manualshive.com logo in svg
background image

5

Proper installation of the unit ensures trouble-free 

operation. Improper installation can result in problems 

ranging from noisy operation to property or equipment 

damages, dangerous conditions that could result in injury 

or personal property damage and that are not covered by 

the warranty. Give this booklet to the user and explain it’s 

provisions. The user should retain these instructions for 

future reference.

•   To avoid possible illness or death of the building 

occupants, do NOT locate outside air intake device 

(economizer, manual fresh air intake, motorized 

fresh air intake) too close to an exhaust outlet, gas 

vent termination, or plumbing vent outlet. For specific 

distances required, consult local codes.

• 

  Allow minimum clearances from the enclosure for 

fire protection, proper operation, and service access 

(see unit clearances). These clearances must be 

permanently maintained.

• 

  When the unit is heating, the temperature of the 

return air entering the unit must be a minimum of 55° 

F.

Ground Level Installations Only:

• 

  When the unit is installed on the ground adjacent 

to the building, a level concrete (or equal) base is 

recommended. Prepare a base that is 3” larger than 

the package unit footprint and a minimum of 3” thick.

• 

  The base should also be located where no runoff of 

water from higher ground can collect in the unit.

• 

 Consider the effect of outdoor fan noise on 

conditioned space and any adjacent occupied 

space.  It is recommended that the unit be placed so 

that condenser air discharge does not blow toward 

windows less than 25 feet away.

•  The unit should be set on a solid, level foundation 

– preferably a concrete slab at least 4 inches 

thick.  The slab should be above ground level and 

surrounded by a graveled area for good drainage.  

Any slab used as a unit’s foundation should not 

adjoin the building as it is possible that sound and 

vibration may be transmitted to the structure.

Heat Pumps require special location consideration in areas 

of heavy snow accumulation and/or areas with prolonged 

continuous subfreezing temperatures.  Heat pump unit 

bases have holes under the outdoor coil to permit drainage 

of defrost water accumulation.  The unit must be situated to 

permit free unobstructed drainage of the defrost water and 

ice.  A minimum of 2” clearance under the outdoor coil is 

required in milder climates.  See FIGURE 1: HEAT PUMP 

ELEVATION CHART. 

Heat Pump Elevation Chart

Design Temperature Suggested Minimum Elevation

+15° and above

2 ½”

-5° to +14°

8”

Below -5°

12”

Figure 1: Heat Pump Elevation Chart

Roof top Installations Only:

•   To avoid possible property damage or personal 

injury, the roof must have sufficient structural 

strength to carry the weight of the unit(s) and snow 

or water loads as required by local codes.  Consult 

a structural engineer to determine the weight 

capabilities of the roof.

• 

  The unit may be installed directly on wood floors 

or on Class A, Class B, or Class C roof covering 

material.

• 

  To avoid possible personal injury, a safe, flat surface 

for service personnel should be provided.

•   Adequate clearances from the unit to any adjacent 

public walkways, adjacent buildings, building 

openings or openable windows must be maintained 

in accordance with National Codes. 

Unit Precautions

• 

  Do not stand or walk on the unit.

• 

  Do not drill holes anywhere in panels or in the base 

frame of the unit except where indicated.  Unit 

access panels provide structural support.

•   Do not remove any access panels until unit has been 

installed on roof curb or field supplied structure.

• 

  Do not roll unit across finished roof without prior 

approval of owner or architect.

•   Do not skid or slide on any surface as this may 

damage unit base.  The unit must be stored on a flat, 

level surface.  Protect the condenser coil because it 

is easily damaged.

CAUTION

All curbs look similar, to avoid incorrect curb 

positioning, check job plans carefully and verify 

markings on curb assembly. Instructions may 

vary in curb styles and supersedes information 

shown.

Roof Curb Installations Only:

Curb installations must comply with local codes and should 

be done in accordance with the established guidelines of 

the National Roofing Contractors Association.

Proper unit installation requires that the roof curb be firmly 

and permanently attached to the roof structure.  Check for 

adequate fastening method prior to setting the unit on the 

curb.

Содержание M Series

Страница 1: ...N THIS MANUAL SHOULD SERVICE THE EQUIPMENT THE MANUFACTURER WILL NOT BE RESPONSIBLE FOR ANY INJURY OR PROPERTY DAMAGE ARISING FROM IMPROPER SERVICE OR SERVICE PROCEDURES IF YOU SERVICE THIS UNIT YOU A...

Страница 2: ...MENT PARTS Ordering Parts When reporting shortages or damages or ordering repair parts give the complete unit model and serial numbers as stamped on the unit s nameplate Replacement parts for this app...

Страница 3: ...ng or installing this unit Multiple power sources may be present Failure to do so may cause property damage personal injury or death WARNING To prevent the risk of property damage personal injury or d...

Страница 4: ...ly within 5 days 4 File the claim with the following supporting documents a Original Bill of Lading certified copy or indemnity bond b Original paid freight bill or indemnity in lieu thereof c Origina...

