FXSQ20~125M8V3B
VRV System air conditioners
4PW25083-1C

Installation and operation manual

6

W

IRING

 

EXAMPLE

 

AND

 

HOW

 

TO

 

SET

 

THE

 

REMOTE

 

CONTROLLER

How to connect wiring

From the outside of the unit

Remove the switch box cover as shown in 

figure 11b

, and make the

connections.

From the inside of the unit

Remove the small bottom plate and the interchangeable plate (in
case of rear suction) or the air filter holding plate (in case of bottom
suction). Lower the switch box as shown in 

figure 11c

Put the wires

through the wiring ports of the switch box cover before connecting
them.

PRECAUTIONS

1

Observe the notes mentioned below when wiring to the power
supply terminal board.

-

Do not connect wires of different gauge to the same power 
supply terminal. (Looseness in the connection may cause 
overheating.)

-

When connecting wires of the same gauge, connect them 
according to the figure.

2

Keep total current of crossover wiring between indoor units less
than 12 A. Branch the line outside the terminal board of the unit
in accordance with electrical equipment standards, when using
two power wiring of a gauge greater than 2 mm

2

 (Ø1.6).

The branch must be sheathed in order to provide an equal or
greater degree of insulation as power supply wiring itself.

3

Do not connect wires of different gauge to the same grounding
terminal. Looseness in the connection may deteriorate the
protection.

4

Remote controller cords and wires connecting the units should
be located at least 50 mm away from power supply wiring. Not
following this guideline may result in malfunction due to
electrical noise.

5

For the remote controller wiring, refer to the "Installation manual
of the remote controller" supplied with the remote controller.

6

Never connect the power supply wiring to the terminal board for
transmission wiring. This mistake could damage the entire
system.

7

Use only specified wires and tightly connect wires to the
terminals. Be careful that wires do not place external stress on
the terminals. Keep wiring in neat order so that they do not
obstruct other equipment such as popping open the switch box
cover. Make sure the cover closes tight. Incomplete connections
could result in overheating, and in the worse case, electric shock
or fire.

Setting of static pressure changeover connector

According to the systems static pressure requirement, reposition
the adaptors of the PC board inside the switch box as shown in
the figure.

W

IRING

 

EXAMPLE

Fit the power supply wiring of each unit with a switch and fuse as
shown in 

figure 19

.

Complete system example (3 systems)

When using 1 remote controller for 1 indoor unit (Normal operation)

(See figure 12)

For group control or use with 2 remote controllers 

(See figure 14)

When including BS unit 

(See figure 16)

1

Small bottom plate

2

Air filter holding plate

3

Switch box

4

Interchangeable plate

5

Square hole (covered by the switch box cover)

FXSQ20~63

FXSQ80~125

Low

not available

Standard

High

1

Black wire

2

Blue wire

NOTE

The unit is factory set for standard static pressure
(X4A) at the time of shipping.

1

Power supply

2

Main switch

3

Power supply wiring

4

Transmission wiring

5

Switch

6

Fuse

7

BS unit REYQ only

8

Indoor unit

9

Remote controller

1

Outdoor unit

2

Indoor unit

3

Remote controller (optional accessories)

4

Most downstream indoor unit

5

For use with 2 remote controllers

6

BS unit

NOTE

It is not necessary to designate an indoor unit address
when using group control. The address is
automatically set when the power is activated.

X6A

X7A

X5A

X4A

X3A

1

2

X6A

X7A

X5A

X4A

X3A

1

2

X7A

X4A

X3A

1

2

X6A

X7A

X5A

X4A

X3A

1

2

X7A

X4A

X3A

1

2

Содержание FXSQ100M8V3B

Страница 1: ...INSTALLATION AND OPERATION MANUAL FXSQ20M8V3B FXSQ25M8V3B FXSQ32M8V3B FXSQ40M8V3B FXSQ50M8V3B FXSQ63M8V3B FXSQ80M8V3B FXSQ100M8V3B FXSQ125M8V3B System air conditioners...

Страница 2: ...2 5 6 7 4 3 4 4 1 3 2 4 5 5 5 2 1 2 3 6a 6a 2 3 1 4 680 85 6b 6b 1 3 2 4 6 5 50 200 45 680 6c 6c 1 5 2 3 7 4 680 65 3 3 1 4 3 4 2 800 630 B A 145 7c 7c 4 2 2 3 1 460 180 350 A 8 8 1 1 5m 0 625mm 2 6...

Страница 3: ...e z naszymi instrukcjami 18 sunt n conformitate cu urm torul urm toarele standard e sau alt e document e normativ e cu condi ia ca acestea s fie utilizate n conformitate cu instruc iunile noastre 19 s...

Страница 4: ...air contains high levels of salt such as air near the ocean and where voltage fluctuates a lot e g in factories Also in vehicles or vessels When selecting the installation site use the supplied paper...

Страница 5: ...nerated even if 1 meter is kept 2 Use suspension bolts for installation Check whether the ceiling is strong enough to support the weight of the indoor unit If there is a risk reinforce the ceiling bef...

Страница 6: ...The paper pattern for installation corresponds with the measurements of the ceiling opening Consult the builder for details Attach the paper pattern for installation to the unit with the attached scre...

Страница 7: ...ee figure 8 Connect the drain hose to the drain raising pipes and insulate them Connect the drain hose to the drain pipe on the indoor unit and tighten it with the metal clamp To ensure a downward slo...

Страница 8: ...matched the system may cause a malfunction Electrical characteristics MCA Min circuit Amps A MFA Max Fuse Amps A KW Fan Motor Rated Output kW FLA Full Load Amps A Specifications for field supplied fus...

Страница 9: ...he remote controller 6 Never connect the power supply wiring to the terminal board for transmission wiring This mistake could damage the entire system 7 Use only specified wires and tightly connect wi...

Страница 10: ...to define time between 2 filter cleaning display indications When contamination is high setting can be changed to half the time inbetween 2 filter cleaning display indications Ultra long life filter L...

Страница 11: ...esent unhook the chains 2 Remove the air filters Remove the air filters by pulling their cloth upward rear suction or backward bottom suction 3 Clean the air filter Use vacuum cleaner A or wash the ai...

Страница 12: ...fter cleaning the air filter make sure to attach it Turn on the main power supply switch The control panel display lights when the power is turned on To protect the unit turn on the main power switch...

Страница 13: ...H ADAPTOR FOR WIRING RyC RyF MAGNETIC RELAY RyH MAGNETIC RELAY J1EH F1U F2U FUSE 250 V 5 A X1A X2A CONNECTOR WIRING ADAPTOR X1M TERMINAL STRIP CONNECTOR FOR OPTIONAL PARTS X16A CONNECTOR WIRING ADAPTO...

Страница 14: ...NOTES NOTES...

Страница 15: ...4 2 1 13 13 2 2 1 14 14 L N IN D OUT D F1 F2 F1 F2 Control box LN P1 P2 P1 P2 F1 F2 T1 T2 LN P1 P2 F1 F2 T1 T2 LN P1 P2 F1 F2 T1 T2 LN P1 P2 F1 F2 T1 T2 P1 P2 P1 P2 2 4 5 3 1 16 16 IN D OUT D F1 F2 F1...

Страница 16: ...Zandvoordestraat 300 B 8400 Oostende Belgium 4PW25083 1C...

Отзывы: