3-29
No.
Evaporator inlet sensor
Evaporator outlet sensor
Compressor suction gas sensor
Back-up operation
EIS
EOS
SGS
1
Normal
Normal
Normal
superheat control
2
Normal
Normal
Abnormal
superheat control
3
Normal
Abnormal
Normal
Liquid refrigerant back prevention
to compressor by EIS and SGS
4
Normal
Abnormal
Abnormal
Expansion valve fixed
opening rate control
5
Abnormal
Normal
Normal
Liquid refrigerant back prevention to
compressor by EOS and SGS
6
Abnormal
Normal
Abnormal
Expansion valve fixed
opening rate control
7
Abnormal
Abnormal
Normal
Expansion valve fixed
opening rate control
8
Abnormal
Abnormal
Abnormal
Expansion valve fixed
opening rate control
●
Back-up for temperature sensors (EIS, EOS, SGS) at frozen mode (superheat control)
03̲LXE10E100以降(27-32)̲E.qx 08.8.22 10:28 AM ページ 3-29