Страница 5: ...ses have holes under the outdoor coil to permit drainage of defrost water accumulation The unit must be situated to permit free unobstructed drainage of the defrost water and ice A minimum of 2 cleara...

Страница 6: ...36 minimum clearance is required between the condenser coils Adequate clearance around the unit should be kept for safety service maintenance and proper unit operation A clearance of 48 is recommende...

Страница 7: ...bserved when installing the unit Provisions for forks have been included in the unit base frame No other fork locations are approved Unit must be lifted by the four lifting holes located at the base f...

Страница 8: ...is unit Multiple power sources may be present Failure to do so may cause property damage personal injury or death WARNING HIGH VOLTAGE To avoid personal injury or death due to electrical shock do not...

Страница 9: ...t the power leads at the point of distribution in accordance with the unit data plate The unit must be electrically grounded in accordance with local codes or in the absence of local codes with the la...

Страница 10: ...ever connecting thermostat wires to terminals on sub base DO NOT use larger than 18 AWG wire A transition to 18 AWG wire may be required before entering thermostat sub base NOTE Refer to unit wiring d...

Страница 11: ...must first be performed in accordance with this manual Damage or repairs due to failure to comply with these requirements are not covered under the warranty After the machines are used for temporary h...

Страница 12: ...airflow setting to be between 300 and 500 CFM per ton see Table below For models with electric heat the total airflow must not be less than that required for operation of the electric heaters See App...

Страница 13: ...quid small line near liquid line access fitting with adequate contact and insulate for best possible reading 3 Check subcooling and superheat System should have a subcooling and superheat within the r...

Страница 14: ...operation if outdoor ambient is mild If the outdoor ambient is low and the unit operates properly in the heating cycle you may check the pressure cutout operation by blocking off the indoor return air...

Страница 15: ...surfaces of the outdoor coil under certain weather conditions of temperature and relative humidity Therefore it is necessary to reverse the flow of the refrigerant to provide hot gas in the outdoor co...

Страница 16: ...for Electrical Failure 1 Place unit into the cooling mode Test for 24 volts at the solenoid If there is no voltage present at coil check the control voltage 2 If voltage is present loosen the nut on...

Страница 17: ...be made at least every two months more often if necessary because of local conditions and usage Dirty throwaway filters should be discarded and replaced with a new clean filter Disposable return air f...

Страница 18: ...18 Wiring Example Electric Heat Wiring Example...

Страница 19: ...2080 939 0 74 0 4 2056 952 0 75 0 6 1973 1000 0 79 0 6 1967 1003 0 79 0 8 1887 1048 0 83 0 8 1890 1051 0 83 T3 0 2 2176 878 0 69 T3 0 2 2145 902 0 71 0 4 2080 939 0 74 0 4 2056 952 0 75 0 6 1973 1000...

Страница 20: ...2 6 5 119 129 125 150 134 148 150 150 7 2 6 5 142 155 150 175 6 9 1 0 3 3 5 Direct Drive Standard Static 1 GPH1660M 208 230 1 60 1 26 9 152 9 EH 1S15 11 3 15 0 54 2 62 5 EH 1S20 15 0 20 0 72 2 83 3 EH...

Страница 21: ...RB LOCATION EMBOSS FOR THRU THE BASE UTILITIES RETURN 11 X 25 SUPPLY 12 X 17 Horizontal Discharge Vertical Discharge NOTE Refer to IOD 7082 included in the literature pack for installing horizontal du...

Страница 22: ...lectric Heater Heater Type X Staged S SCR modulating Voltage 1 208 230 1 60 Single phase 60 Hz Chassis S Small Kilowatt 5 5 kW 10 10 kW 15 15 kW 18 18 KW 20 20 kW 30 30 kW EH S05 5 1500 EH S10 10 1500...

Страница 23: ...1 F1 BK RD 208 230V 1PH 60Hz L1 L2 T1 T2 C S CM BR RD GR BK GR RD FB3 F3 F3 5 BK RD RD YL BR BK PU BK RD PU BK 5 L1 L2 T1 T2 BK BC COMP RC COM H F PU PU CMC L1 L2 T1 T2 FB2 F2 F2 BK RD BK RD BK PU BR...

Страница 24: ...LP Liquid Propane Residential Package Outdoor Section ELECTRICAL Supply Voltage Measure L1 and L2 Voltage L1 L2 Compressor Amps Condenser Fan Amps PRESSURES TEMPERATURES Suction Circuit Pressure Suct...

Страница 25: ...25 THIS PAGE INTENTIONALLY LEFT BLANK...

Страница 26: ...26 THIS PAGE INTENTIONALLY LEFT BLANK...

Страница 27: ...27 THIS PAGE INTENTIONALLY LEFT BLANK...

Страница 28: ...OODMAN BRAND AMANA BRAND GOODMAN BRAND AMANA BRAND PRODUCT REGISTRATION Thank you for your recent purchase Though not required to get the protection of the standard warranty registering your product i...

Отзывы: