Troubleshooting
SiENBE04-925_A
80
Service Diagnosis
Troubleshooting
Check No.01
Refer to P.118
Turn off the power supply
and disconnect the fan
motor connector, then
turn the power on.
Check No.01
Check the output of the
fan motor connector
YES
YES
NO
YES
YES
NO
NO
NO
Note : The motor may break when the
motor connector is disconnected
while remaining power supply.
(Turn off the power supply before
connecting the connector also.)
Caution
Replace the indoor
fan motor.
Replace the indoor
unit PCB.
Replace the indoor
unit PCB.
Does the fan
rotate smoothly?
Does the
fan rotate?
Is the
motor power
supply voltage 310 ~
340 VDC generated?
Is the
motor control
voltage 15 VDC
generated?
Turn off the power supply
and rotate the fan by hand.
Turn the power on and
start operation.
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Check No.01
Check the output of the
fan motor connector
(R12033)
NO
YES
YES
NO
YES
NO
Replace the indoor
fan motor.
Replace the indoor
unit PCB.
Replace the indoor
unit PCB.
Replace the indoor
fan motor.
Replace the indoor
fan motor and the
indoor unit PCB.
Is the rotation
pulse generated?
Is the
rotation
command voltage 1
~ 6 VDC
generated?
Is the rotation
pulse generated?
Stop the fan motor.
SIENBE04-925_A_FRONT.pdf 95
24/02/2011 13:53:56
Содержание Inverter FTXL20G2V1B
Страница 8: ...SiENBE04 925_A vi Table of Contents...
Страница 14: ...Introduction SiENBE04 925_A xii...
Страница 15: ...SiENBE04 925_A List of Functions 1 Part 1 List of Functions 1 Functions 2...
Страница 17: ...SiENBE04 925_A Specifications 3 Part 2 Specifications 1 Specifications 4...
Страница 20: ...Specifications SiENBE04 925_A 6 Specifications...
Страница 186: ...SiENBE04 925_A Outdoor Unit RXL20G2V1B Removal Procedure 171 4 Feature of the thermistors Step Procedure Points R9356...