12/16
Breadcrumb
Setting name
Range, step
Default value
Date
Value
Field settings table
Installer setting at variance with
default value
9.I
[6-0E]
R/W
E-07 = 4
40~ 75°C, step: 1°C
65°C
9.I
[7-00]
R/W
0~4°C, step: 1°C
0°C
9.I
[7-01]
R/W
2~40°C, step: 1°C
2°C
9.I
[7-02]
R/W
0: Single zone
1: Dual zone
9.I
[7-03]
2.5
9.I
[7-04]
0
9.I
[7-05]
R/W
0: Very high
1: High
2: Medium
3: Low
4: Very low
9.I
[7-06]
R/W
0: Disabled
1: Enabled
9.I
[7-07]
R/W
0: No
1: Yes
9.I
[7-08]
--
R/W
0
1 (*8)
9.I
[7-09]
20%
9.I
[7-0A]
R/W
20~95%, step 5%
95%
9.I
[7-0B]
R/W
20~95%, step 5%
95%
9.I
[7-0C]
R/W
20~300 seconds, step 5 sec
125 seconds
9.I
[7-0D]
R/W
2~20, step 0,5 °C
4 °C
9.I
[7-0E]
R/W
2~22, step 0,5 °C
7 °C
9.I
[8-00]
R/W
0~20 min, step 1 min
1 min
9.I
[8-01]
R/W
5~95 min, step: 5 min
30 min
9.I
[8-02]
R/W
0~10 hour, step: 0,5 hour
0,5 hour
9.I
[8-03]
R/W
20~95 min, step: 5 min
50 min
9.I
[8-04]
R/W
0~95 min, step: 5 min
95 min
9.I
[8-05]
R/W
0: No
1: Yes
9.I
[8-06]
R/W
0~10°C, step: 1°C
5°C
9.I
[8-07]
R/W
[9-03]~[9-02], step: 1°C
18°C
9.I
[8-08]
R/W
[9-03]~[9-02], step: 1°C
20°C
9.I
[8-09]
R/W
[9-01]~[9-00], step: 1°C
35°C
9.I
[8-0A]
R/W
[9-01]~[9-00], step: 1°C
33°C
9.I
[8-0B]
13
9.I
[8-0C]
10
9.I
[8-0D]
16
9.I
[9-00]
R/W ([2-
0C]
≠
2)
R/O ([2-
0C] = 2)
[2-0C]=2:
37~70, step: 1°C
70°C
[2-0C]
≠
2:
37~55, step: 1°C
55°C
9.I
[9-01]
R/W
15~37°C, step: 1°C
25°C
9.I
[9-02]
R/W
18~22°C, step: 1°C
22°C
9.I
[9-03]
R/W
5~18°C, step: 1°C
7°C
9.I
[9-04]
R/W
1~4°C, step: 1°C
2°C
9.I
[9-05]
R/W
15~37°C, step: 1°C
25°C
9.I
[9-06]
R/W ([2-
0C]
≠
2)
R/O ([2-
0C] = 2)
[2-0C]=2:
37~70, step: 1°C
70°C
[2-0C]
≠
2:
37~55, step: 1°C
55°C
--
Boiler efficiency
HP forced OFF
Hysteresis value used to control the tank bivalent in case it’s
supporting space heating operation
Additional zone fixed pump PWM, in case a bizone kit is installed.
Main zone fixed pump PWM, in case a bizone kit is installed.
Time needed by the mixing valve to turn from one side to the other,
in case a bizone kit is installed.
Offset on the setpoint to determine when the tank is high enough to
go the excess state
What is the maximum temperature setpoint?
Domestic hot water booster heater overshoot temperature.
Domestic hot water booster heater hysteresis.
How many leaving water temperature zones are there?
--
Maximum running time for domestic hot water operation.
What is the mimimum desired LWT for add. zone in heating?
What is the desired comfort main LWT in cooling?
What is the desired comfort main LWT in heating?
What is the mimimum desired LWT for main zone in heating?
BBR16 activation*
*BBR16 settings are only visible when the language of the user
interface is set to Swedish.
Minimum running time for domestic hot water operation.
How much is the minimum pump PWM value.
--
What is the maximum desired LWT for main zone in heating?
What is the maximum desired LWT for main zone in cooling?
What is the desired eco main LWT in cooling?
What is the desired eco main LWT in heating?
--
--
Anti-recycling time.
Booster heater delay timer.
Additional running time for the maximum running time.
Allow modulation of the LWT to control the room temp?
Leaving water temperature maximum modulation.
What is the maximum desired LWT for add. zone in heating?
What is the mimimum desired LWT for main zone in cooling?
Leaving water temperature overshoot temperature.
4P681797-1 - 2022.01
(*1) 300 Tank_(*2) 500 Tank_
(*3) *X*_(*4) *H*_(*5) *B*_
(*6) *EKECBUA*3V_(*7) *EKECBUA*6V_(*8) *EKECBUA*9W_(*9) BUH less_
(*10) 16P
Содержание ETSHB16P30EF