Troubleshooting
SiUS041111
96
Service Diagnosis
4.14 Discharge Pipe Temperature Control
Remote
Controller
Display
F3
Method of
Malfunction
Detection
An error is determined with the temperature detected by the discharge pipe thermistor.
Malfunction
Decision
Conditions
If the temperature detected by the discharge pipe thermistor rises above A, the compressor
stops.
The error is cleared when the discharge pipe temperature has dropped below B.
09/12 class
15/18/24 class
If the error repeats, the system is shut down.
Reset condition: Continuous run for about 60 minutes without any other error
Supposed
Causes
Defective discharge pipe thermistor
(Defective outdoor heat exchanger thermistor or outdoor temperature thermistor)
Defective electronic expansion valve or coil
Refrigerant shortage
Defective four-way valve
Water mixed in refrigerant
Defective stop valve
Defective outdoor unit PCB
Stop temperatures
A
B
°C
°F
°C
°F
(1) above 50 Hz (rising), above 45 Hz (dropping)
110
230
97
206.6
(2) 39 ~ 50 Hz (rising), 34 ~ 45 Hz (dropping)
105
221
92
197.6
(3) below 39 Hz (rising), below 34 Hz (dropping)
100
212
87
188.6
Stop temperatures
A
B
°C
°F
°C
°F
(1) above 50 Hz (rising), above 45 Hz (dropping)
118
244.4
85
185
(2) 35 ~ 50 Hz (rising), 30 ~ 45 Hz (dropping)
110
230
77
170.6
(3) below 35 Hz (rising), below 30 Hz (dropping)
93
199.4
60
140