Check
SiENBE04-925_A
124
Service Diagnosis
5.1.12 Rotation Pulse Check on the Outdoor Unit PCB
Check No.15
RXL20-35G2V1B
Make sure that the voltage of 320 ± 30 V is applied.
1. Set operation off and power off. Disconnect the connector S70.
2. Check that the voltage between the pins 4 - 7 is 320 VDC.
3. Check that the control voltage between the pins 3 - 4 is 15 VDC.
4. Check that the rotation command voltage between the pins 2 - 4 is 0 ~ 15 VDC.
5. Keep operation off and power off. Connect the connector S70.
6. Check whether 2 pulses (0 ~ 15 VDC) are output at the pins 1 - 4 when the fan motor is
rotated 1 turn by hand.
When the fuse is melted, check the outdoor fan motor for proper function.
If NG in step 2
→
Defective PCB
→
Replace the outdoor unit PCB.
If NG in step 4
→
Defective Hall IC
→
Replace the outdoor fan motor.
If OK in both steps 2 and 4
→
Replace the outdoor unit PCB.
RXL20G2V1B9
1. Check that the voltage between the pins 10 - 11 is 15 VDC.
2. Check if the Hall IC generates the rotation pulse (0 ~ 15 VDC) 4 times between the pins 10 -
12, 10 - 13, when the fan motor is manually rotated once.
1
2
3
4
5
6
7
320 VDC
(R10811)
S70
PCB
Actual rotation pulse output (0 ~ 15VDC)
Rotation command pulse input (0 ~ 15VDC)
15 VDC
13
12
11
10
9
8
7
6
5
4
3
2
1
S70
Phase U
15 VDC
Phase V
Phase W
HU (Hall IC)
HV (Hall IC)
Free pin
Free pin
Free pin
Free pin
Free pin
Free pin
(R11907)
SIENBE04-925_A_FRONT.pdf 139
24/02/2011 13:53:58
Содержание Inverter FTXL20G2V1B
Страница 8: ...SiENBE04 925_A vi Table of Contents...
Страница 14: ...Introduction SiENBE04 925_A xii...
Страница 15: ...SiENBE04 925_A List of Functions 1 Part 1 List of Functions 1 Functions 2...
Страница 17: ...SiENBE04 925_A Specifications 3 Part 2 Specifications 1 Specifications 4...
Страница 20: ...Specifications SiENBE04 925_A 6 Specifications...
Страница 186: ...SiENBE04 925_A Outdoor Unit RXL20G2V1B Removal Procedure 171 4 Feature of the thermistors Step Procedure Points R9356...