6. REFRIGERANT PIPING WORK
〈
For refrigerant piping of outdoor units, see the installation manual attached to the outdoor unit.
〉
〈
Execute heat insulation work completely on both sides of the gas piping and the liquid piping. Otherwise, a
water leakage can result sometimes.
〉
(
When using a heat pump, the temperature of the gas piping can reach up to approximately 120°C, so use
insulation which is sufficiently resistant.)
〈
Also, in cases where the temperature and humidity of the refrigerant piping sections might exceed 30°C or
RH80%, reinforce the refrigerant insulation. (20mm or thicker) Condensate may form on the surface of the
insulating material.
〉
〈
Be sure to check the type of R410A refrigerant to be used before doing any work. (Using an incorrect
refrigerant will prevent normal operation of the unit.)
〉
CAUTION
This product is designed to be used with new refrigerant (R410A). Always observe the precautions on the
following when installing.
•
Use a pipe cutter and flare suitable for the type of refrigerant.
•
Apply ester oil or ether oil around the flare section before connecting.
•
Use the flare nut provided to the unit. Do not use a different flare nut (class 1), or otherwise refrigerant
leakage may result.
•
To prevent dust, moisture or other foreign matter from infiltrating the tube, either pinch the end or cover
it with tape.
•
Do not allow anything other than the designated refrigerant to get mixed into the refrigerant circuit, such
as air, etc. If any refrigerant gas leaks while working on the unit, ventilate the room thoroughly right away.
•
The outdoor unit is charged with refrigerant.
•
Be sure to use both a spanner and torque wrench
together, as shown in the drawing, when connecting
or disconnecting pipes to/from the unit.
(Refer to Fig. 6)
•
Refer to “Table 1” for the dimensions of flare nut
spaces.
•
Use the flare nut included with the unit main body.
•
When connecting the flare nut, apply ester oil or
ether oil to the flare section (inside only), and spin
3-4 times before screwing in.
(Refer to Fig. 7)
CAUTION
•
Do not let oil get on the screw holders on the dressing board. Oil can weaken the screw holders.
•
Refer to “Table 1” to determine the proper tightening torque.
•
Be careful not to damage the flare section.
Torque wrench
Spanner
Piping union
Flare nut
Fig. 6
Fig. 7
Coat here with ester or ether oil.
01_EN_3PN06583-10W.fm Page 9
Thursday, March 24, 2011 9:03 AM
Содержание FBQ20DAVMK
Страница 30: ...MEMO...
Страница 31: ...FBQ20DAVMK FBQ24DAVMK FBQ36DAVMK FBQ45DAVMK FBQ48DAVMK...
Страница 32: ...2 1 1...
Страница 33: ...3 1 1 2 2 3 3 4 4 R410A SUNISO R410A R410A 33 3 3 R407C 40 4 0 R410A R410A...
Страница 34: ...4 2 R410A 1 2 1 1 2 3 1 1 1 M5 16 24 20 18 48 45 36 26 4 5 1 6 2 7 8 9 10 11 12 9 4 2 8 2 13 2 M4 8...
Страница 35: ...5 2 2 BRC1C61 BRC4C62 13 1 1...
Страница 36: ...6 3 2 1 3 80 10 1 2 1 1...
Страница 39: ...9 5 1 11 9 11 5 2 3 4 4 11 9 5...
Страница 40: ...10 6 C 120 RH 80 C 30 20 R410A R410A 1 6 1 4 3 7 1 6 7...
Страница 42: ...12 4 4 8 8 7 7 8 9...
Страница 43: ...13 9 0 02 BCuP 2 JIS Z 3264 B Cu93P 710 795 ISO 3677 7 1 2 25 32 100 1 1 5 1 1 2 2 1 1 4 4 100 1 1 2...
Страница 44: ...14 2 3 4 100 1 100 1 2 1 5 1...
Страница 45: ...15 6 2 1 8 25 50 11 3 3 6 1 4 3 3...
Страница 46: ...16 9 230 ASSY 10 1 10 1 3...
Страница 47: ...17 2 50 X2M...
Страница 48: ...18 3 140 125 10 15 8 X1M 8 X2M 4 10...
Страница 49: ...19 12 5 8 13 8 12 13 0 96 0 80 1 44 1 18 1 44 1 18...
Страница 50: ...20 2 2 2 36 24 20 4 2 5 48 45 4 2 1 25 0 75 500 15 2 1 1 16 1 10 14 1 2 2 16 1 10 230 60...
Страница 51: ...21 9 1 2 10 P1 P2 2 2 1 2 2 1 12 1 1 2 2 16 16 10 2 P 1 P 2 P 1 P 1 2 11 12...
Страница 52: ...22 S 2 13 M 9 3 P1 P2 2 4 11 11 12 13 1 1 2 2 14...
Страница 53: ...23 1 1 2 2 1 2 L H 3 7 11 21 03 3 21 11 7 01 02 03 02 21 4 02 3 3...
Страница 55: ...25 12 00 00 10 4 1 12 6 6 88 88 90 88 90...
Страница 56: ...26 1 1 1 2 2 2 2 0 1 2 3 6 3 1 1 3 2 4 5 6 1 5 2 00 2 12 A1 A3 A6 A8 AF AH AJ C1 C4 C6 C9 CC CJ E0 E1...
Страница 57: ...27 E3 E4 E5 E7 E9 F3 H3 H7 H9 J1 J2 J3 J5 J6 J7 J8 J9 JA JC L1 L4 L5 L8 L9 LC P1 P3 P4 PJ U0 U1 L3 L2 L1 U2...
Страница 58: ...28 U4 UF UF U5 U8 UA UC UJ 5...
Страница 59: ......
Страница 60: ...3P370016 1 M14N008 HT 00_CV_3PN06583 10W fm Page 2 Thursday March 24 2011 8 56 AM http www daikin com global_ac...