Function and Control
55
3.5
Input Current Control
Outline
Detect an input current by the CT during the compressor is running, and set the frequency
upper limit from such input current.
In case of heat pump model, this control is the upper limit control function of the frequency
which takes priority of the lower limit of four way valve activating compensation.
Detail
The frequency control will be made within the following zones.
When a “stop current” continues for 2.5 seconds after rushing on the stop zone, the compressor
operation stops.
If a “drooping current” is continues for 1.0 second after rushing on the drooping zone, the
frequency will be 2 Hz drooping.
Repeating the above drooping continues until the current rushes on the drooping zone without
change.
In the unchanged zone, the frequency limit will remain.
In the return / reset zone, the frequency limit will be cancelled.
Limitation of current drooping and stop value according to the outdoor air temperature
1. In case the operation mode is cooling
The current droops when outdoor air temperature becomes higher than a certain level
(model by model).
2. In case the operation mode is heating (only for heat pump model)
The current droops when outdoor air temperature becomes higher than a certain level
(model by model).
3.6
Freeze-up Protection Control
Outline
During cooling operation, the signals being sent from the indoor unit allow the operating
frequency limitation and then prevent freezing of the indoor heat exchanger. (The signal from
the indoor unit must be divided into the zones as the followings.
Detail
Conditions for Start Controlling
Judge the controlling start with the indoor heat exchanger temperature after 2 sec from
operation start.
Control in Each Zone
2 Hz drooping
1.0
s
econd
a
fter
r
us
hing in the
drooping zone
After 2.5
s
econd
s
Compre
ss
or
s
top
s
S
top zone
I 1
I 2
I
3
Re
s
et zone
(R1
3
7
8
)
Drooping zone
Unch
a
nged
zone
Inp
u
t c
u
rrent
drooping
He
a
t exch
a
nger
thermi
s
tor temper
a
t
u
re
S
top zone
A
B
C
D
E
Ret
u
rn / Re
s
et zone
(R1
3
79)
Drooping zone
Unch
a
nged zone
Up zone
SiENBE04-512A.book Page 55 Friday, October 5, 2007 1:49 PM
Содержание FTKS20CVMB(9)
Страница 1: ...SiENBE04 512A Service Manual Inverter Pair Wall Mounted Type C Series D Series...
Страница 17: ...List of Functions SiENBE04 512A 8 List of Functions...
Страница 18: ...SiENBE04 512A Specifications 9 Part 2 Specifications 1 Specifications 10 1 1 Cooling Only 10 1 2 Heat Pump 16...
Страница 37: ...Specifications SiENBE04 512A 28 Specifications...
Страница 73: ...Control Specification SiENBE04 512A 64 Function and Control...
Страница 103: ...Instruction SiENBE04 512A 94 System Configuration...
Страница 147: ...Check SiENBE04 512A 138 Service Diagnosis...
Страница 225: ...Outdoor Unit RK X H C ARK X H C R Y N C SiENBE04 512A 216 Removal Procedure...
Страница 226: ...SiENBE04 512A Others 217 Part 8 Others 1 Others 218 1 1 Test Run from the Remote Control 218 1 2 Jumper Settings 219...
Страница 229: ...Others SiENBE04 512A 220 Others...
Страница 241: ...Wiring Diagrams SiENBE04 512A 232 Appendix...
Страница 245: ...SiENBE04 512A iv Index wiring diagrams 229...