SiBE041434E
Main Functions
Function and Control
28
1.12 Inverter POWERFUL Operation
Outline
In order to exploit the cooling and heating capacity to full extent, the air conditioner can be
operated by increasing the indoor fan rotating speed and the compressor frequency.
Detail
When the
POWERFUL
button is pressed, the fan speed and target temperature are converted
to the following states for 20 minutes.
A
= 60 ~ 80 rpm (depending on the model)
Ex: POWERFUL operation in cooling
Note:
POWERFUL operation cannot be used together with ECONO, COMFORT AIRFLOW, or
OUTDOOR UNIT QUIET operation.
Operation mode
Fan speed
Target temperature
COOL
H tap +
A
rpm
18°C
DRY
Dry rotating speed +
A
rpm
Lowered by 2.5°C
HEAT
H tap +
A
rpm
31°C
FAN
H tap +
A
rpm
—
AUTO
Same as cooling / heating in
POWERFUL operation
The target temperature is
kept unchanged.
(R19177)
Target temp.
Fan
A
rpm
18˚C
H tap
Set tap
20 minutes
It should be the lower limit of
cooling temperature.
It counts 20 minutes also
in the remote controller.
POWERFUL
ON
POWERFUL
OFF
Ending condition:
1. After the lapse of 20 minutes.
2. Operation OFF
3. POWERFUL operation is OFF.
Содержание FTXM-K Series
Страница 16: ...SiBE041434E 1 List of Functions Part 1 List of Functions 1 Functions 2...
Страница 18: ...SiBE041434E 3 Specifications Part 2 Specifications 1 Specifications 4...
Страница 66: ...SiBE041434E 51 Remote Controller Part 5 Remote Controller 1 20 25 Class 52 2 35 42 50 Class 54...
Страница 122: ...Check SiBE041434E 107 Service Diagnosis 42 50 class R21204 W V U DC_P1 Power module DC_N1 Power module...
Страница 137: ...Revision History Month Year Version Revised contents 02 2015 SiBE041434E First edition...