17 Piping installation
In this chapter
17.1 Preparing refrigerant piping
17.1.1 Refrigerant piping requirements
INFORMATION
Also read the precautions and requirements in the
6].
CAUTION
Piping MUST be installed according to instructions given in
61]. Only mechanical joints (e.g. braze+flare connections) that are
compliant with the latest version of ISO14903 can be used.
NOTICE
The piping and other pressure-containing parts shall be suitable for refrigerant. Use
phosphoric acid deoxidised seamless copper for refrigerant.
▪
Foreign materials inside pipes (including oils for fabrication) must be
≤30 mg/10 m.
Refrigerant piping diameter
For piping connections of the indoor unit use the following piping diameters:
Class
Pipe outer diameter (mm)
Liquid pipe
Gas pipe
15~32
Ø6.4
Ø9.5
40~63
Ø12.7
Refrigerant piping material
▪
Piping material:
Phosphoric acid deoxidised seamless copper.
▪
Flare connections:
Only use annealed material.
▪
Piping temper grade and thickness: