

4

3

3

2

2

150

8

6

6

4

4

4

3

3

100

10

8

8

6

6

6

4

4

50

14

12 10 10

8

8

6

6

Wiring Table

CAUTION

To avoid risk of property damage, personal 

injury or fire, use only copper conductors.

CAUTION

Label all wires prior to disconnection when 

servicing controls. Wiring errors can cause 

improper and dangerous operation. Verify 

proper operation after servicing. 

NOTE: A weather-tight disconnect switch, 

properly sized for the unit total load, must be 

field or factory installed.  An external field 

supplied disconnect may be mounted on the 

exterior panel.

Ensure the data plate is not covered by the field-supplied 

disconnect switch.

• 

  Some disconnect switches are not fused.  Protect 

the power leads at the point of distribution in 

accordance with the unit data plate.

•   The unit must be electrically grounded in accordance 

with local codes or, in the absence of local codes, 

with the latest edition of the National Electrical Code 

ANSI/NFPA 70, and/or the Canadian Electrical Code, 

CSA C22.1, Part 1.  A ground lug is provided for this 

purpose.  Do not use the ground lug for connecting a 

neutral conductor.

• 

  Connect power wiring to the electrical power block 

located within the main control box.

Control Box

control box Connections

note: depending on the options installed, the 

location of the components may vary in some 

models. 

WARNING

Failure of unit due to operation on improper 

line voltage or with excessive phase unbalance 

constitutes product abuse and will void your 

warranty and may cause severe damage to the 

unit electrical components.

Areas Without Convenience Outlet

It is recommended that an independent 115V power source 

be brought to the vicinity of the roof top unit for portable 

lights and tools used by the service mechanic.

NOTE: Refer to local codes for requirements. 

These outlets can also be factory installed.

Units installed on Roof Tops

Main power and low voltage wiring may enter the unit 

through the condenser end of unit or through the roof curb. 

Install conduit connectors at the desired entrance locations.  

External connectors must be weatherproof.  All holes in the 

unit base must be sealed (including those around conduit 

Содержание M Series

Страница 1: ...N THIS MANUAL SHOULD SERVICE THE EQUIPMENT THE MANUFACTURER WILL NOT BE RESPONSIBLE FOR ANY INJURY OR PROPERTY DAMAGE ARISING FROM IMPROPER SERVICE OR SERVICE PROCEDURES IF YOU SERVICE THIS UNIT YOU A...

Страница 2: ...MENT PARTS Ordering Parts When reporting shortages or damages or ordering repair parts give the complete unit model and serial numbers as stamped on the unit s nameplate Replacement parts for this app...

Страница 3: ...ng or installing this unit Multiple power sources may be present Failure to do so may cause property damage personal injury or death WARNING To prevent the risk of property damage personal injury or d...

Страница 4: ...ly within 5 days 4 File the claim with the following supporting documents a Original Bill of Lading certified copy or indemnity bond b Original paid freight bill or indemnity in lieu thereof c Origina...

Страница 5: ...ses have holes under the outdoor coil to permit drainage of defrost water accumulation The unit must be situated to permit free unobstructed drainage of the defrost water and ice A minimum of 2 cleara...

Страница 6: ...36 minimum clearance is required between the condenser coils Adequate clearance around the unit should be kept for safety service maintenance and proper unit operation A clearance of 48 is recommende...

Страница 7: ...bserved when installing the unit Provisions for forks have been included in the unit base frame No other fork locations are approved Unit must be lifted by the four lifting holes located at the base f...

Страница 8: ...is unit Multiple power sources may be present Failure to do so may cause property damage personal injury or death WARNING HIGH VOLTAGE To avoid personal injury or death due to electrical shock do not...

Страница 9: ...t the power leads at the point of distribution in accordance with the unit data plate The unit must be electrically grounded in accordance with local codes or in the absence of local codes with the la...

Страница 10: ...ever connecting thermostat wires to terminals on sub base DO NOT use larger than 18 AWG wire A transition to 18 AWG wire may be required before entering thermostat sub base NOTE Refer to unit wiring d...

