background image

ERQ125~250A7W1B

Inverter condensing unit

4PW51323-1C – 2018.04

Installation manual

11

Setting the cool/heat operation

1

Performing cool/heat setting with the remote controller
connected to the control box.
Keep the cool/heat selector switch (DS1) on the outdoor unit PC
board at the factory setting position IN/D UNIT. 

(See figure 19)

2

Performing cool/heat setting with the cool/heat selector.
Connect the cool/heat selector remote controller (optional) to the
A/B/C terminals and set the cool/heat selector switch (DS1) on
the outdoor unit PC board (A1P) to OUT/D UNIT. 

(See figure 20)

3

Perform cool/heat setting with the field supplied controller. 
Set the cool/heat selector switch (DS1) on the outdoor unit PC
board (A1P) to OUT/D UNIT.

 

(See figure 20)

.

Connect the A/B/C terminals with the field supplied controller so
that:
- A/B/C terminals are not connected for cooling operation
- A and C terminals are short-circuited for heating operation
- B and C are short-circuited for fan only operation

8.8.

Field line connection: power wiring

The power cord must be clamped to the plastic bracket using field
supplied clamp material.

The green and yellow striped wrapped wires must be used for
grounding. 

(See figure 13)

Be sure to keep the power line and transmission line
apart from each other.

Be careful about polarity of the transmission line.

Make sure that the transmission line is clamped as
shown in 

figure 20

.

Check that wiring lines do not make contact with
refrigerant piping.

Firmly close the lid and arrange the electrical wires so
as to prevent the lid or other parts from coming loose.

When you do not use a wire conduit, be sure to
protect the wires with vinyl tubes etc, to prevent the
edge of the knock-out hole from cutting the wires.

1

Remote controller

1

Cool/heat selector

For low-noise operation, it is necessary to get the optional
'External control adaptor for outdoor unit' (DTA104A61/62).

For details, see the installation manual attached to the
adaptor.

1

Power supply (400 V, 3N~ 50 Hz)

2

Fuse

3

Earth leakage breaker

4

Grounding wire

5

Power supply terminal block

6

Connect each power wire
RED to L1, WHT to L2, BLK to L3 and BLU to N

7

Ground wire (GRN/YLW)

8

Clamp the power wire to the plastic bracket using a field supplied 
clamp to prevent external force being applied to the terminal. 

9

Clamp (field supply)

10

Cup washer

11

When connecting the earth wire, it is recommended to perform 
curling.

When routing ground wires, secure clearance of
50 mm or more away from compressor lead wires.
Failure to observe this instruction properly may
adversely effect correct operation of other units
connected to the same ground.

When connecting the power supply cord, the earth
connection must be made before the current-carrying
connections are established. When disconnecting the
power supply cord, the current-carrying connections
must be separated before the earth connection is.
Length of the conductors between the power supply
cord anchorage and the terminal block itself must be
such that the current-carrying conductors are
tautened before the earthing conductor is in case the
power supply cord is pulled loose from the cord
anchorage.

Precautions when laying power wiring

Do not connect wiring of different thicknesses to the
power terminal block. (Slack in the power wiring may
cause abnormal heat.)

When connecting wiring which is the same thickness,
do as shown in the figure below.

For wiring, use the designated power wire and
connect firmly, then secure to prevent outside
pressure being exerted on the terminal board.

Use an appropriate screwdriver for tightening the
terminal screws. A screwdriver with a small head will
strip the head and make proper tightening impossible.

Over-tightening the terminal screws may break them.

See the table below for tightening torque for the
terminal screws.

Recommendations when connecting the ground

When pulling the ground wire out, wire it so that it comes
through the cut out section of the cup washer. (An
improper ground connection may prevent a good ground
from being achieved.) 

(See figure 13)

Tightening torque (N•m)

M8 (Power terminal block)

5.5~7.3

M8 (Ground)

M3 (Inter-unit wiring terminal block)

0.8~0.97

4PWEN51323-1C_2018_04.book  Page 11  Thursday, May 31, 2018  9:12 PM

Содержание ERQ125A7W1B

Страница 1: ...INSTALLATION MANUAL ERQ125A7W1B ERQ200A7W1B ERQ250A7W1B Inverter condensing unit 4PWEN51323 1C_2018_04 book Page 1 Thursday May 31 2018 9 12 PM...

Страница 2: ...0 mm A B C D A B 3 a 10 mm b 300 mm c 10 mm d 500 mm e 20 mm f 600 mm a 50 mm b 100 mm c 50 mm d 500 mm e 100 mm f 500 mm 4 a 10 mm b 300 mm c 10 mm d 500 mm e 20 mm a 50 mm b 100 mm c 50 mm d 500 mm...

Страница 3: ...e av B if lge Sertifikat C som det fremkommer i den Tekniske Konstruksjonsfilen D og gjennom positiv bed mmelse av E Anvendt modul F G Risikokategori H Se ogs neste side 13 jotka on esitetty asiakirja...

Страница 4: ...tuur M C Jahutusaine N Surve turvaseadme seadistus P bar Tootmisnumber ja tootmisaasta vaadake mudeli andmeplaati 21 PS K bar TS TSmin L C TSmax PS M C N P bar 22 Maksimalus leistinas sl gis PS K bar...

Страница 5: ...III net devices This could result in malfunction or breakdown of the total system ERQ125A7W1B ERQ200A7W1B ERQ250A7W1B Inverter condensing unit Installation manual READ THIS MANUAL ATTENTIVELY BEFORE S...

Страница 6: ...ervice space dimensions Refer to figure 2 for impact of wall heights of sides B D on service space dimensions In case of an installation site where only the sides A B have obstacles the wall heights h...

Страница 7: ...eeping proper distances away from stereo equipment personal computers etc See figure 3 In places with weak reception keep distances of 3 m or more to avoid electromagnetic disturbance of other equipme...

Страница 8: ...er the unit in order to prevent infiltration of water coming from under the unit When installed in a corrosive environment use a nut with plastic washer 1 to protect the nut tightening part from rust...

Страница 9: ...lid and make sure that the stop valves are fully closed 2 Connect a charge hose to service ports of all stop valves 3 Recover gas and oil from the pinched piping by using a recovery unit Do not vent g...

Страница 10: ...d Be sure that the field installed piping does not touch other pipes the bottom panel or side panel Especially for the bottom and side connection be sure to protect the piping with suitable insulation...

Страница 11: ...lve Performing the airtightness test and vacuum drying Valve A must always be shut Otherwise the refrigerant in the unit will pour out Close Open Open Close Close NOTE Make sure to perform airtightnes...

Страница 12: ...59 Resistor R95 Resistor current limiting S1NPH Pressure sensor high S1NPL Pressure sensor low S1PH S3PH Pressure switch high SD1 Safety devices input T1A Current sensor A6P A7P V1R Power module A4P A...

Страница 13: ...ngerous when struck by lightning due to abnormal rise in electrical potential in the grounding This unit uses an inverter and therefore generates noise which will have to be reduced to avoid interferi...

Страница 14: ...terials to be prepared on site 2 3 1 Use a power wire pipe for the power wiring Outside the unit make sure the weak low voltage electric wiring i e for the remote control between units etc and the hig...

Страница 15: ...e breaker 4 Grounding wire 5 Power supply terminal block 6 Connect each power wire RED to L1 WHT to L2 BLK to L3 and BLU to N 7 Ground wire GRN YLW 8 Clamp the power wire to the plastic bracket using...

Страница 16: ...ctory charged but depending on the length of the piping when installed the outdoor unit may require additional charging For charging the additional refrigerant follow the procedure as described in thi...

Страница 17: ...n page 12 are completed If the stop valve is left open without turning on the power it may cause refrigerant to build up in the compressor leading to insulation degradation Always use a charge hose fo...

Страница 18: ...Mode Ready Error Cooling Heating changeover Low noise Demand Multi Indivi dual Bulk master Bulk slave HAP H1P H2P H3P H4P H5P H6P H7P H8P Single outdoor unit system c x x w x x x x x Error code P8 re...

Страница 19: ...ll point pen to avoid touching live parts Make sure to re attach the inspection cover 1 into the switch box cover 2 after the job is finished WARNING ELECTRIC SHOCK Caution when performing service to...

Страница 20: ...ither one of the possible settings as shown below in the field marked 2 Push the button and the setting is defined 1 LED H1 8P 2 Push button switches BS1 BS5 3 Dip switch 1 DS1 1 4 4 Dip switch 2 DS2...

Страница 21: ...rging operation not applicable B refrigerant recovery operation vacuuming operation C setting of high static pressure D automatic low noise operation setting at nighttime E low noise operation level s...

Страница 22: ...ng after abnormal completion of the test operation The test operation is only completed if there is no malfunction code displayed on the remote controller In case of a displayed malfunction code perfo...

Страница 23: ...ing maximum concentration Check the maximum concentration level in accordance with steps 1 to 4 below and take whatever action is necessary to comply 1 Calculate the amount of refrigerant kg charged t...

Страница 24: ...4PWEN51323 1C_2018_04 book Page 1 Thursday May 31 2018 9 12 PM...

Страница 25: ...4PWEN51323 1C_2018_04 book Page 2 Thursday May 31 2018 9 12 PM...

Страница 26: ...4PWEN51323 1C_2018_04 book Page 4 Thursday May 31 2018 9 12 PM...

Страница 27: ...UNIT A1P 3 2 F1 F2 13 L1 L2 L3 N 1 3 4 2 6 5 7 8 9 10 11 14 1 9 2 3 8 L1 L2 TO IN D F1 F2 A1P F1 F2 L N P1 P2 2 3 6 7 4 5 15 1 2 5 6 4 3 7 8 21 12 13 14 15 16 5 1 7 10 3 2 9 6 6 6 6 7 4 11 8 6 6 24 13...

Страница 28: ...4PW51323 1C 2018 04 Copyright 2009 Daikin 4PW51323 1 C 0000000I 4PWEN51323 1C_2018_04 book Page 1 Thursday May 31 2018 9 12 PM...

Отзывы: