background image

English

23

With Wireless Remote Controller Used

Set the wireless remote controller address before using the wireless remote controller.
For the setting method of the address, refer to the operation manual provided with the wireless remote 
controller.

NOTE

A “MODE NO.” is set on a group basis. To make a mode setting on a room unit basis or check the setting 
made, however, set the corresponding mode number in the parentheses.

1. Settings for Optional Accessories

In the case of connecting optional accessories, refer to the operation manuals provided with the optional 
accessories and make necessary settings.

2. External Static Pressure Settings

Make settings in either method (a) or method (b) as explained below.
(a) Use the airflow auto adjustment function to make settings.

Airflow auto adjustment: The volume of blow-off air is automatically adjusted to the rated quantity.

NOTE

Be sure to check that the external static pressure is within the rated range before making the settings. 
If the external static pressure is beyond the rated range, no automatic adjustments will be made and an 

airflow rate insufficiency or water leakage may result. (Refer to the relevant technical datasheet for the

 

rated range of the external static pressure.)

(1)Check that power supply wiring and wiring the units to the air conditioner is completed along with 

duct installation. If a closing damper is installed in the air-conditioning system, make sure that the 
closing damper is opened. Furthermore, check that the air filter as a field supply is attached to the 
air passage on the suction side.

(2)If there are a number of air outlets and inlets, adjust the throttles so that the airflow rate of each air 

outlet and inlet will coincide with the designed airflow rate. At that time, operate the air conditioner 
in “fan operation mode”. To change the airflow rate, press and set the airflow adjustment button of 
the remote controller to H, or L.

(3)Make settings for airflow automatic adjustment. After setting the air conditioner to “fan operation 

mode”, stop the air conditioner, go to “FIELD SET MODE”, select “MODE NO. 21” (11 in the case 
of group settings), set the setting “FIRST CODE NO.” to 7, and set the setting “SECOND CODE 
NO.” to 03. 
Return to normal mode after these settings, and press the ON/OFF OPERATION button. Then the 
operation lamp will be lit and the air conditioner will go into fan operation for airflow automatic 
adjustment. Do not adjust the throttles of the air outlets or inlets during automatic adjustment of the 
air conditioner. After the air conditioner runs approximately one to eight minutes, the air conditioner 
will finish airflow adjustment automatically, the operation lamp will be turned OFF, and the air 
conditioner will come to a stop.

Table 3 

(4)After the air conditioner stops operating, check with “MODE NO. 21” on an indoor unit basis that 02 

is set for the “SECOND CODE NO.” in Table 3. If the air conditioner does not stop operating 
automatically or the “SECOND CODE NO.” is not 02, repeat steps from (3). If error is displayed, 
check the defective point.

MODE NO.

FIRST CODE NO.

Setting contents

11 (

21

t

n

e

m

t

s

u

j

d

a

 

w

o

lf

ri

A

7

)

SECOND CODE NO.

3

0

2

0

1

0

OFF

Completion of airflow adjustment

Start of airflow adjustment

01_EN_3PN06583-10W.fm  Page 22   Thursday, March 24, 2011  9:03 AM

Содержание FBQ20DAVMK

Страница 1: ...eiling mounted duct type READ THESE INSTRUCTIONS CAREFULLY BEFORE INSTALLATION KEEP THIS MANUAL IN A HANDY PLACE FOR FUTURE REFERENCE English 00_CV_3PN06583 10W fm Page 1 Thursday March 24 2011 8 56 A...

Страница 2: ...dealer or qualified personnel to carry out installation work Do not attempt to install the air conditioner yourself Improper installation may result in water leakage electric shocks or fire Install t...

Страница 3: ...gas leaks into the room and comes into contact with a source of fire such as a fan heater stove or cooker Do not touch any refrigerant that leaks out of refrigerant piping joints or connections Touch...

Страница 4: ...CT Refrigerant The refrigerant R410A requires that strict Precautions be observed for keeping the system clean dry and tightly sealed A Clean and Dry Strict measure must be taken to keep impurities in...

Страница 5: ...rder to protect the indoor unit from damage use packing materials to protect the unit after carrying until the installation starts Do not use the unit in locations with high salt content in the air su...

Страница 6: ...ng heating Is the unit fully insulated Refrigerant pip ing drain piping and duct Condensate water may drip Does drainage flow smoothly Condensate water may drip Does the power supply voltage correspon...

Страница 7: ...nual for the outdoor unit CAUTION The indoor and outdoor units and the power supply wiring and remote controller cord must be installed at least 1m away from any televisions or radios This is to preve...

Страница 8: ...lower part of the product see axial direction view A 1 Refer to Fig 4 3 Inspection hatch 3 for the lower part of the product and the lower part of the control box see axial direction view A 2 Refer t...

Страница 9: ...ceiling after the installation holes are opened For details consult your construction or interior contractor 4 Install the hanging bolts Make sure that the hanging bolts are M10 in size Use hole in an...

Страница 10: ...ay occur as a result of damage such as hole damage to the resin drain pan 2 Make adjustments so that the unit will be in the right position 3 Check the level of the unit 4 Remove the washer fixing pla...

Страница 11: ...ing Use the flare nut provided to the unit Do not use a different flare nut class 1 or otherwise refrigerant leakage may result To prevent dust moisture or other foreign matter from infiltrating the t...

Страница 12: ...all the way into the pipe connections inside the machine Exposed piping may cause condensation or burns on contact Make absolutely sure to execute heat insulation works on the pipe connecting section...

Страница 13: ...ce of the main unit to the upper part of the flare nut joint Insulation material for piping field supply Wrap the insulation material around the portion from the surface of the main unit to the upper...

Страница 14: ...arts damage 7 DRAIN PIPING WORK 1 Remove the drain socket cover for transportation 2 Conduct drain piping work Check that the piping ensures proper draining Make sure that the diameter of the piping e...

Страница 15: ...the piping on completion of the installation of the piping Provide approximately one liter of water gradually into the drain pan through the water inlet on the bottom of the drain socket or the outlet...

Страница 16: ...n the air suction side Be sure to select an air filter with a duct collection efficiency of 50 weight percent Explain the operation and washing methods of the locally procured components i e the air f...

Страница 17: ...not connect the earth wire to gas pipes plumbing pipes lightning rods or telephone earth wires Gas pipes might cause explosions or fire if gas leaks Plumbing no earth effect if hard vinyl piping is u...

Страница 18: ...ternal electric noise that may interfere with the remote controller wiring For the installation and wiring of the remote controller refer to the remote controller installation manual provided with the...

Страница 19: ...ote controller terminals X2M If stranded wires are used do not solder the front end of the wires Twist and fix the upper part so that the wires will not drop out Fix the cord with the clamp 8 to the w...

Страница 20: ...ed do not solder it Tightening torque for the terminal screws Use the correct screwdriver for tightening the terminal screws If the blade of screwdriver is too small the head of the screw might be dam...

Страница 21: ...s up to 16 indoor units All indoor units operate according to the remote controller Refer to Fig 10 2 remote controllers control 2 remote controllers control 1 indoor unit Refer to Fig 14 Group contro...

Страница 22: ...Insert a screwdriver into the recess between the upper and lower part of remote controller and working from the 2 positions pry off the upper part The remote controller PC board is attached to the upp...

Страница 23: ...ontrol box lids are closed on the indoor and outdoor units Field setting must be made from the remote controller in accordance with the installation condition Setting can be made by changing the MODE...

Страница 24: ...the air passage on the suction side 2 If there are a number of air outlets and inlets adjust the throttles so that the airflow rate of each air outlet and inlet will coincide with the designed airflow...

Страница 25: ...mind that a shortage of airflow quantity or water leakage will result because the air conditioner will be operated outside the rated range of airflow quantity if the external static pressure is wrong...

Страница 26: ...the code reads anything other than 00 refer to the malfunction diagnoses below Press the INSPECTION TEST OPERATION button four times to return to normal operation mode When using wireless remote contr...

Страница 27: ...find the lower code A long beep indicate the Malfunction code NOTE 1 In case wired remote controller Press the INSPECTION TEST OPERATION button on remote controller starts flashing and changes the ins...

Страница 28: ...ording to model J8 Liquid piping temperature sensor system error outdoor unit J9 Suction temperature sensor faulty outdoor unit JA Pressure sensor for discharge pipe faulty outdoor unit JC Pressure se...

Страница 29: ...U4 UF Transmission error indoor unit outdoor unit Wrong wiring between indoor and outdoor units or malfunction of the PC board mounted on the indoor and the outdoor units If UF is shown the wiring bet...

Страница 30: ...MEMO...

Страница 31: ...FBQ20DAVMK FBQ24DAVMK FBQ36DAVMK FBQ45DAVMK FBQ48DAVMK...

Страница 32: ...2 1 1...

Страница 33: ...3 1 1 2 2 3 3 4 4 R410A SUNISO R410A R410A 33 3 3 R407C 40 4 0 R410A R410A...

Страница 34: ...4 2 R410A 1 2 1 1 2 3 1 1 1 M5 16 24 20 18 48 45 36 26 4 5 1 6 2 7 8 9 10 11 12 9 4 2 8 2 13 2 M4 8...

Страница 35: ...5 2 2 BRC1C61 BRC4C62 13 1 1...

Страница 36: ...6 3 2 1 3 80 10 1 2 1 1...

Страница 37: ...7 2 1 100 1 2 7 4 1 3 300 450 450 1 1 4 A 1 2 450 450 1 2 4 A 2 3 3 20 300 1 450 300 2500 620 2 700 2 1 4 450 450 1 3 300 3...

Страница 38: ...8 2 8 3 10 7 6 M10 4 3 2 4 3 300 3 100 1 7 A 1 A 2 1 450 450 2 20 3 200 B 300 D B C D 24 20 1000 1038 1300 48 45 36 1400 1438 1700...

Страница 39: ...9 5 1 11 9 11 5 2 3 4 4 11 9 5...

Страница 40: ...10 6 C 120 RH 80 C 30 20 R410A R410A 1 6 1 4 3 7 1 6 7...

Страница 41: ...11 1 A 8 3 9 5 39 9 32 7 13 2 12 8 8 5 15 9 75 4 61 8 19 7 19 3 8 3 9 5 90 60 200 8 5 15 9 60 30 300 8 8 5 4 5 4 7 5 4...

Страница 42: ...12 4 4 8 8 7 7 8 9...

Страница 43: ...13 9 0 02 BCuP 2 JIS Z 3264 B Cu93P 710 795 ISO 3677 7 1 2 25 32 100 1 1 5 1 1 2 2 1 1 4 4 100 1 1 2...

Страница 44: ...14 2 3 4 100 1 100 1 2 1 5 1...

Страница 45: ...15 6 2 1 8 25 50 11 3 3 6 1 4 3 3...

Страница 46: ...16 9 230 ASSY 10 1 10 1 3...

Страница 47: ...17 2 50 X2M...

Страница 48: ...18 3 140 125 10 15 8 X1M 8 X2M 4 10...

Страница 49: ...19 12 5 8 13 8 12 13 0 96 0 80 1 44 1 18 1 44 1 18...

Страница 50: ...20 2 2 2 36 24 20 4 2 5 48 45 4 2 1 25 0 75 500 15 2 1 1 16 1 10 14 1 2 2 16 1 10 230 60...

Страница 51: ...21 9 1 2 10 P1 P2 2 2 1 2 2 1 12 1 1 2 2 16 16 10 2 P 1 P 2 P 1 P 1 2 11 12...

Страница 52: ...22 S 2 13 M 9 3 P1 P2 2 4 11 11 12 13 1 1 2 2 14...

Страница 53: ...23 1 1 2 2 1 2 L H 3 7 11 21 03 3 21 11 7 01 02 03 02 21 4 02 3 3...

Страница 54: ...24 Daikin 21 01 4 01 3 50 01 1 4 50 23 13 06 01 60 02 70 03 80 04 90 05 100 06 110 07 120 08 130 09 140 10 150 11 160 12 180 13 200 14 3 LCD 5 01 5 2500 20 10 0 01 1250 02 3...

Страница 55: ...25 12 00 00 10 4 1 12 6 6 88 88 90 88 90...

Страница 56: ...26 1 1 1 2 2 2 2 0 1 2 3 6 3 1 1 3 2 4 5 6 1 5 2 00 2 12 A1 A3 A6 A8 AF AH AJ C1 C4 C6 C9 CC CJ E0 E1...

Страница 57: ...27 E3 E4 E5 E7 E9 F3 H3 H7 H9 J1 J2 J3 J5 J6 J7 J8 J9 JA JC L1 L4 L5 L8 L9 LC P1 P3 P4 PJ U0 U1 L3 L2 L1 U2...

Страница 58: ...28 U4 UF UF U5 U8 UA UC UJ 5...

Страница 59: ......

Страница 60: ...3P370016 1 M14N008 HT 00_CV_3PN06583 10W fm Page 2 Thursday March 24 2011 8 56 AM http www daikin com global_ac...

Отзывы: