SiENBE04-925_A
Main Functions
Function and Control
25
1.5
Automatic Operation
Outline
Automatic Cooling / Heating Function
When the AUTO mode is selected with the remote control, the microcomputer automatically
determines the operation mode as cooling or heating according to the room temperature and
the set temperature at start-up, and automatically operates in that mode.
The unit automatically switches the operation mode to maintain the room temperature at the set
temperature.
Detail
Ts: set temperature (set by remote control)
Tt: target temperature (determined by microcomputer)
Tr: room thermistor temperature (detected by room temperature thermistor)
C: correction value
1. The set temperature (Ts) determines the target temperature (Tt).
(Ts = 18 ~ 30°C).
2. The target temperature (Tt) is calculated as;
Tt = Ts + C
where C is the correction value
.
C = 0°C
3. Thermostat ON/OFF point and mode switching point are as follows.
Tr means the room thermistor temperature.
1
Heating
→
Cooling switching point:
Tr
≥
Tt + 2.5°C
2
Cooling
→
Heating switching point:
Tr < Tt – 2.5°C
3
Thermostat ON/OFF point is the same as the ON/OFF point of cooling or heating
operation.
4. During initial operation
Tr
≥
Ts: Cooling operation
Tr < Ts: Heating operation
Ex: When the target temperature is 25°C
Cooling
→
23°C: Thermostat OFF
→
22°C: Switch to heating
Heating
→
26.5°C: Thermostat OFF
→
27.5°C: Switch to cooling
(R11893)
Target tempe 2.5°C
Heating Operation
Target temperature – 2.5°C
Cooling Operation
Target tempe 1.5°C
= Thermostat OFF
Target temperature – 2.0°C
= Thermostat OFF
SIENBE04-925_A_FRONT.pdf 39
24/02/2011 13:53:51
Содержание Inverter FTXL20G2V1B
Страница 8: ...SiENBE04 925_A vi Table of Contents...
Страница 14: ...Introduction SiENBE04 925_A xii...
Страница 15: ...SiENBE04 925_A List of Functions 1 Part 1 List of Functions 1 Functions 2...
Страница 17: ...SiENBE04 925_A Specifications 3 Part 2 Specifications 1 Specifications 4...
Страница 20: ...Specifications SiENBE04 925_A 6 Specifications...
Страница 186: ...SiENBE04 925_A Outdoor Unit RXL20G2V1B Removal Procedure 171 4 Feature of the thermistors Step Procedure Points R9356...