Choosing an Installation Site
+PUVCNNCVKQP5RCEG4GSWKTGOGPVU
ű
60
(1500)
ű
11-3/4
(300)
ű
98 (2500)
*
ű
60
(1500)
*
ű
60
(1500)
F
or installation
in high places
Air
outlet
Air
outlet
Air
inlet
*
ű
60 (1500)
*
ű
60 (1500)
unit:inch (mm)
*
ű
60
(1500)
*
ű
60
(1500)
r
Leave 8 inch (200mm) or more space where marked with the
*
, on sides where the air outlet is closed.
#KTƃQYFKTGEVKQP
r
The air direction shown is an example.
r
Select the appropriate number of directions according to the shape of the room and the location of the unit. (Field settings have to
be made using the remote controller and the outlet vents have to be shut off if 2 or 3 directions are selected.
See the blocking pad kit (sold separately) installation manual for details.)
#KTƃQYFKTGEVKQP
'ZCORNG
Piping
Air outlet
Piping
Piping
Air outlet in 2 directions
Air outlet in 3 directions
Air outlet in 4 directions
7UGUWURGPUKQPDQNVUHQTKPUVCNNCVKQP%JGEMYJGVJGTVJGEGKNKPIKUUVTQPIGPQWIJVQUWRRQTVVJG
YGKIJVQHVJGWPHVJGTGKUCTKUMTGKPHQTEGVJGEGKNKPIDGHQTGKPUVCNNKPIVJGWPKV
(Installation pitch is marked on the template. Refer to it to check for points requiring reinforcing.)