Страница 11: ...must first be performed in accordance with this manual Damage or repairs due to failure to comply with these requirements are not covered under the warranty After the machines are used for temporary h...

Страница 12: ...airflow setting to be between 300 and 500 CFM per ton see Table below For models with electric heat the total airflow must not be less than that required for operation of the electric heaters See App...

Страница 13: ...quid small line near liquid line access fitting with adequate contact and insulate for best possible reading 3 Check subcooling and superheat System should have a subcooling and superheat within the r...

Страница 14: ...operation if outdoor ambient is mild If the outdoor ambient is low and the unit operates properly in the heating cycle you may check the pressure cutout operation by blocking off the indoor return air...

Страница 15: ...surfaces of the outdoor coil under certain weather conditions of temperature and relative humidity Therefore it is necessary to reverse the flow of the refrigerant to provide hot gas in the outdoor co...

Страница 16: ...for Electrical Failure 1 Place unit into the cooling mode Test for 24 volts at the solenoid If there is no voltage present at coil check the control voltage 2 If voltage is present loosen the nut on...

Страница 17: ...be made at least every two months more often if necessary because of local conditions and usage Dirty throwaway filters should be discarded and replaced with a new clean filter Disposable return air f...

Страница 18: ...18 Wiring Example Electric Heat Wiring Example...

Страница 19: ...2080 939 0 74 0 4 2056 952 0 75 0 6 1973 1000 0 79 0 6 1967 1003 0 79 0 8 1887 1048 0 83 0 8 1890 1051 0 83 T3 0 2 2176 878 0 69 T3 0 2 2145 902 0 71 0 4 2080 939 0 74 0 4 2056 952 0 75 0 6 1973 1000...

Страница 20: ...2 6 5 119 129 125 150 134 148 150 150 7 2 6 5 142 155 150 175 6 9 1 0 3 3 5 Direct Drive Standard Static 1 GPH1660M 208 230 1 60 1 26 9 152 9 EH 1S15 11 3 15 0 54 2 62 5 EH 1S20 15 0 20 0 72 2 83 3 EH...

Страница 21: ...RB LOCATION EMBOSS FOR THRU THE BASE UTILITIES RETURN 11 X 25 SUPPLY 12 X 17 Horizontal Discharge Vertical Discharge NOTE Refer to IOD 7082 included in the literature pack for installing horizontal du...

Страница 22: ...lectric Heater Heater Type X Staged S SCR modulating Voltage 1 208 230 1 60 Single phase 60 Hz Chassis S Small Kilowatt 5 5 kW 10 10 kW 15 15 kW 18 18 KW 20 20 kW 30 30 kW EH S05 5 1500 EH S10 10 1500...

Страница 23: ...1 F1 BK RD 208 230V 1PH 60Hz L1 L2 T1 T2 C S CM BR RD GR BK GR RD FB3 F3 F3 5 BK RD RD YL BR BK PU BK RD PU BK 5 L1 L2 T1 T2 BK BC COMP RC COM H F PU PU CMC L1 L2 T1 T2 FB2 F2 F2 BK RD BK RD BK PU BR...

Страница 24: ...LP Liquid Propane Residential Package Outdoor Section ELECTRICAL Supply Voltage Measure L1 and L2 Voltage L1 L2 Compressor Amps Condenser Fan Amps PRESSURES TEMPERATURES Suction Circuit Pressure Suct...

Страница 25: ...25 THIS PAGE INTENTIONALLY LEFT BLANK...

Страница 26: ...26 THIS PAGE INTENTIONALLY LEFT BLANK...

Страница 27: ...27 THIS PAGE INTENTIONALLY LEFT BLANK...

Страница 28: ...OODMAN BRAND AMANA BRAND GOODMAN BRAND AMANA BRAND PRODUCT REGISTRATION Thank you for your recent purchase Though not required to get the protection of the standard warranty registering your product i...

Отзывы: