background image

English

4

FOR THE FOLLOWING ITEMS, TAKE SPECIAL CARE DURING CONSTRUCTION AND 
CHECK AFTER INSTALLATION IS FINISHED.

1. Items to be checked after completion of work

2. Items to be checked at time of delivery 

*Also review the “SAFETY CONSIDERATIONS”

 

Points for explanation about operations

4. NOTE TO THE INSTALLER

Be sure to instruct customers how to properly operate the unit (especially cleaning filters, operating dif-
ferent functions, and adjusting the temperature) by having them carry out operations themselves while
looking at the manual.

3. SELECTING INSTALLATION SITE

1. Select an installation site where the following conditions are satisfied and that meets 

with your customer’s approval.

In the upper space (including the back of the ceiling) of the indoor unit where there is no possible 
dripping of water from the refrigerant pipe, drain pipe, water pipe, etc.

Where the wall is strong enough to bear the indoor unit weight.

Where sufficient clearance for installation and maintenance can be ensured.

Where optimum air distribution can be ensured.

Where nothing blocks the air passage.

Where condensate can be properly drained.

Where  wall surface is not particularly inclined.

Where not exposed to combustible gases.

Where piping between indoor and outdoor units is possible within the allowable limit (Refer to the
installation manual of the outdoor unit.)

Items to be checked

If not properly done, what is likely to occur

Check

Is the indoor unit fixed firmly?

The unit may drop, vibrate or make noise.

Is the gas leak test finished?

It may result in insufficient cooling.

Is the unit fully insulated?

Condensate water may drip.

Does drainage flow smoothly?

Condensate water may drip.

Does the power supply voltage correspond 
to that shown on the name plate?

The unit may malfunction or the components 
burn out.

Are wiring and piping correct?

The unit may malfunction or the components 
burn out.

Is the unit safely grounded?

Dangerous at electric leakage.

Is wiring size according to specifications?

The unit may malfunction or the components 
burn out.

Is something blocking the air outlet or inlet 
of either the indoor or outdoor units?

It may result in insufficient cooling.

Are refrigerant piping length and additional 
refrigerant charge noted down?

The refrigerant charge in the system is not 
clear.

Items to be checked

Check

Did you explain about operations while showing the instruction manual to your customer?

Did you hand the instruction manual over to your customer?

The items with 

WARNING and 

CAUTION marks in the instruction manual are the items per-

taining to possibilities for bodily injury and material damage in addition to the general usage of the
product. Accordingly, it is necessary that you make a full explanation about the described contents
and also ask your customers to read the instruction manual.

01_EN_3P184443-2.fm  Page 4  Monday, July 3, 2006  3:14 PM

Содержание FAY71FJV1

Страница 1: ...SAMENTE ESTAS INSTRUCCIONES ANTES DE INSTALAR GUARDE ESTE MANUAL EN UN LUGAR A MANO PARA LEER EN CASO DE TENER ALGUNA DUDA PRIMA DELL INSTALLAZIONE LEGGERE ATTENTAMENTE QUESTE ISTRUZIONI TENERE QUESTO...

Страница 2: ...reenkomstig de bepalingen van Richtlijnen zoals geamendeerd siguiendo las disposiciones de Directivas seg n lo enmendado secondo le prescrizioni per Direttive come da modifica de acordo com o previsto...

Страница 3: ...guinte s norma s ou outro s documento s normativo s desde que estes sejam utilizados de acordo com as nossas instru es overholder f lgende standard er eller andet andre retningsgivende dokument er for...

Страница 4: ...ry out installation work Do not try to install the machine your self Improper installation may result in water leakage electric shocks or fire Perform installation work in accordance with this install...

Страница 5: ...chen Plastic parts may deteriorate and fall off or result in water leakage b where corrosive gas such as sulfurous acid gas is produced Corroding copper pipes or soldered parts may result in refrigera...

Страница 6: ...ote controller from Table 1 according to customer request and install in an appropriate place For installation follow the Installation manual included with the remote controllers Table 1 NOTE If the c...

Страница 7: ...of the outdoor unit Items to be checked If not properly done what is likely to occur Check Is the indoor unit fixed firmly The unit may drop vibrate or make noise Is the gas leak test finished It may...

Страница 8: ...installation panel is attached to the rear of the unit To detach remove the screws from the bottom of the panel Refer to Fig 1 2 Attach the installation panel to the wall using the paper pattern for i...

Страница 9: ...ok on the installation panel Refer to Fig 4 and 5 If running pipes from the left side or using embedded pipes remove the bottom panel to make work easier CAUTION Install the unit so that it is level o...

Страница 10: ...wrong refrigerant will prevent the unit from functioning properly CAUTION Use a pipe cutter and flare suitable for the type of refrigerant Apply ester oil or ether oil around the flare section before...

Страница 11: ...are leaking After checking for gas leaks in the pipe connections insulate them as shown in Fig 11 and 12 Install so that no pipes are exposed as this may cause leaking Pipe size Further tightening ang...

Страница 12: ...igerant piping systems For instance if the chlorine based flux is used it will cause pipe corrosion or in particular if the flux contains fluorine it will damage the refrigerant oil Before brazing loc...

Страница 13: ...it through the drain pipes and corrode the heat exchanger 7 ELECTRIC WIRING WORK All field supplied parts and materials and electric works must conform to local codes Use copper wire only For electric...

Страница 14: ...nal board Remote controller cord connections not necessary for slave unit of simultaneous operation system Feed wires through the clamp and connect to the terminal board for transmission wiring no po...

Страница 15: ...lack in the power wiring may cause abnormal heating Use sleeve insulated round pressure terminals for connections to the power terminal block If none are available connect wires of the same diameter t...

Страница 16: ...he remote controller that suits the indoor unit which has the most functions as attached swing flap 4 For simultaneous operation system connect the remote controller cord to the master unit 1 2 3 P1 P...

Страница 17: ...e installation manual attached to the wireless remote controller for setting instructions 3 Setting indoor unit number of simultaneous operation system When using in simultaneous operation system mode...

Страница 18: ...ler from the master unit if the optional remote controller for slave unit is used However remove the wires attached to the remote controller terminal board of the master unit 5 CONTROL BY 2 REMOTE CON...

Страница 19: ...function diagnoses below 2 HOW TO DIAGNOSE FOR PROBLEMS With the power on Troubles can be monitored on the remote controller or the LED s on the PC board of the indoor unit Trouble shooting with the d...

Страница 20: ...rmal mode 3 Depending on the model or the conditions it may carry out an emergency shut down 4 If the HBP H2P is off the branch wiring between each of the indoor and outdoor units may either be incorr...

Страница 21: ...utdoor unit E1 Outdoor unit s PC board faulty outdoor unit E3 High pressure abnormal outdoor unit E4 Low pressure abnormal outdoor unit E5 Compressor motor lock malfunction outdoor unit E7 Outdoor fan...

Страница 22: ...s shown the wiring between the indoor and outdoor units is not properly wired Therefore immediately disconnect the power supply and correct the wiring The com pressor and the fan mounted on the outdoo...

Страница 23: ...OLLER KIT IS BEING USED 5 REMOTE CONTROLLER MODEL VARIES ACCORDING TO THE COMBINATION SYSTEM CONFIRM ENGINEERING MATERIALS AND CATALOGS ETC BEFORE CONNECTING 6 SYMBOLS SHOW AS FOLLOWS RED RED BLK BLAC...

Страница 24: ...YSTEM CONFIRM ENGINEERING MATERIALS AND CATALOGS ETC BEFORE CONNECTING 6 SYMBOLS SHOW AS FOLLOWS RED RED BLK BLACK WHT WHITE YLW YELLOW ORG ORANGE GRY GRAY PRP PURPLE BLU BLUE 7 CONFIRM THE METHOD OF...

Страница 25: ...0608 HT 3P184443 2 EM00A030E 00_CV_3P184443 2 fm Page 2 Monday July 3 2006 2 21 PM...

Отзывы: