SiBE041434E
Troubleshooting
Service Diagnosis
76
4.10 Outdoor Unit PCB Abnormality
Error Code
E1
Method of Error
Detection
The system checks if the microprocessor is working in order.
The system checks if the zero-cross signal comes in properly.
Error Decision
Conditions
The microprocessor program runs out of control.
The zero-cross signal is not detected.
Supposed
Causes
Defective outdoor unit PCB
Broken harness between PCBs
Noise
Momentary drop of voltage
Momentary power failure
Troubleshooting
20/25/35 class
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Continuously ON or OFF
Blink
YES
(R21200)
NO
YES
NO
Replace the outdoor unit
PCB (main PCB).
Ground the system.
Zero-cross signal
abnormality.
Replace the outdoor unit
PCB (filter PCB).
Replace the harness.
Check if the outdoor unit is
grounded.
Is LED A blinking?
Grounded?
Is the harness
broken?
Turn on the power again.
∗
Before you check the LED A,
cancel the standby electricity
saving function by starting fan
operation with the remote
controller.
∗
Wait at least for 7 sec. after
turning on the power.
Содержание FTXM-K Series
Страница 16: ...SiBE041434E 1 List of Functions Part 1 List of Functions 1 Functions 2...
Страница 18: ...SiBE041434E 3 Specifications Part 2 Specifications 1 Specifications 4...
Страница 66: ...SiBE041434E 51 Remote Controller Part 5 Remote Controller 1 20 25 Class 52 2 35 42 50 Class 54...
Страница 122: ...Check SiBE041434E 107 Service Diagnosis 42 50 class R21204 W V U DC_P1 Power module DC_N1 Power module...
Страница 137: ...Revision History Month Year Version Revised contents 02 2015 SiBE041434E First edition...