EDUS391000-C
Control Devices
Controls
47
2.5.6
Setting Group No. for Centralized Control
Set the group number of each group of the indoor unit from the remote controller. (In case of no remote controller, also
connect the remote controller and set the group No. Then, remove the remote controller.)
1. Turn ON the power of the indoor unit and unified ON/OFF controller. (Unless the power is ON, no setting can be
made.)
Check that the installation and electrical wiring are correct before turning the power supply ON.
When the power supply is turned ON, all LCD appear once and the unit may not accept the operation for about one
minute with the display of “
” flashing (an interval of ON, ON, and OFF).
2. While in the normal mode, hold down the “
” button for a minimum of 4 seconds.
The remote controller will enter the FIELD SET MODE.
3. Select the MODE No. “
00
” with the “
” button.
4. Use the “
” button to select the group No. for each group. (Group numbers increase in the order of 1-00, 1-01,
...1-15, 2-00, ... 8-15.)
5. Press “
” to set the selected group No.
6. Press “
” to return to the NORMAL MODE.
Note:
For simplified remote controller, see the installation table.
For setting group No. of HRV and wiring adaptor for other air conditioners, etc., refer to the instruction manual
attached.
NOTICE
Enter the group No. and installation place of the indoor unit into the attached installation table. Be sure to keep the
installation table with the operation manual for maintenance.
2.5.7
Confirming Operation
Before starting test operation, supply power to the indoor units, outdoor units, and unified ON/OFF controller and press
the ON/OFF BUTTON.
If the operation lamp flashes, it indicates a malfunction in the indoor unit of the applicable group.
If the display of “
” flashes, it indicates a malfunction in the optional controllers for centralized control. Check
for such malfunctions.
Note:
For test operation of indoor and outdoor units, refer to the installation manual attached with the outdoor unit.
After turning the power supply ON, if the unit does not accept operation for two minutes or more with the display of
“
” flashing, check the following points.
Check that setting of the connector for setting master controller is correct.
Check that the group No. for centralized control has been set.
TEST
SETTIING
Unit NO.
3
4
5
2·6
UNIT NO.
SECOND
CODE NO.
MODE NO.
FIELD
SET
MODE
FIRST
CODE NO.
Содержание FXFQ-PVJU
Страница 1: ...EDUS 391000 C AMERICAS AMERICAS Controls...
Страница 9: ...Control Devices EDUS391000 C 8 Controls Other Features...
Страница 63: ...Control Devices EDUS391000 C 62 Controls 2 7 7 Electric Wiring Connection ground wire to ground terminal...
Страница 64: ...EDUS391000 C Control Devices Controls 63...
Страница 65: ...Control Devices EDUS391000 C 64 Controls...
Страница 66: ...EDUS391000 C Control Devices Controls 65 1P167242A...
Страница 70: ...EDUS391000 C Adapter Controls 69 C 3K019189B...
Страница 74: ...EDUS391000 C Adapter Controls 73 3 3 DTA109A51 DIII NET Expander Adapter 1P013360...
Страница 75: ...Adapter EDUS391000 C 74 Controls 1P013360...
Страница 76: ...EDUS391000 C Adapter Controls 75 1P013360...
Страница 77: ...Adapter EDUS391000 C 76 Controls 3 4 KRP1C74 75 Wiring Adapter C 2P263038A...
Страница 78: ...EDUS391000 C Adapter Controls 77 C 2P263038A...
Страница 79: ...Adapter EDUS391000 C 78 Controls C 2P263038A KRP1C74 Compact multi flow...
Страница 82: ...EDUS391000 C Adapter Controls 81...
Страница 83: ...Adapter EDUS391000 C 82 Controls...
Страница 84: ...EDUS391000 C Adapter Controls 83 C 1P161221...
Страница 89: ...Adapter EDUS391000 C 88 Controls...