background image

ERQ125~250A7W1B

Inverter condensing unit

4PW51323-1C – 2018.04

Installation manual

15

12. B

EFORE

 

OPERATION

12.1.

Service precautions

Pay attention to the fan.

 It is dangerous to inspect the unit while the

fan is running. Be sure to turn off the main switch and to remove the
fuses from the control circuit located in the outdoor unit.

12.2.

Checks before initial start-up

After the installation, check the following before switching on the
circuit breaker:

1

The position of the switches that require an initial setting
Make sure that switches are set according to your application
needs before turning the power supply on.

2

Power supply wiring and transmission wiring
Use a designated power supply and transmission wiring and
make sure that it has been carried out according to the
instructions described in this manual, according to the wiring
diagrams and according to local and national regulations.

3

Pipe sizes and pipe insulation
Make sure that correct pipe sizes are installed and that the
insulation work is properly executed.

4

Air tight test and vacuum drying
Make sure the air tight test and vacuum drying were completed.

5

Additional refrigerant charge
The amount of refrigerant to be added to the unit should be
written on the included "Added Refrigerant" plate and attached
to the rear side of the front cover.

6

Insulation test of the main power circuit
Using a megatester for 500 V, check that the insulation
resistance of 2 M

 or more is attained by applying a voltage of

500 V DC between power terminals and earth. Never use the
megatester for the transmission wiring.

7

Installation date and field setting
Be sure to keep record of the installation date on the sticker on
the rear of the upper front panel according to EN60335-2-40.
and keep record of the contents of the field setting.

12.3.

Field setting

If required, carry out field settings according to the following
instructions. Refer to the service manual for more details.

Opening the switch box and handling the switches

When carrying out field settings, remove
the inspection cover (1).

Operate the switches with an insulated
stick (such as a ball-point pen) to avoid
touching live parts.

Make sure to re-attach the inspection cover (1) into the switch box
cover (2) after the job is finished.

WARNING: ELECTRIC SHOCK 

Caution when performing service to inverter
equipment

1

Do not open the electric box cover for 10 minutes after
the power supply is turned off.

2

Measure the voltage between terminals on the
terminal block for power supply with a tester and
confirm that the power supply is shut off.
In addition, measure the points, as shown in the figure
below, with a tester and confirm that the voltage of the
capacitor in the main circuit is less than 50 V DC.

3

To prevent damaging the PC-board, touch a
noncoated metal part to eliminate static electricity
before pulling out or plugging in connectors.

4

The performing of the service to the inverter
equipment must be started after the junction
connectors X1A and X2A for the fan motors in the
outdoor unit are been pulled out. Be carefull not to
touch the live parts.
(If a fan rotates due to strong wind, it may store
electricity in the capacitor or in the main circuit and
cause electric shock.)

5

After the service is finished, plug the junction
connecter back in. Otherwise the error code 

E7

 will be

displayed on the remote controller and normal
operation will not be performed.

For details refer to the wiring diagram labeled on the back
of the electric box cover.

NOTE

Play it safe!

For protection of the PCB, touch the switch box casing
by hand in order to eliminate static electricity from your
body before performing service.

A2P

A1P

A3P

TP1 TP2

NOTE

Remark that during the first running period of the unit,
required power input may be higher than stated on the
nameplate of the unit. This phenomenon originates
from the compressor that needs elapse of a 50 hours
run in period before reaching smooth operation and
stable power consumption.

Make sure that the circuit breaker on the power supply
panel of the installation is switched off.

Attach the power wire securely.

Introducing power with a missing N-phase or with a
mistaken N-phase will break the equipment.

NOTE

Make sure that all outside panels, except for the panel
on the electric box, are closed while working.

Close the lid of the electric box firmly before turning on
the power.

2

1

4PWEN51323-1C_2018_04.book  Page 15  Thursday, May 31, 2018  9:12 PM

Содержание ERQ125A7W1B

Страница 1: ...INSTALLATION MANUAL ERQ125A7W1B ERQ200A7W1B ERQ250A7W1B Inverter condensing unit 4PWEN51323 1C_2018_04 book Page 1 Thursday May 31 2018 9 12 PM...

Страница 2: ...0 mm A B C D A B 3 a 10 mm b 300 mm c 10 mm d 500 mm e 20 mm f 600 mm a 50 mm b 100 mm c 50 mm d 500 mm e 100 mm f 500 mm 4 a 10 mm b 300 mm c 10 mm d 500 mm e 20 mm a 50 mm b 100 mm c 50 mm d 500 mm...

Страница 3: ...e av B if lge Sertifikat C som det fremkommer i den Tekniske Konstruksjonsfilen D og gjennom positiv bed mmelse av E Anvendt modul F G Risikokategori H Se ogs neste side 13 jotka on esitetty asiakirja...

Страница 4: ...tuur M C Jahutusaine N Surve turvaseadme seadistus P bar Tootmisnumber ja tootmisaasta vaadake mudeli andmeplaati 21 PS K bar TS TSmin L C TSmax PS M C N P bar 22 Maksimalus leistinas sl gis PS K bar...

Страница 5: ...III net devices This could result in malfunction or breakdown of the total system ERQ125A7W1B ERQ200A7W1B ERQ250A7W1B Inverter condensing unit Installation manual READ THIS MANUAL ATTENTIVELY BEFORE S...

Страница 6: ...ervice space dimensions Refer to figure 2 for impact of wall heights of sides B D on service space dimensions In case of an installation site where only the sides A B have obstacles the wall heights h...

Страница 7: ...eeping proper distances away from stereo equipment personal computers etc See figure 3 In places with weak reception keep distances of 3 m or more to avoid electromagnetic disturbance of other equipme...

Страница 8: ...er the unit in order to prevent infiltration of water coming from under the unit When installed in a corrosive environment use a nut with plastic washer 1 to protect the nut tightening part from rust...

Страница 9: ...lid and make sure that the stop valves are fully closed 2 Connect a charge hose to service ports of all stop valves 3 Recover gas and oil from the pinched piping by using a recovery unit Do not vent g...

Страница 10: ...d Be sure that the field installed piping does not touch other pipes the bottom panel or side panel Especially for the bottom and side connection be sure to protect the piping with suitable insulation...

Страница 11: ...lve Performing the airtightness test and vacuum drying Valve A must always be shut Otherwise the refrigerant in the unit will pour out Close Open Open Close Close NOTE Make sure to perform airtightnes...

Страница 12: ...59 Resistor R95 Resistor current limiting S1NPH Pressure sensor high S1NPL Pressure sensor low S1PH S3PH Pressure switch high SD1 Safety devices input T1A Current sensor A6P A7P V1R Power module A4P A...

Страница 13: ...ngerous when struck by lightning due to abnormal rise in electrical potential in the grounding This unit uses an inverter and therefore generates noise which will have to be reduced to avoid interferi...

Страница 14: ...terials to be prepared on site 2 3 1 Use a power wire pipe for the power wiring Outside the unit make sure the weak low voltage electric wiring i e for the remote control between units etc and the hig...

Страница 15: ...e breaker 4 Grounding wire 5 Power supply terminal block 6 Connect each power wire RED to L1 WHT to L2 BLK to L3 and BLU to N 7 Ground wire GRN YLW 8 Clamp the power wire to the plastic bracket using...

Страница 16: ...ctory charged but depending on the length of the piping when installed the outdoor unit may require additional charging For charging the additional refrigerant follow the procedure as described in thi...

Страница 17: ...n page 12 are completed If the stop valve is left open without turning on the power it may cause refrigerant to build up in the compressor leading to insulation degradation Always use a charge hose fo...

Страница 18: ...Mode Ready Error Cooling Heating changeover Low noise Demand Multi Indivi dual Bulk master Bulk slave HAP H1P H2P H3P H4P H5P H6P H7P H8P Single outdoor unit system c x x w x x x x x Error code P8 re...

Страница 19: ...ll point pen to avoid touching live parts Make sure to re attach the inspection cover 1 into the switch box cover 2 after the job is finished WARNING ELECTRIC SHOCK Caution when performing service to...

Страница 20: ...ither one of the possible settings as shown below in the field marked 2 Push the button and the setting is defined 1 LED H1 8P 2 Push button switches BS1 BS5 3 Dip switch 1 DS1 1 4 4 Dip switch 2 DS2...

Страница 21: ...rging operation not applicable B refrigerant recovery operation vacuuming operation C setting of high static pressure D automatic low noise operation setting at nighttime E low noise operation level s...

Страница 22: ...ng after abnormal completion of the test operation The test operation is only completed if there is no malfunction code displayed on the remote controller In case of a displayed malfunction code perfo...

Страница 23: ...ing maximum concentration Check the maximum concentration level in accordance with steps 1 to 4 below and take whatever action is necessary to comply 1 Calculate the amount of refrigerant kg charged t...

Страница 24: ...4PWEN51323 1C_2018_04 book Page 1 Thursday May 31 2018 9 12 PM...

Страница 25: ...4PWEN51323 1C_2018_04 book Page 2 Thursday May 31 2018 9 12 PM...

Страница 26: ...4PWEN51323 1C_2018_04 book Page 4 Thursday May 31 2018 9 12 PM...

Страница 27: ...UNIT A1P 3 2 F1 F2 13 L1 L2 L3 N 1 3 4 2 6 5 7 8 9 10 11 14 1 9 2 3 8 L1 L2 TO IN D F1 F2 A1P F1 F2 L N P1 P2 2 3 6 7 4 5 15 1 2 5 6 4 3 7 8 21 12 13 14 15 16 5 1 7 10 3 2 9 6 6 6 6 7 4 11 8 6 6 24 13...

Страница 28: ...4PW51323 1C 2018 04 Copyright 2009 Daikin 4PW51323 1 C 0000000I 4PWEN51323 1C_2018_04 book Page 1 Thursday May 31 2018 9 12 PM...

Отзывы: