FXSQ20~125M8V3B
VRV System air conditioners
4PW25083-1C

Installation and operation manual

4

The outdoor unit is charged with refrigerant.

Be sure to use both a spanner and torque wrench together when
connecting or disconnecting pipes to/from the unit.

Refer to 

Table 1

 for the dimensions of flare nut spaces and the

appropriate tightening torque. (Overtightening may damage the
flare and cause leaks.)

Table 1

When connecting the flare nut, coat the flare both inside and
outside with ether oil or ester oil and initially tighten by hand 3 or
4 turns before tightening firmly.
Coat here with ether oil or ester oil

Check the pipe connector for gas leaks, then insulate it.

D

RAIN

 

PIPING

 

WORK

Rig the drain piping as shown in the figure and take measures
against condensation. Improperly rigged piping could lead to leaks
and eventually wet furniture and belongings.

1

Install the drain pipes.

-

Keep piping as short as possible and slope it downwards so 
that air may not remain trapped inside the pipe.

-

Keep pipe size equal to or greater than that of the connecting 
pipe (vinyl pipe of 25 mm nominal diameter and 32 mm outer 
diameter).

-

Use the supplied drain hose and metal clamp. Tighten the 
clamp firmly.

Insulate the drain hose inside the building.

If the drain hose cannot be sufficiently set on a slope, fit the
hose with drain raising piping (field supply).

HOW TO PERFORM PIPING 

(See figure 8)

Connect the drain hose to the drain raising pipes, and insulate
them.

Connect the drain hose to the drain pipe on the indoor unit, and
tighten it with the metal clamp.

-

To ensure a downward slope of 1:100, install hanging bars 
every 1 to 1.5 m.

-

If unifying multiple drain pipes, install the pipes as shown in 

figure 9

.

2

After piping work is finished, check if drainage flows smoothly.

-

Open the water inlet lid, add approximately 1 l of water 
gradually and check the drainage flow. 

(See figure 10)

1

Torque wrench

2

Spanner

3

Piping union

4

Flare nut

Pipe 

gauge

Tightening torque

Flare dimension 

A (mm)

Flare shape

Ø6.4

14.2~17.2 N•m 

(144~176 kgf•cm)

8.7~9.1

Ø9.5

32.7~39.9 N•m 

(333~407 kgf•cm)

12.8~13.2

Ø12.7

49.5~60.3 N•m 

(504~616 kgf•cm)

16.2~16.6

Ø15.9

61.8~75.4 N•m 

(630~770 kgf•cm)

19.3~19.7

1

Liquid pipe

2

Gas pipe

3

Insulation for fitting of liquid line 
(supplied with the unit)

4

Insulation for fitting of gas line 
(supplied with the unit)

5

Clamps (use 2 clamps per 
insulation)

1

Hanging bar

1

2

4

3

R=0.4~0.8

45

° ±

2

90

°±

2

A

5

3

1

2

4

1-1.5 m

1

1

Metal clamp

2

Drain hose

3

White tape (field 
supply)

1

Ceiling slab

2

Hanging bar

3

Adjustable range

4

Drain hose (supplied with the unit)

5

Metal clamp (supplied with the unit)

6

Drain raising pipe (field supply)

Installation

A

Rear suction installation

275

When canvas duct is installed

350-530

When air inlet panel is directly installed

275

1

Multiple drain piping

1

Water inlet

2

Portable pump

3

Water inlet lid

4

Bucket (adding water from water inlet)

5

Drain outlet for maintenance (with rubber drain plug)

6

Refrigerant pipes

2

1

3

Содержание FXSQ100M8V3B

Страница 1: ...INSTALLATION AND OPERATION MANUAL FXSQ20M8V3B FXSQ25M8V3B FXSQ32M8V3B FXSQ40M8V3B FXSQ50M8V3B FXSQ63M8V3B FXSQ80M8V3B FXSQ100M8V3B FXSQ125M8V3B System air conditioners...

Страница 2: ...2 5 6 7 4 3 4 4 1 3 2 4 5 5 5 2 1 2 3 6a 6a 2 3 1 4 680 85 6b 6b 1 3 2 4 6 5 50 200 45 680 6c 6c 1 5 2 3 7 4 680 65 3 3 1 4 3 4 2 800 630 B A 145 7c 7c 4 2 2 3 1 460 180 350 A 8 8 1 1 5m 0 625mm 2 6...

Страница 3: ...e z naszymi instrukcjami 18 sunt n conformitate cu urm torul urm toarele standard e sau alt e document e normativ e cu condi ia ca acestea s fie utilizate n conformitate cu instruc iunile noastre 19 s...

Страница 4: ...air contains high levels of salt such as air near the ocean and where voltage fluctuates a lot e g in factories Also in vehicles or vessels When selecting the installation site use the supplied paper...

Страница 5: ...nerated even if 1 meter is kept 2 Use suspension bolts for installation Check whether the ceiling is strong enough to support the weight of the indoor unit If there is a risk reinforce the ceiling bef...

Страница 6: ...The paper pattern for installation corresponds with the measurements of the ceiling opening Consult the builder for details Attach the paper pattern for installation to the unit with the attached scre...

Страница 7: ...ee figure 8 Connect the drain hose to the drain raising pipes and insulate them Connect the drain hose to the drain pipe on the indoor unit and tighten it with the metal clamp To ensure a downward slo...

Страница 8: ...matched the system may cause a malfunction Electrical characteristics MCA Min circuit Amps A MFA Max Fuse Amps A KW Fan Motor Rated Output kW FLA Full Load Amps A Specifications for field supplied fus...

Страница 9: ...he remote controller 6 Never connect the power supply wiring to the terminal board for transmission wiring This mistake could damage the entire system 7 Use only specified wires and tightly connect wi...

Страница 10: ...to define time between 2 filter cleaning display indications When contamination is high setting can be changed to half the time inbetween 2 filter cleaning display indications Ultra long life filter L...

Страница 11: ...esent unhook the chains 2 Remove the air filters Remove the air filters by pulling their cloth upward rear suction or backward bottom suction 3 Clean the air filter Use vacuum cleaner A or wash the ai...

Страница 12: ...fter cleaning the air filter make sure to attach it Turn on the main power supply switch The control panel display lights when the power is turned on To protect the unit turn on the main power switch...

Страница 13: ...H ADAPTOR FOR WIRING RyC RyF MAGNETIC RELAY RyH MAGNETIC RELAY J1EH F1U F2U FUSE 250 V 5 A X1A X2A CONNECTOR WIRING ADAPTOR X1M TERMINAL STRIP CONNECTOR FOR OPTIONAL PARTS X16A CONNECTOR WIRING ADAPTO...

Страница 14: ...NOTES NOTES...

Страница 15: ...4 2 1 13 13 2 2 1 14 14 L N IN D OUT D F1 F2 F1 F2 Control box LN P1 P2 P1 P2 F1 F2 T1 T2 LN P1 P2 F1 F2 T1 T2 LN P1 P2 F1 F2 T1 T2 LN P1 P2 F1 F2 T1 T2 P1 P2 P1 P2 2 4 5 3 1 16 16 IN D OUT D F1 F2 F1...

Страница 16: ...Zandvoordestraat 300 B 8400 Oostende Belgium 4PW25083 1C...

Отзывы: