FWEC2T/4T/10

8

maximum speed); this switch has no effects if 

the main ON/OFF switch is set in the ON mo-

de with automatic ventilation (only FWEC10)

 

„

Green led warning (FWEC2T):

 

Ū Led is switched off: fan coil is working 

neither in cooling nor heating mode. 

There are no anomalies.

 

Ū Led is permanently switched on: fan coil 

is working in cooling or heating mode.

 

Ū Led is slowly blinking: water temperatu-

re is not compliant

 

Ū Led is quickly blinking: temperature 

probe is faulty or disconnected

 

„

Blue and red warning led (FWEC4T and 

FWEC10):

 

Ū Led is permanently blue: fan coil is in co-

oling mode

 

Ū Led is permanently red: fan coil is in he-

ating mode

 

Ū Red led is blinking: water temperature is 

too low to heat

 

Ū Both red and blue led blinking: tempe-

rature probe is faulty or disconnected

 

„

Control knob for temperature setting from 5 

to 35 °C

 

„

Manual switch mode:

 

Ū SUMMER/COOLING

 

Ū WINTER/HEATING

4  ELECTRICAL CONNECTIONS

All of the operations must be carried out by 

qualified staff, in accordance with regulations 

in force. For any electrical related procedure, 

refer to the electrical diagrams attached to this 

documentation.

We also suggest making sure that the charac-

teristics of the electrical network are suitable for 

the absorption levels reported in the electrical 

data table.

Before carrying out any operation on elec-

trical parts, make sure the power supply is 

disconnected. Check that the net voltage is 

compatible with the specifications of the unit 

(voltage, number of phases, frequency) shown 

on the unit rating plate. The supply voltage 

must not fluctuate by more than ±5% in relation 

to the rated value. The electrical connections 

must be set up according to the electrical dia-

gram attached to the specific unit and with the 

regulations in force. 

WARNING:

 the use of shielded cable is rec-

ommended during the installation.

5  OPERATING AND ADJUSTMENT SETTING:

On the electric circuit of the controller there are 

electric devices able to modify three different 

settings:

 

Ū REMOTE jumper used to specify the position 

of the air probe on the basis of which the con-

troller makes the adjustment. The two  pos-

sibilities are on board probe (factory default 

setting) or remote wired probe (Fig. 5).

 

Ū AUTO jumper to specify how the changeover 

(SUMMER/WINTER) is supposed to be applied 

by the controller (only FWEC4T and FWEC10). 

The two possibilities are the manual selec-

tion (factory default setting) or the automatic 

changeover on the basis of air temperature 

(Fig. 5).

 

Ū Potentiometer for the hysteresis calibration 

(from 1°C to 10°C) around the temperature 

SET for the automatic SUMMER/WINTER 

changeover (only FWEC4T and FWEC10); we 

suggest not to modify this value if not strictly 

necessary, for example as a consequence of a 

quick and large variation of the air tempera-

ture (Fig. 5)

Содержание FWEC2T

Страница 1: ...ng Elektronische Regler f r Fancoils FWEC2T FWEC4T FWEC10 Manuel d installation et d utilisation R gulateurs lectroniques pour ventilo convecteurs FWEC2T FWEC4T FWEC10 Installation and use manual Fan...

Страница 2: ...E GENERALI p 3 2 CODICI E DESCRIZIONI p 3 3 LEGENDA ED ISTRUZIONI DI UTILIZZO p 3 4 COLLEGAMENTI ELETTRICI p 4 5 IMPOSTAZIONI DI FUNZIONAMENTO E REGOLAZIONE p 4 6 REGOLAZIONE E FUNZIONAMENTO p 5 7 DAT...

Страница 3: ...la legislazione ap plicabile Le unit devono essere trattate presso un impianto specializzato di lavorazione per il riutilizzo il riciclaggio e il recupero Assicuran dovi che questo prodotto sia smalti...

Страница 4: ...adeguate agli assorbi menti indicati nella tabella dati elettrici Prima di effettuare qualsiasi operazione su parti elettriche assicurarsi che non vi sia tensione Veri ficare che la tensione della ret...

Страница 5: ...e ratura reale dell ambiente Il consenso acqua alla ventilazione solo se sonda acqua presente segue la logica di attivazione e di sattivazione riportata in figura 7 in caso di FWEC4T ed FWEC10 il cons...

Страница 6: ...GENERAL CAUTIONARY NOTES p 7 2 CODES AND DESCRIPTION p 7 3 OPERATING INSTRUCTIONS AND LEGEND p 7 4 ELECTRICAL CONNECTIONS p 8 5 OPERATING AND ADJUSTMENT SETTING p 8 6 ADJUSTMENT LOGICS p 9 7 TECHNICAL...

Страница 7: ...or reuse recycling and re covery By ensuring this product is disposed of correctly you will help to prevent potential negative consequences for the environment and human health For more information co...

Страница 8: ...g out any operation on elec trical parts make sure the power supply is disconnected Check that the net voltage is compatible with the specifications of the unit voltage number of phases frequency show...

Страница 9: ...odically moved The water consent to ventilation only if the water probe is connected is driven by the ac tivation and deactivation logic reported in fig ure 7 in case of FWEC4T and FWEC10 the water co...

Страница 10: ...MANDATIONS G N RALES p 11 2 CODES ET D SIGNATION p 11 3 L GENDES ET INSTRUCTIONS D UTILISATION p 11 4 BRANCHEMENTS LECTRIQUES p 12 5 INSTRUCTIONS DE MONTAGE MURAL p 12 6 R GLAGE ET FONCTIONNEMENT p 13...

Страница 11: ...sp cialis de collecte de recyclage et de r utilisation En vous assurant que ce produit est bien limin correctement vous contribuer la pr vention des cons quences n gatives potentielles pour l envi ron...

Страница 12: ...es Avant de proc der toute intervention sur les parties lectriques isoler l appareil du secteur d alimenta tion lectrique S assurer que les caract ristiques du secteur d alimentation lectrique sont co...

Страница 13: ...le Le signal de validation pour la ventilation si la sonde eau est pr sente suit la logique d activation et de d sactivation indiqu e dans la figure 7 dans le cas de FWEC4T et FWEC10 le consentement d...

Страница 14: ...1 ALLGEMEINEWARNHINWEISE S 15 2 CODES UND BESCHREIBUNG S 15 3 LEGENDE UND GEBRAUCHSANWEISUNG S 15 4 STROMANSCHL SSE S 16 5 BETRIEBSEINSTELLUNGEN UND REGELUNGEN S 16 6 REGELUNG UND BETRIEB S 16 7 TECH...

Страница 15: ...Die Einheiten m ssen in speziellen Behandlungsanlagen f r die Wiederver wendung RecyclingundR ckgewinnungaufbereitet werden Durch Sicherstellung einer korrekten Entsor gung dieses Produkts k nnen Sie...

Страница 16: ...rnehmen ohne dass man sichergestellt hat dass keine Spannung vorliegt berpr fen ob die Netzspannung mit den Nenndaten Spannung Phasenanzahl Frequenz des Gebl sekonvektors bereinstimmen die auf dem Ty...

Страница 17: ...Wasserf hler vorhanden folgt der auf Abbildung 7 dar gestellten Aktivierungs und Deaktivierungslogik Bei FWEC4T und FWEC10 ist die Wasserzulassung zur Bel f tung nur im Heizmodus aktiv Beim Modell FW...

Страница 18: ...ENCIAS GENERALES p 19 2 C DIGOSY DESCRIPCI N p 19 3 LEYENDA E INSTRUCCIONES DE USO p 19 4 CONEXIONES EL CTRICAS p 20 5 CONFIGURACI N DE FUNCIONAMIENTOY REGULACI N p 20 6 REGULACI NY FUNCIONAMIENTO p 2...

Страница 19: ...ser tratadas en una instalaci n especializada para su reutilizaci n re ciclaje y recuperaci n Al asegurarse de que este producto es desechado correctamente contri buir a evitar potenciales consecuenc...

Страница 20: ...ca sean adecuadas para las absorciones indicadas en la tabla de datos el ctricos Antes de efectuar cualquier operaci n en partes el c tricas compruebe que no haya tensi n Verifique que la tensi n de l...

Страница 21: ...autorizaci n para enviar agua a la ventilaci n solo si est prevista la sonda de agua sigue la l gica de activaci n y desactivaci n indicada en la figura 7 en el caso de FWEC4T y FWEC10 el consentimien...

Страница 22: ...FWEC2T 4T 10 22 8 FIGURE 1 FWEC2T 20 25 3 0 3 5 15 1 0 2 5 3 6 1 2 FWEC4T 20 25 3 0 3 5 15 1 0 2 5 4 1 6...

Страница 23: ...FC66006512 01 23 3 FWEC10 20 25 3 0 3 5 15 1 0 2 5 4 1 6 4 Montaggio 4 Mounting 4 Montage 4 Montage 4 Montaje...

Страница 24: ...eration 5 Pogrammation des param tres de fonctionnement 5 Betriebseinstellungen 5 Configuraci n de funcionamiento 6 Set point temperatura 6 Temperature set point 6 Set point temperature 6 Tempe raturs...

Страница 25: ...r zur Bel ftung einwilligen 7 Autorizaci n para enviar agua a la ventilaci n 17 0 22 0 30 0 37 0 C C ON OFF ON OFF 8 Regolazione modulante 8 Modulating control R glage modulant 8 Modulierender Regelun...

Страница 26: ...ambiante SA Umgebungstemperaturf hler SA Sonda de temperatura ambiente SW Sonda temperatura acqua SW Water temperature probe SW Sonde temp rature eau SW Wassertemperaturf hler SW Sonda de temperatura...

Страница 27: ...otor MV Motor L fter MV Motor ventilador SA Sonda temperatura ambiente SA Ambient temperature probe SA Sonde temp rature ambiante SA Umgebungstemperaturf hler SA Sonda de temperatura ambiente SW Sonda...

Страница 28: ...ilateur inverter MV INV Motor L fterinverter MV INV Motor ventilador inverter SA Sonda temperatura ambiente SA Ambient temperature probe SA Sonde temp rature ambiante SA Umgebungstemperaturf hler SA S...

Страница 29: ...tilateur inverter MV INV Motor L fterinverter MV INV Motor ventilador inverter SA Sonda temperatura ambiente SA Ambient temperature probe SA Sonde temp rature ambiante SA Umgebungstemperaturf hler SA...

Страница 30: ...FWEC2T 4T 10 30...

Страница 31: ...FC66006512 01 31...

Страница 32: ...Zandvoordestraat 300 B 8400 Oostende Belgium...

Отзывы: