background image

Installation manual

8

ERQ125~250A7W1B

Inverter condensing unit

4PW51323-1C – 2018.04

8.1.

Internal wiring – Parts table

Refer to the wiring diagram sticker on the unit. The abbreviations
used are listed below:
A1P~A7P............. Printed circuit board
BS1~BS5 ............ Push button switch (mode, set, return, test, reset)
C1,C63,C66 ........ Capacitor
DS1,DS2 ............. Dip switch
E1HC~E3HC ....... Crankcase heater
F1U ..................... Fuse (650 V, 8 A, B) (A4P) (A8P)
F1U,F2U.............. Fuse (250 V, 3.15 A, T) (A1P)
F5U ..................... Field fuse
F400U ................. Fuse (250 V, 6.3 A, T) (A2P)
H1P~H8P ............ Pilot lamp (service monitor - orange)

H2P: Under preparation or in test operation when

blinking

H2P: Malfunction detection when light up

HAP..................... Pilot lamp (service monitor - green)
K1........................ Magnetic relay
K2........................ Magnetic contactor (MIC)
K2M,K3M ............ Magnetic contactor (M2C,M3C) (only for ERQ250)
K1R,K2R ............. Magnetic relay (K2M,K3M)
K3R~K5R ............ Magnetic relay (Y1S~Y3S)
K6R~K9R ............ Magnetic relay (E1HC~E3HC)
L1R...................... Reactor
M1C~M3C ........... Motor (compressor)
M1F,M2F ............. Motor (fan)
PS ....................... Switching power supply (A1P,A3P)
Q1DI.................... Earth leakage breaker (field supply)
Q1RP .................. Phase reversal detection circuit
R1T ..................... Thermistor (fin) (A2P)
R1T ..................... Thermistor (air) (A1P)
R2T ..................... Thermistor (suction)
R4T ..................... Thermistor (coil-deicer)
R5T ..................... Thermistor (coil-outlet)
R6T ..................... Thermistor (liquid-pipe receiver)
R7T ..................... Thermistor (accumulator)
R10...................... Resistor (current sensor) (A4P) (A8P)
R31T~R33T......... Thermistor (discharge) (M1C~M3C)
R50,R59 .............. Resistor
R95...................... Resistor (current limiting)
S1NPH ................ Pressure sensor (high)
S1NPL................. Pressure sensor (low)
S1PH,S3PH ........ Pressure switch (high)
SD1 ..................... Safety devices input
T1A...................... Current sensor (A6P,A7P)
V1R ..................... Power module (A4P,A8P)
V1R,V2R ............. Power module (A3P)
X1A,X4A.............. Connector (M1F,M2F)
X1M..................... Terminal strip (power supply)
X1M..................... Terminal strip (control) (A1P)
X1M..................... Terminal strip (A5P)
Y1E,Y2E.............. Expansion valve (electronic type) (main, subcool)
Y1S ..................... Solenoid valve (hotgas bypass)
Y2S ..................... Solenoid valve (oil return)
Y3S ..................... Solenoid valve (4 way valve)
Y4S ..................... Solenoid valve (injection)
Z1C~Z7C............. Noise filter (ferrite core)
Z1F...................... Noise filter (with surge absorber)

L1,L2,L3 .............. Live
N.......................... Neutral

............ Field wiring

............... Terminal strip

....................... Connector

...................... Terminal

....................... Protective earth (screw)

BLK...................... Black
BLU ..................... Blue
BRN..................... Brown
GRN .................... Green
GRY..................... Grey
ORG .................... Orange
PNK ..................... Pink
RED..................... Red
WHT .................... White
YLW..................... Yellow

8.2.

Optional parts cool/heat selector

S1S...................... Selector switch (fan, cool/heat)
S2S...................... Selector switch (cool/heat)

NOTE

This wiring diagram only applies to the outdoor
unit.

When using the option adaptor, refer to the
installation manual.

Refer to the installation manual, for connection
wiring to indoor-outdoor transmission F1-F2, and
on how to use BS1~BS5 and DS1, DS2 switch.

Do not operate the unit by short-circuiting
protection device S1PH.

NOTE

Use copper conductors only.

For connection wiring to the central remote
controller, refer to the installation manual of the
central remote controller.

Use insulated wire for the power cord.

4PWEN51323-1C_2018_04.book  Page 8  Thursday, May 31, 2018  9:12 PM

Содержание ERQ125A7W1B

Страница 1: ...INSTALLATION MANUAL ERQ125A7W1B ERQ200A7W1B ERQ250A7W1B Inverter condensing unit 4PWEN51323 1C_2018_04 book Page 1 Thursday May 31 2018 9 12 PM...

Страница 2: ...0 mm A B C D A B 3 a 10 mm b 300 mm c 10 mm d 500 mm e 20 mm f 600 mm a 50 mm b 100 mm c 50 mm d 500 mm e 100 mm f 500 mm 4 a 10 mm b 300 mm c 10 mm d 500 mm e 20 mm a 50 mm b 100 mm c 50 mm d 500 mm...

Страница 3: ...e av B if lge Sertifikat C som det fremkommer i den Tekniske Konstruksjonsfilen D og gjennom positiv bed mmelse av E Anvendt modul F G Risikokategori H Se ogs neste side 13 jotka on esitetty asiakirja...

Страница 4: ...tuur M C Jahutusaine N Surve turvaseadme seadistus P bar Tootmisnumber ja tootmisaasta vaadake mudeli andmeplaati 21 PS K bar TS TSmin L C TSmax PS M C N P bar 22 Maksimalus leistinas sl gis PS K bar...

Страница 5: ...III net devices This could result in malfunction or breakdown of the total system ERQ125A7W1B ERQ200A7W1B ERQ250A7W1B Inverter condensing unit Installation manual READ THIS MANUAL ATTENTIVELY BEFORE S...

Страница 6: ...ervice space dimensions Refer to figure 2 for impact of wall heights of sides B D on service space dimensions In case of an installation site where only the sides A B have obstacles the wall heights h...

Страница 7: ...eeping proper distances away from stereo equipment personal computers etc See figure 3 In places with weak reception keep distances of 3 m or more to avoid electromagnetic disturbance of other equipme...

Страница 8: ...er the unit in order to prevent infiltration of water coming from under the unit When installed in a corrosive environment use a nut with plastic washer 1 to protect the nut tightening part from rust...

Страница 9: ...lid and make sure that the stop valves are fully closed 2 Connect a charge hose to service ports of all stop valves 3 Recover gas and oil from the pinched piping by using a recovery unit Do not vent g...

Страница 10: ...d Be sure that the field installed piping does not touch other pipes the bottom panel or side panel Especially for the bottom and side connection be sure to protect the piping with suitable insulation...

Страница 11: ...lve Performing the airtightness test and vacuum drying Valve A must always be shut Otherwise the refrigerant in the unit will pour out Close Open Open Close Close NOTE Make sure to perform airtightnes...

Страница 12: ...59 Resistor R95 Resistor current limiting S1NPH Pressure sensor high S1NPL Pressure sensor low S1PH S3PH Pressure switch high SD1 Safety devices input T1A Current sensor A6P A7P V1R Power module A4P A...

Страница 13: ...ngerous when struck by lightning due to abnormal rise in electrical potential in the grounding This unit uses an inverter and therefore generates noise which will have to be reduced to avoid interferi...

Страница 14: ...terials to be prepared on site 2 3 1 Use a power wire pipe for the power wiring Outside the unit make sure the weak low voltage electric wiring i e for the remote control between units etc and the hig...

Страница 15: ...e breaker 4 Grounding wire 5 Power supply terminal block 6 Connect each power wire RED to L1 WHT to L2 BLK to L3 and BLU to N 7 Ground wire GRN YLW 8 Clamp the power wire to the plastic bracket using...

Страница 16: ...ctory charged but depending on the length of the piping when installed the outdoor unit may require additional charging For charging the additional refrigerant follow the procedure as described in thi...

Страница 17: ...n page 12 are completed If the stop valve is left open without turning on the power it may cause refrigerant to build up in the compressor leading to insulation degradation Always use a charge hose fo...

Страница 18: ...Mode Ready Error Cooling Heating changeover Low noise Demand Multi Indivi dual Bulk master Bulk slave HAP H1P H2P H3P H4P H5P H6P H7P H8P Single outdoor unit system c x x w x x x x x Error code P8 re...

Страница 19: ...ll point pen to avoid touching live parts Make sure to re attach the inspection cover 1 into the switch box cover 2 after the job is finished WARNING ELECTRIC SHOCK Caution when performing service to...

Страница 20: ...ither one of the possible settings as shown below in the field marked 2 Push the button and the setting is defined 1 LED H1 8P 2 Push button switches BS1 BS5 3 Dip switch 1 DS1 1 4 4 Dip switch 2 DS2...

Страница 21: ...rging operation not applicable B refrigerant recovery operation vacuuming operation C setting of high static pressure D automatic low noise operation setting at nighttime E low noise operation level s...

Страница 22: ...ng after abnormal completion of the test operation The test operation is only completed if there is no malfunction code displayed on the remote controller In case of a displayed malfunction code perfo...

Страница 23: ...ing maximum concentration Check the maximum concentration level in accordance with steps 1 to 4 below and take whatever action is necessary to comply 1 Calculate the amount of refrigerant kg charged t...

Страница 24: ...4PWEN51323 1C_2018_04 book Page 1 Thursday May 31 2018 9 12 PM...

Страница 25: ...4PWEN51323 1C_2018_04 book Page 2 Thursday May 31 2018 9 12 PM...

Страница 26: ...4PWEN51323 1C_2018_04 book Page 4 Thursday May 31 2018 9 12 PM...

Страница 27: ...UNIT A1P 3 2 F1 F2 13 L1 L2 L3 N 1 3 4 2 6 5 7 8 9 10 11 14 1 9 2 3 8 L1 L2 TO IN D F1 F2 A1P F1 F2 L N P1 P2 2 3 6 7 4 5 15 1 2 5 6 4 3 7 8 21 12 13 14 15 16 5 1 7 10 3 2 9 6 6 6 6 7 4 11 8 6 6 24 13...

Страница 28: ...4PW51323 1C 2018 04 Copyright 2009 Daikin 4PW51323 1 C 0000000I 4PWEN51323 1C_2018_04 book Page 1 Thursday May 31 2018 9 12 PM...

Отзывы: