background image

ERQ125~250A7W1B

Inverter condensing unit

4PW51323-1C – 2018.04

Installation manual

7

7.

L

EAK

 

TEST

 

AND

 

VACUUM

 

DRYING

The units were checked for leaks by the manufacturer.

After connecting the field piping, perform the following inspections.

1

Preparations
Referring to 

figure 12

, connect a nitrogen tank, a cooling tank,

and a vacuum pump to the outdoor unit and perform the
airtightness test and the vacuum drying. The stop valve and
valves A and B in 

figure 12

 should be open and closed as shown

in the table below when performing the airtightness test and
vacuum drying.

2

Airtightness test and vacuum drying

Airtightness test:

Pressurize the liquid and gas pipes to 4.0 MPa (40 bar) (do not
pressurize more than 4.0 MPa (40 bar)). If the pressure does not
drop within 24 hours, the system passes the test. If the pressure
drops, check where the nitrogen leaks from.

Vacuum drying: Use a vacuum pump which can evacuate to 
–100.7 kPa (5 Torr, –755 mm Hg)

1.

Evacuate the system from the liquid and gas pipes by using a
vacuum pump for more than 2 hours and bring the system to 
–100.7 kPa. After keeping the system under that condition for
more than 1 hour, check if the vacuum gauge rises or not. If it
rises, the system may either contain moisture inside or have
leaks.

2.

Following should be executed if there is a possibility of moisture
remaining inside the pipe (if piping work is carried out during the
raining season or over a long period of time, rainwater may enter
the pipe during work).
After evacuating the system for 2 hours, pressurize the system
to 0.05 MPa (vacuum break) with nitrogen gas and evacuate the
system again using the vacuum pump for 1 hour to –100.7 kPa
(vacuum drying). If the system can not be evacuated to 
–100.7 kPa within 2 hours, repeat the operation of vacuum
break and vacuum drying.
Then, after leaving the system in vacuum for 1 hour, confirm that
the vacuum gauge does not rise.

8.

F

IELD

 

WIRING

1

Pressure reducing valve

2

Nitrogen

3

Measuring instrument

4

Tank (siphon system)

5

Vacuum pump

6

Charge hose

7

Service port for adding refrigerant

8

Liquid line stop valve

9

Gas line stop valve

10

Outdoor unit

11

To air handling unit

12

Stop valve service port

13

Dotted lines represent on site piping

14

Valve B

15

Valve C

16

Valve A

State 
of the valves A and B 
and the stop valve

Valve 

A

Valve 

B

Valve 

C

Liquid 

side 

stop 

valve

Gas 

side 

stop 

valve

Performing the 
airtightness test and 
vacuum drying
(Valve A must always be 
shut. Otherwise the 
refrigerant in the unit will 
pour out.)

Close

Open

Open

Close

Close

NOTE

Make sure to perform airtightness test
and vacuum drying using the service
ports of the stop valves of the liquid
side and of the gas side. (For the
service port location, refer to the
"Caution" label attached on the front
panel of the outdoor unit.)

See 

"11.3. Stop valve operation

procedure" on page 13

 for details

on handling the stop valve.

To prevent entry of any contamination and to
prevent insufficient pressure resistance, always
use the special tools dedicated for working with
R410A refrigerant.

NOTE

Make sure to use nitrogen gas. 

All field wiring and components must be installed by a
licensed electrician and must comply with relevant local
and national regulations.

The field wiring must be carried out in accordance with the
wiring diagrams and the instructions given below.

Be sure to use a dedicated power circuit. Never use a
power supply shared by another appliance. This can lead
to electric shock or fire.

Be sure to install an earth leakage circuit breaker.
(Because this unit uses an inverter, install an earth leakage
circuit breaker that is capable of handling high harmonics
in order to prevent malfunctioning of the earth leakage
breaker itself.)

Do not operate until refrigerant piping work is completed.
(If operated before completion of the piping work, the
compressor may break down.)

Never remove a thermistor, sensor, etc., when connecting
power wiring and transmission wiring.
(If operated without thermistor, sensor, etc., the
compressor may break down.)

The reversed phase protection detector of this product only
functions when the product starts up. Consequently,
reversed phase detection is not performed during normal
operation of the product.

The reversed phase protection detector is designed to stop
the product in the event of an abnormality when the
product is started up.

Replace two of the three phases (L1, L2, and L3) during
reverse-phase protection circuit operation.

If the possibility of reversed phase exists after a
momentary blackout and the power goes on and off while
the product is operating, attach a reversed phase
protection circuit locally. Running the product in reversed
phase can break the compressor and other parts.

Means for disconnection must be incorporated in the field
wiring in accordance with the wiring rules.
(An all-pole disconnection switch must be available on the
unit.)

4PWEN51323-1C_2018_04.book  Page 7  Thursday, May 31, 2018  9:12 PM

Содержание ERQ125A7W1B

Страница 1: ...INSTALLATION MANUAL ERQ125A7W1B ERQ200A7W1B ERQ250A7W1B Inverter condensing unit 4PWEN51323 1C_2018_04 book Page 1 Thursday May 31 2018 9 12 PM...

Страница 2: ...0 mm A B C D A B 3 a 10 mm b 300 mm c 10 mm d 500 mm e 20 mm f 600 mm a 50 mm b 100 mm c 50 mm d 500 mm e 100 mm f 500 mm 4 a 10 mm b 300 mm c 10 mm d 500 mm e 20 mm a 50 mm b 100 mm c 50 mm d 500 mm...

Страница 3: ...e av B if lge Sertifikat C som det fremkommer i den Tekniske Konstruksjonsfilen D og gjennom positiv bed mmelse av E Anvendt modul F G Risikokategori H Se ogs neste side 13 jotka on esitetty asiakirja...

Страница 4: ...tuur M C Jahutusaine N Surve turvaseadme seadistus P bar Tootmisnumber ja tootmisaasta vaadake mudeli andmeplaati 21 PS K bar TS TSmin L C TSmax PS M C N P bar 22 Maksimalus leistinas sl gis PS K bar...

Страница 5: ...III net devices This could result in malfunction or breakdown of the total system ERQ125A7W1B ERQ200A7W1B ERQ250A7W1B Inverter condensing unit Installation manual READ THIS MANUAL ATTENTIVELY BEFORE S...

Страница 6: ...ervice space dimensions Refer to figure 2 for impact of wall heights of sides B D on service space dimensions In case of an installation site where only the sides A B have obstacles the wall heights h...

Страница 7: ...eeping proper distances away from stereo equipment personal computers etc See figure 3 In places with weak reception keep distances of 3 m or more to avoid electromagnetic disturbance of other equipme...

Страница 8: ...er the unit in order to prevent infiltration of water coming from under the unit When installed in a corrosive environment use a nut with plastic washer 1 to protect the nut tightening part from rust...

Страница 9: ...lid and make sure that the stop valves are fully closed 2 Connect a charge hose to service ports of all stop valves 3 Recover gas and oil from the pinched piping by using a recovery unit Do not vent g...

Страница 10: ...d Be sure that the field installed piping does not touch other pipes the bottom panel or side panel Especially for the bottom and side connection be sure to protect the piping with suitable insulation...

Страница 11: ...lve Performing the airtightness test and vacuum drying Valve A must always be shut Otherwise the refrigerant in the unit will pour out Close Open Open Close Close NOTE Make sure to perform airtightnes...

Страница 12: ...59 Resistor R95 Resistor current limiting S1NPH Pressure sensor high S1NPL Pressure sensor low S1PH S3PH Pressure switch high SD1 Safety devices input T1A Current sensor A6P A7P V1R Power module A4P A...

Страница 13: ...ngerous when struck by lightning due to abnormal rise in electrical potential in the grounding This unit uses an inverter and therefore generates noise which will have to be reduced to avoid interferi...

Страница 14: ...terials to be prepared on site 2 3 1 Use a power wire pipe for the power wiring Outside the unit make sure the weak low voltage electric wiring i e for the remote control between units etc and the hig...

Страница 15: ...e breaker 4 Grounding wire 5 Power supply terminal block 6 Connect each power wire RED to L1 WHT to L2 BLK to L3 and BLU to N 7 Ground wire GRN YLW 8 Clamp the power wire to the plastic bracket using...

Страница 16: ...ctory charged but depending on the length of the piping when installed the outdoor unit may require additional charging For charging the additional refrigerant follow the procedure as described in thi...

Страница 17: ...n page 12 are completed If the stop valve is left open without turning on the power it may cause refrigerant to build up in the compressor leading to insulation degradation Always use a charge hose fo...

Страница 18: ...Mode Ready Error Cooling Heating changeover Low noise Demand Multi Indivi dual Bulk master Bulk slave HAP H1P H2P H3P H4P H5P H6P H7P H8P Single outdoor unit system c x x w x x x x x Error code P8 re...

Страница 19: ...ll point pen to avoid touching live parts Make sure to re attach the inspection cover 1 into the switch box cover 2 after the job is finished WARNING ELECTRIC SHOCK Caution when performing service to...

Страница 20: ...ither one of the possible settings as shown below in the field marked 2 Push the button and the setting is defined 1 LED H1 8P 2 Push button switches BS1 BS5 3 Dip switch 1 DS1 1 4 4 Dip switch 2 DS2...

Страница 21: ...rging operation not applicable B refrigerant recovery operation vacuuming operation C setting of high static pressure D automatic low noise operation setting at nighttime E low noise operation level s...

Страница 22: ...ng after abnormal completion of the test operation The test operation is only completed if there is no malfunction code displayed on the remote controller In case of a displayed malfunction code perfo...

Страница 23: ...ing maximum concentration Check the maximum concentration level in accordance with steps 1 to 4 below and take whatever action is necessary to comply 1 Calculate the amount of refrigerant kg charged t...

Страница 24: ...4PWEN51323 1C_2018_04 book Page 1 Thursday May 31 2018 9 12 PM...

Страница 25: ...4PWEN51323 1C_2018_04 book Page 2 Thursday May 31 2018 9 12 PM...

Страница 26: ...4PWEN51323 1C_2018_04 book Page 4 Thursday May 31 2018 9 12 PM...

Страница 27: ...UNIT A1P 3 2 F1 F2 13 L1 L2 L3 N 1 3 4 2 6 5 7 8 9 10 11 14 1 9 2 3 8 L1 L2 TO IN D F1 F2 A1P F1 F2 L N P1 P2 2 3 6 7 4 5 15 1 2 5 6 4 3 7 8 21 12 13 14 15 16 5 1 7 10 3 2 9 6 6 6 6 7 4 11 8 6 6 24 13...

Страница 28: ...4PW51323 1C 2018 04 Copyright 2009 Daikin 4PW51323 1 C 0000000I 4PWEN51323 1C_2018_04 book Page 1 Thursday May 31 2018 9 12 PM...

Отзывы: