APPENDIX A BLOWER PERFORMANCE TABLES - HEAT PUMP
APPENDIX A BLOWER PERFORMANCE TABLES – HEAT PUMP
5 TON HEAT PUMP
Standard Static Drive
Model: GPHM56041
Horizontal Flow
Down Flow
Speed
Tap
External
Static
Pressure
(ESP), in w.c.
SCFM
RPM
BHP
Speed
Tap
External
Static
Pressure
(ESP), in w.c.
SCFM
RPM
BHP
T1
0.2
1372
665
0.20
T1
0.2
1380
664
0.20
0.4
1259
734
0.23
0.4
1262
735
0.23
0.6
1133
813
0.25
0.6
1132
811
0.25
0.8
1016
888
0.27
0.8
1006
884
0.27
T2
0.2
2176
878
0.69
T2
0.2
2145
902
0.71
0.4
2080
939
0.74
0.4
2056
952
0.75
0.6
1973
1000
0.79
0.6
1967
1003
0.79
0.8
1887
1048
0.83
0.8
1890
1051
0.83
T3
0.2
2176
878
0.69
T3
0.2
2145
902
0.71
0.4
2080
939
0.74
0.4
2056
952
0.75
0.6
1973
1000
0.79
0.6
1967
1003
0.79
0.8
1887
1048
0.83
0.8
1890
1051
0.83
T4
0.2
2234
960
0.86
T4
0.2
2293
950
0.85
0.4
2162
1003
0.9
0.4
2195
995
0.89
0.6
2101
1042
0.83
0.6
2112
1042
0.93
0.8
2053
1073
0.96
0.8
2034
1088
0.97
T5
0.2
2300
982
0.93
T5
0.2
2364
971
0.92
0.4
2222
1025
0.98
0.4
2274
1019
0.97
0.6
2170
1061
1.01
0.6
2190
1063
1.01
0.8
2120
1095
1.04
0.8
2113
1110
1.06
Shaded area indicates air flow below 1500 SCFM (300 SCFM/ton) that