SiBE041434E
Field Settings
Trial Operation and Field Settings
114
4.4
Jumper Settings
Indoor Unit
For the location of the jumper, refer to page 8, 10.
Outdoor Unit
For the location of the jumper, refer to page
.
Caution
Replace the PCB if you accidentally cut a wrong jumper.
Jumpers are necessary for electronic circuit. Improper operation may occur if you cut any of
them.
Function
Jumper
When connected
(factory setting)
When cut
Fan speed setting when
compressor stops for
thermostat OFF. (effective
only in cooling operation)
JB
Fan speed setting ;
Remote controller setting
The fan stops.
Power failure recovery
function
JC
Auto-restart
The unit does not resume
operation after recovering
from a power failure. Timer
settings are cleared.
Function
Jumper
When connected
(factory setting)
When cut
Improvement of
defrost performance
20/25/35 class
→
J5
42/50 class
→
J8
Standard control
Reinforced control (Ex: The
frequency increases, the
duration time of defrost
lengthens.)